PF Power Fittings Technical Reference

TL T Clamp, U-Bolt Type (TLL)

TL T clamp, U-bolt type

Models: TL-11 to TL-55 (15 sizes) · Reference Weight: 0.71–2.6 kg · Body: aluminium alloy, hardware hot-dip galvanised

A U-Bolt Over Each Leg

A U-bolt passes under the conductor and pulls a keeper plate down on top of it, two nuts on the keeper. The branch leaves the main body at 90°, and both legs close the same way.

The TL-53, TL-54 and TL-55 numbers are also carried by a separate clamp-plate series for 120–630 mm² conductor, built to its own drawing. Quote the type with the model: TL clamp-plate T clamp.

Two Digits, Five Steps

The two digits are not a sequence. The first is the main line conductor range, the second is the branch range, and both use the same five-step ladder:

Digit Conductor diameter Body bore Ø
1 7.5 – 10.0 mm 16 mm
2 10.8 – 14.0 mm 16 mm
3 14.5 – 17.5 mm 23 mm
4 18.0 – 22.4 mm 23 mm
5 22.4 – 26.0 mm 26 mm

So TL-42 is a 18.0–22.4 mm main line with a 10.8–14.0 mm branch.

The table is a complete triangle, and that is the whole story. Fifteen rows exist and fifteen combinations are possible when the branch is never larger than the main line: 1+2+3+4+5 = 15. There is no TL-12, no TL-23, no TL-15 anywhere in the catalogue. The range simply stops at an equal-leg tap.

Look down the Ø columns and the 15 rows collapse into three bore sizes: digits 1 and 2 share the 16 mm bore, digits 3 and 4 share 23 mm, digit 5 takes 26 mm. That is why Ø1 on a TL-21 is identical to Ø1 on a TL-11 even though the main line is a size heavier.

Two rows step down instead of up and are worth knowing about: TL-33 at 1.05 kg against TL-32 at 1.06, and TL-43 at 1.12 against TL-42 at 1.13. Use the row weight as printed for freight.

H and L: Read the Row, Do Not Interpolate

Overall length runs 112 to 125 mm and does not climb with conductor size. TL-51, a 22.4–26.0 mm main line with a 7.5–10.0 mm branch, is 114 mm long — shorter than TL-31 at 119 mm, two steps smaller on the main line.

H and L are set by the body casting and the branch bore, so two fittings that take the same branch need not share an outline.

Do not design string spacing or phase clearance off a linear interpolation of H and L. Read the row for the exact model you are ordering, or ask us for the outline drawing of that combination.

Weight

Reference weight follows the body and the U-bolt sets, not the conductor size:

  • 0.71 kg on the 16 mm body (digits 1–2)
  • 1.05–1.17 kg on the 23 mm body (digits 3–4)
  • 2.5–2.6 kg on the 26 mm body (digit 5)

Inside one body the branch digit changes almost nothing: TL-51 through TL-55 all sit at 2.5–2.6 kg while their branch range runs from 7.5 mm to 26 mm — a factor of three and a half in conductor diameter for the same body.

When you are costing freight, use the row weight; do not scale from the conductor size.

Technical Parameters

TL T clamp, U-bolt type, dimensions

ModelApplicable ConductorMain Dimensions (mm)Reference Weight (kg)
BusbarDown LeadØ1Ø2HL
TL-117.5~10.07.5~10.016161441120.71
TL-2110.8~14.07.5~10.016161441120.78
TL-2210.8~14.010.8~14.016161441120.79
TL-3114.5~17.57.5~10.023161461191.07
TL-3214.5~17.510.8~14.023161461191.06
TL-3314.5~17.514.5~17.523231521211.05
TL-4118.0~22.47.5~10.023161461191.13
TL-4218.0~22.410.8~14.023161461191.13
TL-4318.0~22.414.5~17.523231521211.12
TL-4418.0~22.418.0~22.423231521211.17
TL-5122.4~26.07.5~10.026161581142.6
TL-5222.4~26.010.8~14.026161581142.5
TL-5322.4~26.014.5~17.526231611212.5
TL-5422.4~26.018.0~22.426231611212.5
TL-5522.4~26.022.4~26.026261641252.5

The 120–630 mm² clamp-plate series: TL clamp-plate T clamp. The compression version for the same job: TY hydraulic T clamp, ACSR to 800 mm². Where the branch is a second conductor running in parallel rather than a tap: TLS double conductor T clamp. Equal-diameter taps on expanded conductor: TL equal diameter T clamp.

Note: U-bolt type, fifteen sizes for 7.5–26 mm conductor. The digits read main line then branch, and the branch never exceeds the run. State whether the branch is aluminium or ACSR when ordering.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: