PF Power Fittings Technical Reference

TLS Bolted Double Conductor T Clamp

TLS bolted double conductor T clamp

Models: 34 combinations in three drop lengths · Reference Weight: 1.2–8.8 kg · Body: aluminium alloy, hardware hot-dip galvanised

The Last Number Is the Drop, Not the Conductor

TLS-<conductor>/<drop> — the part after the slash is the down-lead drop in millimetres, and it is the only thing that changes between the three blocks of the table.

Block Drop L Rows Weight band
Short 120 mm 10 1.2 – 5.5 kg
Medium 200 mm 13 1.3 – 8.8 kg
Long 400 mm 11 2.1 – 7.7 kg

Every dimension except L is identical across the three blocks for a given conductor. TLS-400/120 and TLS-400/400 are the same clamp body with a longer down-lead stem. If you are upgrading a clamp on an existing structure, the drop length is the dimension you match first — a 400 mm drop bolted where a 120 mm one was designed will foul the jumper.

The Three Blocks Are Not the Same Range

The blocks cover different conductors, which is easy to miss:

  • Only in the 200 mm block — TLS-630N, TLS-1000N, TLS-1440N. If your conductor is NRLH58GJ-1000 or NAHLGJQ-1440 and your drop is 120 or 400 mm, those rows do not exist.
  • Only in the 120 mm block — TLS-630N. It is not there; the 630 heat-resistant conductor is catalogued at 200 and 400 mm only.
  • 400 mm block has no 1000N — TLS-400N and TLS-1440N are present, TLS-1000N is not.

So the grid is 10 × 13 × 11 rows, not a rectangle. Check the drop column before you check the model number.

LGKK-900 Is 50 mm Here Too

TLS-600K/120 is bored at 52 mm and TLS-900K/120 at 50 mm — the larger expanded conductor takes the smaller bore. This matches the TL equal diameter clamp and the SJ twin spacer, three catalogues in agreement, and it is worth repeating because it is the most common order error on LGKK work.

It holds on every page but one: the TLS double drop clamp is bored 52 mm for LGKK-900, because that is the wide double-drop body and it clears the conductor rather than gripping it.

Where the Weight Goes

Roughly, the drop accounts for 0.1 to 1.5 kg per step, and the conductor accounts for the rest:

  • TLS-240: 1.2 → 1.3 → 2.1 kg across 120 → 200 → 400 mm
  • TLS-400N: 5.0 → 6.2 → 7.7 kg
  • TLS-1440N: 6.5 (200 mm) and 7.5 (400 mm)

The heat-resistant and expanded rows cost far more weight than their conductor section suggests. TLS-400N/120 at 5.0 kg against TLS-400/120 at 2.4 kg is more than double for the same nominal section — that is the deeper keeper pack and heavier hardware the N conductor needs, and it is the same pattern as the TY hydraulic clamp N rows.

Technical Parameters

TLS bolted double conductor T clamp, dimensions

ModelApplicable Conductor (mm2)Main Dimensions (mm)Reference Weight (kg)
Ø HabL
TLS-240/120LGJ-240228050141201.2
TLS-300/120LGJ-3002510063161202.3
TLS-400/120LGJ-4002910080161202.4
TLS-500/120LGJ-5003110080181202.45
TLS-630/120LGJ-63035100100181203.6
TLS-800/120LGJ-80039125125201204.8
TLS-400N/120NAHLGJQ-40029125125201205.0
TLS-600K/120LGKK-60052125125201205.5
TLS-900K/120LGKK-90050125125201205.4
TLS-1400/120LGJQT-140052125125201205.5
TLS-240/200LGJ-240228050142001.3
TLS-300/200LGJ-3002510063162002.5
TLS-400/200LGJ-4002810080162002.5
TLS-500/200LGJ-5003110080182002.6
TLS-630/200LGJ-63035100100182004.0
TLS-800/200LGJ-80039125125202006.0
TLS-400N/200NAHLGJQ-40029125125202006.2
TLS-630N/200NRLH58GJ-63035150150242008.8
TLS-600K/200LGKK-60052125125202006.8
TLS-900K/200LGKK-90050125125202006.6
TLS-1000N/200NRLH58GJ-100043150150242006.2
TLS-1400/200LGJQT-140052125125202006.8
TLS-1440N/200NRLH58GJQ-144052150150242006.5
TLS-240/400LGJ-240228050144002.1
TLS-300/400LGJ-3002510063164003.3
TLS-400/400LGJ-4002810080164003.6
TLS-400N/400NAHLGJQ-40029125125204007.7
TLS-500/400LGJ-5003110080184005.0
TLS-630/400LGJ-63035100100184006.1
TLS-800/400LGJ-80039125125204007.5
TLS-600K/400LGKK-60052125125204007.2
TLS-900K/400LGKK-90050125125204007.3
TLS-1400/400LGJQT-140052125125204007.2
TLS-1440N/400NAHLGJQ-144052150150244007.5

TLS bolted double conductor T clamp, drop detail

One Row With a Longer Head

The catalogue also carries TLS-2×400/120 — a twin 400 mm² phase with a 120 mm drop, LGJ-400 on the run and LGJQ-400 on the branch. It takes the same bore as TLS-400/120 at Ø 28.5 mm, but the head is longer, and the sheet dimensions it with one extra column:

Model Conductor Ø H a b L L1 Weight
TLS-2×400/120 LGJ-400 / LGJQ-400 28.5 mm 153 mm 120 mm 20 mm 120 mm 157 mm 4.5 kg

L1 = 157 mm is the overall length including the head, and H is 33 mm taller than the single-drop TLS-400/120. On a tight jumper loop that 33 mm is what decides whether the jumper clears the yoke plate, so check H against the string design rather than against the conductor size.

It is one catalogued size in this format. If your twin phase is 300 or 500 mm², the twin-head pattern can be built to order — send us the conductor pair and we quote it as a special.

Single conductor bolted tee: TL U-bolt T clamp. Two conductors parallel rather than twinned: TYS bolted double conductor clamp. Two separate down-leads: TLS double drop clamp. Pressed version: TYS compression double conductor clamp.

Note: State conductor, drop length and whether the down-lead is one or two. Dimensions vary within casting tolerance.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: