PF Power Fittings Technical Reference

TL T Clamp, Clamp-Plate Type

TL T clamp, clamp-plate type

Models: TL-45 to TL-66 (8 sizes) · Reference Weight: 2.6–3.6 kg · Body: aluminium alloy, hardware hot-dip galvanised

Plates Down the Conductor

A row of clamp plates is bolted onto each leg, two bolts per plate. The conductor is held along a length of plate rather than at a single saddle, and the plates are what take the section at this size.

The TL-53, TL-54 and TL-55 numbers are also carried by a separate U-bolt series for 7.5–26 mm conductor, built to its own drawing. Quote the type with the model: TL U-bolt T clamp.

Digits Are Sections

The two digits are main line then branch, and the ladder is four steps:

Digit Conductor section Clamp bore
3 120 – 150 mm² 17.5 mm
4 185 – 240 mm² 22.0 mm
5 300 – 400 mm² 28.0 mm
6 500 – 630 mm² 34.5 mm

So TL-65 is a 500–630 mm² main line with a 300–400 mm² branch.

The tolerance is not triangular on this page. TL-45 is a 185–240 mm² main line with a 300–400 mm² branch — the branch is heavier than the run, and the body carries a 22.0 mm main bore beside a 28.0 mm branch bore.

Eight of the twelve possible combinations are catalogued. Missing are TL-43 and TL-44 (a 185–240 mm² run tapped at 120–240 mm²), TL-46 (185–240 feeding 500–630) and TL-63 (500–630 feeding 120–150). If your design lands on one, tell us and we will quote it against the drawing rather than substitute a nearby size.

H Does Not Follow the Conductor

H runs 168 to 210 mm and does not climb with section. TL-45 has the smallest main line on the page and the tallest body at 210 mm. TL-55, TL-56, TL-64, TL-65 and TL-66 all sit at 196 mm, and TL-53 and TL-54 come in at 168 mm.

Do not design phase clearance off a linear interpolation of H. Read the row for the model you are ordering.

Weight

Reference weight runs 2.6 kg at TL-45 and TL-53, rising one step per size to 3.6 kg at TL-66. Inside the 300–400 mm² main line the branch digit is worth 0.5 kg: TL-53 at 2.6, TL-54 at 2.7, TL-55 at 3.0, TL-56 at 3.1.

When you are costing freight, use the row weight; do not scale from the conductor size.

Technical Parameters

ModelApplicable Conductor (mm2)Main Dimensions (mm)Reference Weight (kg)
BusbarDown LeadØ1Ø2H
TL-45185~240300~40022.028.02102.6
TL-53300~400120~15028.017.51682.6
TL-54300~400185~24028.022.01682.7
TL-55300~400300~40028.028.01963.0
TL-56300~400500~63028.034.51963.1
TL-64500~630185~24034.522.01963.3
TL-65500~630300~40034.528.01963.4
TL-66500~630500~63034.534.51963.6

TL T clamp, clamp-plate type, side view

The 7.5–26 mm U-bolt series: TL U-bolt T clamp. Two conductors per phase: TLS double conductor T clamp. Pressed rather than bolted: TY hydraulic T clamp.

Note: Clamp-plate type, eight sizes for 120–630 mm² conductor. The digits are sections, and TL-45 carries a heavier branch than its run. State whether the branch is aluminium or ACSR when ordering.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: