TLS Double Conductor T Clamp

Models: 15 sizes · Reference Weight: 2.0–11.8 kg · Body: aluminium alloy, hardware hot-dip galvanised
Two Conductor Pairs, One Clamp
This family holds a twin conductor pair in one body. The first eight rows are dimensioned by pair section — TLS-44 is a 185–240 mm² pair, TLS-55 is a 300–400 mm² pair — and the last seven are dimensioned by conductor name, because above 500 mm² the pair is always a specific expanded or heat-resistant conductor.
| Block | Rows | Conductor format | Drop |
|---|---|---|---|
| Plain | 8 | Section ranges, 185–630 mm² | 120 mm |
-200 |
4 | LGJ-500, LGJQT-1400, NAHLGJQ-1440 | 200 mm |
-400 |
3 | 185–240, 300–400 pairs | 400 mm |
The suffix is the drop length. TLS-44 is a 120 mm drop, TLS-44-400 is the same clamp at 400 mm — 4.8 kg against 2.0 kg, which is more than double the mass for a longer stem and its keepers.
Body Height Follows The Bore
H is the overall body height, and it is set by the larger of the two bores rather than by the size code:
| Largest bore | H | Rows |
|---|---|---|
| 22 mm | 120 mm | TLS-44 |
| 28 mm | 160 mm | TLS-45, TLS-53, TLS-54, TLS-55 |
| 34.5 mm | 170–180 mm | TLS-56, TLS-65, TLS-66 |
So H rises in three steps across the eight 120 mm rows, and it does not rise with the section pair — TLS-53 and TLS-55 are both 28 mm bodies at 160 mm although one carries a 120–150 mm² branch and the other a 300–400 mm² branch. The -400 versions sit 20 mm taller where the bore grows: TLS-44-400 is 140 against 120, TLS-55-400 is 180 against 160, and TLS-45-400 stays at 160 on its 25 mm bore.
That gives the string calculation what it needs — the vertical envelope from the main bore to the end of the drop — and the outline drawing goes out with the quotation.
The Branch Bore Changes Between the 120 and 400 Versions
TLS-45 and TLS-45-400 are the same pair (185–240 mm² main, 300–400 mm² branch) and differ in one figure beyond length:
- TLS-45: Ø2 = 28.0 mm
- TLS-45-400: Ø2 = 25.0 mm
A 3 mm narrower branch bore on the long-drop version, because the long drop is built for one down-lead: TLS-45 and TLS-45-400 do not take the same branch conductor, and the bore is the one printed on the row you order. Tell us the conductor and the drop together and the two match up before the order goes in.
TLS-55-400 reads the same way from the other side: Ø1 = 25.0 mm where TLS-55 is 28.0 mm, so the main bore is narrower on the 400 version.
The 200 mm Block Is Conductor-Specific
Four rows, and each is written against one conductor rather than a section range:
- TLS-500/300-200 — LGJ-500
- TLS-1400/300-200 and TLS-1400/1400-200 — LGJQT-1400
- TLS-1440N/1440N-200 — NAHLGJQ-1440, at 11.8 kg, the heaviest fitting here
All four sit at L = 200 mm with Ø 52 mm main bores and 31 to 52 mm branch bores. The 1440N row is 5 kg above the 1400/1400 row for the same Ø — that is the heat-resistant keeper pack again, and it is the same premium seen on the TY hydraulic and TLS single drop ranges.
Technical Parameters
| Model | Applicable Conductor (mm2) | Main Dimensions (mm) | Reference Weight (kg) | ||||
|---|---|---|---|---|---|---|---|
| Busbar | Down Lead | Ø1 | Ø2 | H | L | ||
| TLS-44 | 185~240 | 185~240 | 22.0 | 22.0 | 120 | 120 | 2.0 |
| TLS-45 | 185~240 | 300~400 | 22.0 | 28.0 | 160 | 120 | 2.2 |
| TLS-53 | 300~400 | 120~150 | 28.0 | 18.0 | 160 | 120 | 2.3 |
| TLS-54 | 300~400 | 185~240 | 28.0 | 22.0 | 160 | 120 | 2.5 |
| TLS-55 | 300~400 | 300~400 | 28.0 | 28.0 | 160 | 120 | 2.7 |
| TLS-56 | 300~400 | 500~630 | 28.0 | 34.5 | 170 | 120 | 3.0 |
| TLS-65 | 500~630 | 300~400 | 34.5 | 28.0 | 180 | 120 | 3.3 |
| TLS-66 | 500~630 | 500~630 | 34.5 | 34.5 | 180 | 120 | 3.5 |
| TLS-500/300-200 | 500 | 300 | 31.0 | 25.0 | 180 | 200 | 5.5 |
| TLS-1400/300-200 | 1400 | 300 | 52.0 | 25.0 | 180 | 200 | 6.5 |
| TLS-1400/1400-200 | 1400 | 1400 | 52.0 | 52.0 | 180 | 200 | 6.8 |
| TLS-1440N/1440N-200 | 1440 | 1440 | 52.0 | 52.0 | 180 | 200 | 11.8 |
| TLS-44-400 | 185~240 | 185~240 | 22.0 | 22.0 | 140 | 400 | 4.8 |
| TLS-45-400 | 185~240 | 300~400 | 22.0 | 25.0 | 160 | 400 | 5.0 |
| TLS-55-400 | 300~400 | 300~400 | 25.0 | 25.0 | 180 | 400 | 6.0 |
Related Clamps
Single-drop twin conductor range from LGJ-240: TLS bolted double conductor T clamp. Two down-leads: TLS double drop clamp. Twin 400 mm² with a 120 mm drop: TLS-2×400/120. Bolted single conductor: TL clamp-plate T clamp.
Note: H is the overall body height and follows the larger bore — 120 mm at 22 mm, 160 at 28 mm, 170 to 180 at 34.5 mm — not the section pair. The -400 versions run 20 mm taller where the bore grows. TLS-45 and TLS-45-400 carry different branch bores, 28.0 and 25.0 mm, so order by the row you need.