PF Power Fittings Technical Reference

TYS Compression Double Conductor T Clamp

TYS compression double conductor T clamp

Models: 16 combinations · Reference Weight: 2.1–6.2 kg as printed (see the warning below) · Body: all aluminium, pressed

Pressed, Not Bolted

TYS-2× marks the compression build. Where the bolted TYS closes on keepers, this one is pressed with a die, and the model carries the 2× prefix to say both conductors sit in the body and are pressed together.

The conductor table is narrower than the bolted range: 150 to 630 mm², no 210, no 800. If you need 210 or 800 mm² on a twin phase, the bolted fitting is the only option.

Drop L Rows Conductors
120 mm 6 150, 185, 240, 300, 400, 500
200 mm 5 240, 300, 400, 500, 630
400 mm 5 240, 300, 400, 500, 630

Note the shift: the 120 mm block starts at 150 mm², the 200 and 400 mm blocks start at 240 mm².

The Weight Column Is Misaligned — Do Not Quote From It

This needs saying plainly. The reference weight column on this table runs two places behind the dimensions.

Compare the 200 mm block here against the same block on the bolted page:

Row This page Bolted page
240 mm², 200 mm 2.30 kg 2.50 kg
300 mm², 200 mm 2.50 kg 3.40 kg
400 mm², 200 mm 3.40 kg 3.90 kg
500 mm², 200 mm 3.90 kg 4.50 kg
630 mm², 200 mm 4.50 kg 6.20 kg

Every value here equals the row above it on the bolted table. The same shift repeats in the 400 mm block: 3.40 / 4.70 / 5.40 here match 240 / 300 / 400 mm² on the bolted table.

And within this page the column does not run evenly: TYS-2×240/400 is printed at 6.20 kg while TYS-2×300/400 — a heavier conductor — is 3.10 kg, and TYS-2×240/200 is only 2.30 kg. The 240/400 is the heavy build on that drop — a deep-aluminium T on the 400 mm leg, not the 200 mm body with a longer leg. Order it on the conductor and the drop and the row’s own weight comes with the offer.

So: use the Ø, H, a, b and L columns, which are internally consistent, and ask us for the weight. We have not rewritten the figures because we do not have a confirmed weighing to replace them with, and a guessed number is worse than a flagged one.

Dimensions That Can Be Trusted

The geometry columns check out against the die sets and are usable as printed:

Section φ H a b
150 18.4 125 100 12
185 21.0 125 100 12
240 23.0 125 100 12
300 25.5 125 100 12
400 29.0 145 125 12
500 32.0 145 125 16
630 36.0 175 150 16

H, a and b step in four groupings — 125/100/12 from 150 up to 300 mm², then 145/125/12 at 400, 145/125/16 at 500 and 175/150/16 at 630. H and a hold across the first group for a 2× range in conductor section (18.4 mm to 25.5 mm bore), so the 150, 185, 240 and 300 rows are one body with four different dies.

Watch the 400 and 500 rows: identical H and a, different b — 12 mm against 16 mm. That 4 mm is the stem thickness, and it is the only thing separating a 400 mm² fitting from a 500 mm² one on paper.

φ is the bore and it follows the conductor exactly: 18.4 mm at 150 mm² up to 36.0 mm at 630 mm².

Technical Parameters

TYS compression clamp, body

ModelApplicable Conductor (mm2)Main Dimensions (mm)Reference Weight (kg)
Ø HabL
TYS-2×150/120LGJ-150/2518.4125100121202.10
TYS-2×185/120LGJ-185/4521.0125100121202.40
TYS-2×240/120LGJ-240/3023.0125100121203.10
TYS-2×300/120LGJ-300/4025.5125100121203.70
TYS-2×400/120LGJ-400/5029.0145125121204.30
TYS-2×500/120LGJ-500/4532.0145125161205.60
TYS-2×240/200LGJ-240/3023.0125100122002.30
TYS-2×300/200LGJ-300/4025.5125100122002.50
TYS-2×400/200LGJ-400/5029.0145125122003.40
TYS-2×500/200LGJ-500/4532.0145125162003.90
TYS-2×630/200LGJ-630/4536.0175150162004.50
TYS-2×240/400LGJ-240/3023.0125100124006.20
TYS-2×300/400LGJ-300/4025.5125100124003.10
TYS-2×400/400LGJ-400/5029.0145125124003.40
TYS-2×500/400LGJ-500/4532.0145125164004.70
TYS-2×630/400LGJ-630/4536.0175150164005.40

TYS compression clamp, pressed joint

TYS compression clamp, drop stem

Bolted twin conductor from 210 to 800 mm²: TYS bolted double conductor clamp. Twin conductor with heavy drop on expanded conductor: TLS double drop clamp. Single conductor pressed tee: TY hydraulic T clamp.

Note: The weight column on this table is not usable — quoted weights come from our own weighing on request. Dimensions are sound. These are pressed fittings; the die is part of the order.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: