TYS Bolted Double Conductor T Clamp

Models: 19 combinations · Reference Weight: 2.1–8.8 kg · Body: aluminium, fasteners hot-dip galvanised
Two Conductors in One Body
TYS takes both conductors of a twin phase in a single clamp and drops one down-lead off it. That is the difference from TLS, which also handles two conductors but is dimensioned and built for a heavier drop.
The table carries two bores, φ1 and φ2, and they are not the two conductors — they are the nominal and the actual diameter of the same conductor:
| Model | φ1 | φ2 | Gap |
|---|---|---|---|
| TYS-210/120 | 21 | 21.5 | 0.5 |
| TYS-240/120 | 22 | 23.0 | 1.0 |
| TYS-300/120 | 25 | 25.5 | 0.5 |
| TYS-400/120 | 28 | 29.5 | 1.5 |
| TYS-500/120 | 31 | 31.5 | 0.5 |
| TYS-630/120 | 35 | 35.5 | 0.5 |
| TYS-800/200 | 39 | 40.0 | 1.0 |
φ1 is the catalogued conductor diameter, φ2 the groove it is cut for. The 0.5–1.5 mm gap is designed clearance, exactly as on the TL equal diameter clamp. Give us the conductor designation, not just the model, and we will confirm which bore you are getting.
The Drop Blocks Again
Three drop lengths, and they are not the same range:
| Drop L | Rows | Conductors |
|---|---|---|
| 120 mm | 6 | 210, 240, 300, 400, 500, 630 |
| 200 mm | 7 | 210, 240, 300, 400, 500, 630, 800 |
| 400 mm | 6 | 240, 300, 400, 500, 630, 800 |
- LGJ-800 exists only at 200 and 400 mm
- LGJ-210 does not exist at 400 mm
- Everything else is available at all three drops
Unlike the TLS range, the drop does not change H. TYS-400/120 and TYS-400/400 are both H 120 mm — the extra length is all in the stem, and D stays at 45 mm.
Two Weight Figures That Do Not Fit
Two rows break the pattern badly enough that they are worth calling out before you use this table to cost freight:
- TYS-800/200 — 3.10 kg. The 800 mm² conductor is the largest on the page. At 200 mm drop it should weigh more than TYS-630/200 at 6.20 kg, and its own 400 mm sibling is 8.80 kg. The 3.10 figure is exactly what TYS-300/120 weighs — it looks like a value carried from another row. Expect something in the 7–8 kg band and confirm before you book freight.
- TYS-630/200 — 6.20 kg against TYS-500/200 at 4.50 kg. That is a 38 % step where every other step in the column is 13–29 %. It may be right — the 630 body is a big jump from 500 — but it is the one row in the block we would check.
Both are printed as-is in the source and shown as-is here. The other seventeen rows are consistent and can be used directly.
D and H Track the Conductor, Not the Drop
| Conductor | H | D |
|---|---|---|
| LGJ-210 | 100 | 34 |
| LGJ-240 | 100 | 36 |
| LGJ-300 | 110 | 40 |
| LGJ-400 | 120 | 45 |
| LGJ-500 | 130 | 52 |
| LGJ-630 | 150 | 60 |
| LGJ-800 | 170 | 65 |
D is the body width and grows 5 mm per step after 300 — this is the dimension that decides whether two phases clear each other on a narrow cross-arm. H grows more slowly at the bottom (100 mm covers both 210 and 240) and then 20 mm per step at the top.
Technical Parameters
| Model | Applicable Conductor (mm2) | Main Dimensions (mm) | Reference Weight (kg) | ||||
|---|---|---|---|---|---|---|---|
| Ø1 | Ø2 | L | H | D | |||
| TYS-210/120 | LGJ-210/25 | 21 | 21.5 | 120 | 100 | 34 | 2.10 |
| TYS-240/120 | LGJ-240/30 | 22 | 23.0 | 120 | 100 | 36 | 2.40 |
| TYS-300/120 | LGJ-300/40 | 25 | 25.5 | 120 | 110 | 40 | 3.10 |
| TYS-400/120 | LGJ-400/50 | 28 | 29.5 | 120 | 120 | 45 | 3.70 |
| TYS-500/120 | LGJ-500/45 | 31 | 31.5 | 120 | 130 | 52 | 4.30 |
| TYS-630/120 | LGJ-630/45 | 35 | 35.5 | 120 | 150 | 60 | 5.60 |
| TYS-210/200 | LGJ-210/25 | 21 | 21.5 | 200 | 100 | 34 | 2.30 |
| TYS-240/200 | LGJ-240/30 | 22 | 23.0 | 200 | 100 | 36 | 2.50 |
| TYS-300/200 | LGJ-300/40 | 25 | 25.5 | 200 | 110 | 40 | 3.40 |
| TYS-400/200 | LGJ-400/50 | 28 | 29.5 | 200 | 120 | 45 | 3.90 |
| TYS-500/200 | LGJ-500/45 | 31 | 31.5 | 200 | 130 | 52 | 4.50 |
| TYS-630/200 | LGJ-630/45 | 35 | 35.5 | 200 | 150 | 60 | 6.20 |
| TYS-800/200 | LGJ-800/55 | 39 | 40.0 | 200 | 170 | 65 | 3.10 |
| TYS-240/400 | LGJ-240/30 | 22 | 23.0 | 400 | 100 | 36 | 3.40 |
| TYS-300/400 | LGJ-300/40 | 25 | 25.5 | 400 | 110 | 40 | 4.70 |
| TYS-400/400 | LGJ-400/50 | 28 | 29.5 | 400 | 120 | 45 | 5.40 |
| TYS-500/400 | LGJ-500/45 | 31 | 31.5 | 400 | 130 | 52 | 6.10 |
| TYS-630/400 | LGJ-630/45 | 35 | 35.5 | 400 | 150 | 60 | 7.80 |
| TYS-800/400 | LGJ-800/55 | 39 | 40.0 | 400 | 170 | 65 | 8.80 |

Related Clamps
Pressed rather than bolted, up to LGJ-630: TYS compression double conductor clamp. Heavier drop on expanded conductor: TLS double drop clamp. Single conductor bolted tee: TL clamp-plate T clamp.
Note: Two weight figures on this table are suspect — see above. State conductor and drop length; dimensions vary within casting tolerance.