TLY Compression T Clamp

Models: 8 sizes · Reference Weight: 5.5–11.3 kg · Body: aluminium alloy, pressed
Built Around Three Main Lines
Every row on this page takes one of three main conductors: LGKK-600, LGJQT-1400 or NRLH58GJ-1000 / NAHLGJQ-1440. There is no LGJ main line at all — if your run is ordinary ACSR, this is the wrong page and you want the TY hydraulic T clamp.
Note what LGKK-600 and LGJQT-1400 have in common: both are bored at Ø1 = 52 mm. An expanded 600 and a 1400 section conductor are the same size on the outside. That is why one casting covers both, and why the six 52 mm rows cost roughly the same as each other.
The Branch Ladder Skips 500 and 630
Branch options run 300, 400, 600K, 1000N, 1400 and 1440N. There is no 500 and no 630 branch anywhere in the table.
That is a real gap, not an omission in the print. If your tap is LGJ-500 or LGJ-630 off a 1400 mm² bus, this family does not have a row for it. The two routes are the TLS double conductor T clamp, which carries 500 and 630 on the branch side, or a special. Tell us the pair and we will quote rather than let you order the nearest size and shim it.
Two Rows, One Shape, One Kilogram Apart
TLY-600K/600K and TLY-1400/1400 are dimensionally identical — Ø 52 / 53.0, H 180, D 76 — and differ only in weight: 7.2 kg against 6.2 kg.
Both are correct. The 600K row is built for the LGKK expanded conductor and carries the deeper keeper pack that conductor needs; the 1400 row is the LGJQT build on the same body. If you are comparing quotations on weight alone, this is the pair that will make one supplier look 14 % lighter for the same fitting.
The last row is the outlier in the other direction: TLY-1440N/1440N at 11.3 kg against 6.2 kg for the 1400/1400, with H growing from 180 to 240 mm and D from 76 to 80. The heat-resistant 1440 needs the longer body and the heavier hardware, and that is nearly double the mass on a fitting that does the same job.
H and D Tell You the Envelope
- H = 110 mm on the two 300 branches — the shortest body in the family
- H = 120 mm on the two 400 branches
- H = 180 mm on the four equal-diameter rows
- H = 240 mm only on the 1440N
D follows the branch: 40 mm for a 300, 45 for a 400, 76 for a 600K/1400, 80 for the 1440N. H and D are branch dimensions, not main-line dimensions — an LJGQ-1400 main with a 300 branch is a 110 mm tall fitting, and that is what decides your jumper clearance.
Technical Parameters

| Model | Applicable Conductor (mm2) | Main Dimensions (mm) | Reference Weight (kg) | ||||
|---|---|---|---|---|---|---|---|
| Busbar | Down Lead | Ø1 | Ø2 | H | D | ||
| TLY-600K/300 | LGKK-600 | LGJ-300 | 52 | 25.5 | 110 | 40 | 5.5 |
| TLY-600K/400 | LGKK-600 | LGJ-400 | 52 | 28.5 | 120 | 45 | 5.8 |
| TLY-600K/600K | LGKK-600 | LGKK-600 | 52 | 53.0 | 180 | 76 | 7.2 |
| TLY-1000N/1000N | NRLH58GJ-1000 | NRLH58GJ-1000 | 43 | 43.5 | 210 | 76 | 6.5 |
| TLY-1400/300 | LGJQT-1400 | LGJ-300 | 52 | 25.5 | 110 | 40 | 5.5 |
| TLY-1400/400 | LGJQT-1400 | LGJ-400 | 52 | 28.5 | 120 | 45 | 5.8 |
| TLY-1400/1400 | LGJQT-1400 | LGJQT-1400 | 52 | 53.0 | 180 | 76 | 6.2 |
| TLY-1440N/1440N | NAHLGJQ-1440 | NAHLGJQ-1440 | 52 | 53.0 | 240 | 80 | 11.3 |
Related Clamps
The bolted TL clamp-plate T clamp covers 120–630 mm² lines without a press. The TL equal-diameter clamp is the same body style for two identical conductors. For 4-to-2 bundle transitions on the same conductors, see the JTY 4-to-2 clamp.
Note: These are pressed fittings — the die set is part of the order. Confirm main and branch conductor designations; the branch bore is cut to the conductor, not to the model number.