PF Power Fittings Technical Reference

PGA Torque Parallel Groove Clamp

Conductors: 10 to 300 mm² · Codes: PGA-301 to PGA-803 · Bolts: 1, 2 or 3

PGA torque parallel groove clamp, dimensioned drawing

PGA is the torque clamp of the parallel groove family — the sheet calls it a 力矩 clamp. Where the ordinary bolted clamp is set by feel, this one is set by the torque on the bolt, which is what you want when the conductor sits at the bottom of the clamp’s range and the cover has a real gap to close.

Six codes cover 10 to 300 mm² in four conductor ranges.

The code is range class plus bolt count

Read PGA-603 as range class 6, three bolts:

Code Range (mm²) Bolts
PGA-301 10~95 1
PGA-302 10~95 2
PGA-502 25~150 2
PGA-602 50~240 2
PGA-603 50~240 3
PGA-803 95~300 3

The last digit is the bolt count, on all six rows. So PGA-302 and PGA-303 are not two versions of the same thing — the second one does not exist, and if you order it you will be asked a question.

The leading digit is the range class, and it steps 3, 5, 6, 8 — so classes 4 and 7 are ranges that are simply not made.

Technical parameters

ModelApplicable conductor (mm²)Main dimensions (mm)Bolts
LBHRM
PGA-30110~95345450881
PGA-30210~95465450882
PGA-50225~150505450882
PGA-60250~24084667010122
PGA-60350~240122667010123
PGA-80395~300133687011.5123

All dimensions in millimetres. No weight is published.

Two shared bodies, and one that is not

B, H, R and M are not free variables — they come in three groups:

Body Codes B H R M
Small PGA-301, 302, 502 54 50 8 M8
Middle PGA-602, 603 66 70 10 M12
Large PGA-803 68 70 11.5 M12

So PGA-502 is the small body — the same 54 × 50 casting as the two 10~95 codes, with a groove that reaches 150 mm² and a length of 50 mm. Only L and the bolt count change inside a body group.

That gives two useful steps to know:

  • PGA-301 → PGA-302 is the same 10~95 clamp with a second bolt. L goes 34 → 46 mm.
  • PGA-602 → PGA-603 is the same 50~240 clamp with a third bolt. L goes 84 → 122 mm.

R here does not track the conductor

On the JB and JBG clamps, doubling R gives you the outside diameter of the largest conductor the clamp takes. On PGA it does not.

R is 8 mm on both the 1095 codes and on the 25150 code. A single 16 mm groove cannot be “cut to” a 150 mm² conductor. What R describes here is the groove of a clamp whose cover is expected to travel: the torque does the closing, not the groove profile.

The practical consequence: do not pick a PGA by checking 2R against your conductor. Pick it by the stated range, and accept that at the bottom of the range the cover is doing a lot of travelling.

Fitting it

  • Torque, not feel. The whole point of this clamp is that the joint is set by a number. Use a torque wrench, and use the figure the factory gives for the bolt size — M8 and M12 take very different values.
  • One-bolt PGA-301 needs a flat surface. With a single bolt there is nothing to stop the cover rocking; it is the version for small conductor on a straight run.
  • Grease both conductors. Aluminium oxide is the contact resistance, and on a torque clamp the torque is what pushes through it.
  • Re-check after the first load cycle. A bolted aluminium joint relaxes as it warms.
  • Current, not tension. PGA crosses a joint; it does not hold a span.

The rest of the family

  • JBT — the all-copper twelve-row clamp with the readable two-digit code.
  • JBTL — the same twelve bodies in copper-aluminium, flash welded.
  • JB — the aluminium clamp for ACSR, 16 to 630 mm².
  • JXD — the wedge type, when even a torque wrench is not available.

Note: Quote PGA-603 and give both conductor sizes. And ask for the tightening torque for the M8 and M12 bolts — it is not on this sheet, and it is the number the clamp depends on.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: