TY2 Hydraulic T Clamp

Models: TY2-240 to TY2-600 (5 sizes) · Reference Weight: 1.2–1.9 kg · Body: aluminium, pressed
What the 2 Means
TY2 is the short-body version of the TY hydraulic T clamp. Same job, same pressed joint, different envelope:
| TY-400/50 | TY2-400 | |
|---|---|---|
| L | 155 mm | 190 mm |
| L2 / H | 120 mm | 140 mm |
| D | 45 mm | 45 mm |
| Weight | 1.9 kg | 1.4 kg |
The TY2 is longer and lighter than the corresponding TY. That combination only makes sense one way: less metal in the wall, more length in the body. TY2 is a lighter-duty build for the hollow-core LGJQ conductor, where the joint carries less bending at the tap.
Three of the Five Rows Are LGJQ Only
The conductor column is the important one here:
- TY2-240 — LGJ-240, standard ACSR
- TY2-300 — LGJ-300 or LGJQ-300
- TY2-400 — LGJ-400 or LGJQ-400
- TY2-500 — LGJQ-500 only
- TY2-600 — LGJQ-600 only
Above 400 mm² there is no standard ACSR support. LGJQ is the lightweight hollow-core conductor used where a large section is needed at reduced mechanical load. If your run is LGJ-500 or LGJ-630 rather than LGJQ, this page does not cover it — take the TY hydraulic T clamp, which goes to LGJ-800.
The Dimension Ladder Is Short and Flat
| Model | L | H | D | Weight |
|---|---|---|---|---|
| TY2-240 | 170 | 128 | 38 | 1.2 |
| TY2-300 | 180 | 132 | 40 | 1.3 |
| TY2-400 | 190 | 140 | 45 | 1.4 |
| TY2-500 | 200 | 139 | 50 | 1.7 |
| TY2-600 | 220 | 142 | 55 | 1.9 |
L climbs 170 to 220 mm in even steps, D climbs 38 to 55 mm, and weight nearly doubles across the range. But H barely moves — 128, 132, 140, 139, 142 mm. H is essentially flat at 128–142 mm across a two-and-a-half-fold range in conductor section, and TY2-500 is actually 1 mm shorter than TY2-400.
If you are setting phase spacing off this table, H is the number that decides it, and it is the number that changes least. Take it from the row.
When to Choose TY2 Over TY
- Hollow-core LGJQ conductor at 500 and 600 mm² — TY2 is the only pressed single-conductor tee we catalogue for those.
- Weight-critical stringing — 1.4 kg against 1.9 kg at 400 mm² is a 26 % saving on a fitting that appears twice per tap.
- Not for standard ACSR above 400 mm², and not where the tap has to take a heavy unbalanced pull — that is TY territory.
Technical Parameters
| Model | Applicable Conductor (mm2) | Main Dimensions (mm) | Reference Weight (kg) | ||
|---|---|---|---|---|---|
| L | H | D | |||
| TY2 -240 | LGJ-240 | 170 | 128 | 38 | 1.2 |
| TY2 -300 | LGJ-300, LGJQ-300 | 180 | 132 | 40 | 1.3 |
| TY2 -400 | LGJ-400, LGJQ-400 | 190 | 140 | 45 | 1.4 |
| TY2 -500 | LGJQ-500 | 200 | 139 | 50 | 1.7 |
| TY2 -600 | LGJQ-600 | 220 | 142 | 55 | 1.9 |
Related Clamps
The full-range pressed tee: TY hydraulic T clamp. Bolted alternative at these sections: TL bolted T clamp, 120–630 mm². For a pressed equal-diameter tee on large conductor: TL equal diameter clamp.
Note: TY2-500 and TY2-600 are LGJQ only. Confirm the conductor type before ordering — an LGJ-500 will not fit the TY2-500 body.