Models: 37 sizes (28 conductor designations) · Reference Weight: 0.4–5.5 kg standard, 3.5–7.0 kg heat-resistant · Body: aluminium, pressed
One Die per Aluminium Section
This is the fact that saves the most money on a TY order. L1, L2 and D depend on the aluminium section only. The steel core changes nothing.
| Conductor | L1 | L2 | D | Weight |
|---|---|---|---|---|
| LGJ-185/10 | 125 | 90 | 32 | 1.4 |
| LGJ-185/25 | 125 | 90 | 32 | 1.4 |
| LGJ-185/30 | 125 | 90 | 32 | 1.4 |
| LGJ-400/20 | 155 | 120 | 45 | 1.9 |
| LGJ-400/35 | 155 | 120 | 45 | 1.9 |
| LGJ-400/50 | 155 | 120 | 45 | 1.9 |
| LGJ-400/65 | 155 | 120 | 45 | 1.9 |
A 400 mm² line runs five different steel cores in normal Chinese practice, and all five take the same clamp body, the same bore and the same die. Buy the die for the aluminium section and it will press every core variant you have on site.
The one place the steel core does bite is the anchor: which is why TY-400/20-35 and TY-400/50-65 are printed as two model numbers instead of one. Both are 155/120/45/1.9, so the difference is in the steel anchor sleeve, and it matters when you press.
Six Model Numbers Cover Twelve Conductors
Six rows carry a range in the model name rather than a single core size:
| Model | Covers |
|---|---|
| TY-95/15/20 | LGJ-95/15, LGJ-95/20 |
| TY-185/25-30 | LGJ-185/25, LGJ-185/30 |
| TY-240/30-40 | LGJ-240/30, LGJ-240/40 |
| TY-300/25-40 | LGJ-300/25, LGJ-300/40 |
| TY-400/20-35 | LGJ-400/20, /30, /35 |
| TY-400/50-65 | LGJ-400/50, /65 |
| TY-500/35-45 | LGJ-500/35, /45 |
Note that TY-185/25-30 and TY-185/30 also both exist as printed rows — the range model and the single model overlap on the 30 core. Both are valid; the single-model row is the one to quote when the conductor is known, the range model when it is not.
The Heat-Resistant Rows Are Twice the Size
Four rows at the bottom of the table are not ACSR and do not share the geometry:
| Model | Conductor | L1 | L2 | D | Weight |
|---|---|---|---|---|---|
| TY-300N | NRLH60GJ-300 | 205 | 295 | 50 | 3.5 |
| TY-400N | NAHLGJ-400 | 215 | 180 | 55 | 3.9 |
| TY-500/35N | NAHLGJQ-500/35 | 290 | 345 | 65 | 6.2 |
| TY-630/45N | NAHLGJQ-630/45 | 300 | 365 | 70 | 7.0 |
Compare TY-300 at 145/110/40 against TY-300N at 205/295/50 — the heat-resistant version is more than twice the length and 45 % heavier for the same nominal section. Heat-resistant aluminium alloy does not take the same compression as ACSR: the wire work-hardens and the joint has to be long, so the fitting is long.
Note also that on three of the four N rows L2 is larger than L1, which is not true anywhere in the standard range. If you are laying these out, L2 is the dimension that grows, and it grows in the branch direction.
Dimension Ladder
For the standard range the ladder is clean and worth carrying in your head:
| Section | L1 | L2 | D |
|---|---|---|---|
| 35–50 | 80 | 60 | 20 |
| 70 | 100 | 70 | 22 |
| 95 | 100 | 80 | 26 |
| 120 | 115 | 80 | 26 |
| 150 | 125 | 90 | 30 |
| 185 | 125 | 90 | 32 |
| 210 | 135 | 100 | 34 |
| 240 | 135 | 100 | 36 |
| 300 | 145 | 110 | 40 |
| 400 | 155 | 120 | 45 |
| 500 | 165 | 130 | 52 |
| 630 | 185 | 150 | 60 |
| 800 | 210 | 170 | 65 |
Two sections share a length (95 and 120 both 100/80, 150 and 185 both 125/90) and only the bore steps up. The TL U-bolt T clamp works the same way: fifteen models on three body bores.
Technical Parameters

| Model | Applicable Conductor (mm2) | Main Dimensions (mm) | Reference Weight (kg) | ||
|---|---|---|---|---|---|
| L1 | L2 | D | |||
| TY-35/6 | LGJ-35/6 | 80 | 60 | 20 | 0.4 |
| TY-50/8 | LGJ-50/8 | 80 | 60 | 20 | 0.5 |
| TY-70/10 | LGJ-70/10 | 100 | 70 | 22 | 0.6 |
| TY-95/15/20 | LGJ-95/15/20 | 100 | 80 | 26 | 0.8 |
| TY-120/7 | LGJ-120/7 | 115 | 80 | 26 | 1.2 |
| TY-120/20 | LGJ-120/20 | 115 | 80 | 26 | 1.2 |
| TY-150/8 | LGJ-150/8 | 125 | 90 | 30 | 1.3 |
| TY-150/20 | LGJ-150/20 | 125 | 90 | 30 | 1.3 |
| TY-185/10 | LGJ-185/10 | 125 | 90 | 32 | 1.4 |
| TY-185/25-30 | LGJ-185/25 | 125 | 90 | 32 | 1.4 |
| TY-185/25-30 | LGJ-185/30 | 125 | 90 | 32 | 1.4 |
| TY-210/10 | LGJ-210/10 | 135 | 100 | 34 | 1.5 |
| TY-210/25 | LGJ-210/25 | 135 | 100 | 34 | 1.5 |
| TY-240/30-40 | LGJ-240/30 | 135 | 100 | 36 | 1.6 |
| TY-240/30-40 | LGJ-240/40 | 135 | 100 | 36 | 1.6 |
| TY-300/15 | LGJ-300/15 | 145 | 110 | 40 | 1.7 |
| TY-300/20 | LGJ-300/20 | 145 | 110 | 40 | 1.7 |
| TY-300/25-40 | LGJ-300/25 | 145 | 110 | 40 | 1.7 |
| TY-300/25-40 | LGJ-300/40 | 145 | 110 | 40 | 1.7 |
| TY-400/20-35 | LGJ-400/20 | 155 | 120 | 45 | 1.9 |
| TY-400/20-35 | LGJ-400/30 | 155 | 120 | 45 | 1.9 |
| TY-400/20-35 | LGJ-400/35 | 155 | 120 | 45 | 1.9 |
| TY-400/50-65 | LGJ-400/50 | 155 | 120 | 45 | 1.9 |
| TY-400/50-65 | LGJ-400/65 | 155 | 120 | 45 | 1.9 |
| TY-500/35-45 | LGJ-500/35 | 165 | 130 | 52 | 2.3 |
| TY-500/35-45 | LGJ-500/45 | 165 | 130 | 52 | 2.3 |
| TY-500/65 | LGJ-500/65 | 165 | 130 | 52 | 2.3 |
| TY-630/45 | LGJ-630/45 | 185 | 150 | 60 | 4.2 |
| TY-630/55 | LGJ-630/55 | 185 | 150 | 60 | 4.2 |
| TY-630/80 | LGJ-630/80 | 185 | 150 | 60 | 4.2 |
| TY-800/55 | LGJ-800/55 | 210 | 170 | 65 | 5.5 |
| TY-800/70 | LGJ-800/70 | 210 | 170 | 65 | 5.5 |
| TY-800/100 | LGJ-800/100 | 210 | 170 | 65 | 5.5 |
| TY-300N | NRLH60GJ-300 | 205 | 295 | 50 | 3.5 |
| TY-400N | NAHLGJ-400 | 215 | 180 | 55 | 3.9 |
| TY-500/35N | NAHLGJQ-500/35 | 290 | 345 | 65 | 6.2 |
| TY-630/45N | NAHLGJQ-630/45 | 300 | 365 | 70 | 7.0 |

Related Clamps
Bolted instead of pressed: TL U-bolt T clamp for 7.5–26 mm, TL clamp-plate T clamp for 120–630 mm². Two conductors per phase: TYS compression double conductor clamp. Larger main lines with a pressed branch: TLY compression T clamp.
Note: These are pressed fittings and the die is part of the order. Give the full conductor designation — TY-400/20-35 and TY-400/50-65 share every dimension but not the steel anchor.