PF Power Fittings Technical Reference

TL Single Conductor T Clamp, Types A / B / C

TL single conductor T clamp

Models: 35 sizes across three tables · Reference Weight: 1.2–11.5 kg · Body: aluminium alloy, hardware hot-dip galvanised

What A, B and C Actually Change

Three tables, one clamp outline. Every dimension on the drawing — Ø, H, a, b — is defined the same way in all three: Ø is the main-line bore, H is the length of the branch stem, a is the stem width and b is the stem thickness.

On ordinary ACSR the three types are identical. TL-300A, TL-300B and TL-300C are all 25 / 100 / 63 / 16 at 1.5 kg. So are TL-400, TL-500, TL-630 and TL-800. If your conductor is LGJ, the letter is not a selection — order whichever is in stock.

The letter only bites on the last two columns of each table, the heat-resistant N grades and the expanded K grades:

Model Type A Type B Type C
LGKK-600 5.8 kg 5.8 kg 11.0 kg
LGKK-900 5.2 kg 5.5 kg 11.1 kg
NAHLGJQ-400 2.3 kg 5.0 kg 8.5 kg
NAHLGJQ-1440 6.5 kg 8.1 kg 11.5 kg

Type C weighs roughly 1.6 to 2.1 times type B on every one of those rows and not a gram more on the ACSR rows. That is the signature of a heavier keeper pack and a longer bolt set rather than a heavier body — and it is the only figure on the page you cannot infer from the conductor size.

We are not going to invent a meaning for the letter. The source catalogue shows the three tables and the weights and nothing else. If your specification calls for a C, tell us what the C is there to do — high tensile load, vibration, a specific utility standard — and we will match it against the drawing before quoting. Ordering a C when a B would do costs you double the weight for no benefit; ordering a B where a C was specified is a submittal rejection.

Three Different Model Number Formats on One Page

The tables do not share a naming scheme, and mixing them up is easy:

  • Table A / B / C, LGJ rows use TL-<section>A — TL-300A, TL-400B. The number is the conductor section in mm².
  • N rows use the same pattern with an N — TL-240NA, TL-400NB, TL-1440NC.
  • K rows carry the conductor name — TL-600KA is specified against LGKK-600, not against a section.

TL-800A and TL-800B are one conductor size apart in weight (4.5 kg against 4.6 kg) and both are 39 / 125 / 125 / 20. TL-900KA and TL-900KB are the same conductor at 5.2 kg and 5.5 kg. Read across the row you need; do not carry a number from one type to another.

The 240–800 mm² Working Range

Table A is the broadest at 14 rows and spans LGJ-300 up to LGJQT-1400, including the 52 mm bores. Table B runs to 11 rows and stops one model earlier on the N side. Table C is 10 rows and starts at LGJ-300 — there is no C below 300 mm², because the C keeper pack does not exist in the smaller bodies.

Two figures worth flagging:

  • TL-400NC is bored at Ø 28 mm while TL-400NA and TL-400NB are both 29 mm. One millimetre, on the main line bore. If you are matching a C to a NB installation, check the conductor’s actual diameter rather than assuming the bore follows the model number.
  • TL-240B at 1.2 kg is the lightest fitting on the page and the only one with an 80 mm H. It is a genuine outlier in a table that otherwise starts at H = 100.

Technical Parameters

TL T clamp, body section

Type A

ModelApplicable Conductor (mm2)Main Dimensions (mm)Reference Weight (kg)
Ø Hab
TL-300ALGJ-3002510063161.5
TL-400ALGJ-4002810063161.5
TL-500ALGJ-5003110080182.8
TL-630ALGJ-63035100100183.5
TL-800ALGJ-80039125125204.5
TL-240NANAHLGJQ-2402210063161.5
TL-300NANAHLGJQ-30025100100202.3
TL-400NANAHLGJQ-40029100100202.3
TL-500NANAHLGJQ-50031125125223.1
TL-630NANAHLGJQ-63035125125223.1
TL-600KALGKK-60052125125205.8
TL-900KALGKK-90052125125205.2
TL-1400ALGJQT-140052125125205.8
TL-1440NANAHLGJQ-144052150150246.5

TL T clamp, branch stem

Type B

ModelApplicable Conductor (mm2)Main Dimensions (mm)Reference Weight (kg)
Ø Hab
TL-240BLGJ-240228050141.2
TL-300BLGJ-3002510063161.5
TL-400BLGJ-4002810063161.5
TL-500BLGJ-5003110080182.8
TL-630BLGJ-63035100100183.5
TL-800BLGJ-80039125125204.6
TL-400NBNAHLGJQ-40029100100205.0
TL-600KBLGKK-60052125125205.8
TL-900KBLGKK-90052125125205.5
TL-1400BLGJQT-140052125125206.8
TL-1440NBNAHLGJQ-144052150150248.1

TL T clamp, keeper detail

Type C

ModelApplicable Conductor (mm2)Main Dimensions (mm)Reference Weight (kg)
Ø Hab
TL-300CLGJ-3002510063161.5
TL-400CLGJ-4002810063161.5
TL-500CLGJ-5003110080182.8
TL-630CLGJ-63035100100183.5
TL-800CLGJ-80039125125204.5
TL-400NCNAHLGJQ-40028100100208.5
TL-600KCLGKK-600521251252011.0
TL-900KCLGKK-900521251252011.1
TL-1400CLGJQT-1400521251252011.0
TL-1440NCNAHLGJQ-1440521501502411.5

The bolted U-bolt TL clamp and its clamp-plate counterpart use a two-digit numbering instead of this letter scheme. For the same tap made by compression, the TY hydraulic T clamp goes to LGJ-800 and includes the N grades.

Note: Dimensions may vary within casting tolerance. State the conductor type and the required type letter when ordering; for N and K conductors always give the full conductor designation.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: