JBCD Grounding Piercing Clamp

JBCD side-exit grounding clamp

JBCD front-exit grounding clamp

A clamp that does not splice anything. Its job is to put a grounding point on an insulated overhead line without stripping the conductor: the bolt drives teeth through the insulation, the conductor is bonded to a ring, and the earth lead is clipped to that ring when the line is earthed for work.

The two photographs are the two versions — the grounding ring exiting to the side of the body, and exiting to the front. Everything else about them is the same, and that is where the ordering trap is.

JBCD side-exit clamp, ring running out to one side

JBCD clamp seen along the conductor, ring ends visible both sides

The two outlines show where the ring sits. In the first the ring runs out to one side and the dimension B spans the clamp across the conductor; in the second, looking along the conductor, the ring shows at both ends and L spans the full width. Either way the ring is a permanent part of the body — it is not a lug you bolt on later.

All 20 sizes

Applicable VoltageModelApplicable Conductor (mm2)Main Dimensions (mm)Bolt QtyGrounding Ring
LBH
(1kV)JBCD-16~120 (1kV)16~12013989751Front Grounding Ring
(1kV)JBCD-35~120 (1kV)35~120142116842Front Grounding Ring
(1kV)JBCD-95~185 (1kV)95~185153116842Front Grounding Ring
(1kV)JBCD-35~240 (1kV)35~240156118952Front Grounding Ring
(1kV)JBCD-150~240 (1kV)150~240153116842Front Grounding Ring
(10kV)JBCD10-35~120 (10kV)35~1201601451152Front Grounding Ring
(10kV)JBCD10-95~185 (10kV)95~1851601451152Front Grounding Ring
(10kV)JBCD10-35~240 (10kV)35~240156*118952Front Grounding Ring
(10kV)JBCD10-150~240 (10kV)150~2401601451152Front Grounding Ring
(20kV)JBCD20-35~120 (20kV)35~1201701481152Front Grounding Ring
(20kV)JBCD20-150~240 (20kV)150~2401701481152Front Grounding Ring
(1kV)JBCD-16~120T (1kV)16~120142116841Side Grounding Ring
(1kV)JBCD-35~120T (1kV)35~120142116842Side Grounding Ring
(1kV)JBCD-95~185T (1kV)95~185153116842Side Grounding Ring
(1kV)JBCD-35~240T (1kV)35~240153116842Side Grounding Ring
(1kV)JBCD-150~240T (1kV)150~240153116842Side Grounding Ring
(10kV)JBCD10-35~120T (10kV)35~1201601451152Side Grounding Ring
(10kV)JBCD10-95~185T (10kV)95~1851601451152Side Grounding Ring
(10kV)JBCD10-35~240T (10kV)35~2401601451152Side Grounding Ring
(10kV)JBCD10-150~240T (10kV)150~2401601451152Side Grounding Ring

Values marked * are the checked figures, explained under the section below.

T means side, no T means front

Code Ring exits
JBCD-35~120 front
JBCD-35~120T side

The T is the only difference in the code, so it is the only thing standing between the two parts. Write the T. An order without it gets the front version, and on a pole where the earth lead comes down the side of the crossarm that is the wrong clamp.

There is no 20 kV side version

The ranges are not symmetric:

Voltage Front Side
1 kV 5 models 5 models
10 kV 4 models 4 models
20 kV 2 models none

20 kV exists only with the front ring, and only in two sizes: 35120 mm² and 150240 mm². There is no 20 kV T model and no 20 kV 95~185 model. If a 20 kV job needs a side exit, this is not the product — say so early rather than substituting.

The 20 kV body is also the same casting for both sizes: L 170, B 148, H 115 on the 35120 and on the 150240. One body covers the whole 20 kV range.

Front and side usually measure the same

Comparing each pair:

Voltage Conductor Front L/B/H Side L/B/H Difference
1 kV 35~120 142/116/84 142/116/84 none
1 kV 95~185 153/116/84 153/116/84 none
1 kV 150~240 153/116/84 153/116/84 none
10 kV 35~120 160/145/115 160/145/115 none
10 kV 95~185 160/145/115 160/145/115 none
10 kV 150~240 160/145/115 160/145/115 none
1 kV 16~120 139/89/75 142/116/84 +27 in B, +9 in H
1 kV 35~240 156/118/95 153/116/84 front one size larger
10 kV 35~240 156*/118/95 160/145/115 see below

Six of the nine pairs are identical to the millimetre. That is not a coincidence — on those sizes the ring is bolted onto the same body, so the envelope does not change.

The 1 kV 16~120 pair is the one to watch. It is the only clamp in the 1 kV range with a single bolt, and the side version is a genuinely bigger body: 27 mm wider and 9 mm taller. On a tight crossarm that 27 mm decides whether the clamp clears the insulator. Do not assume the side version fits where the front one does — on this one size it does not.

The 1 kV side range uses fewer bodies. Five side models share two shells — 142/116/84 for the two 120 mm² models, 153/116/84 for all three of the larger ones — while the five front models spread over four. One consequence: the front range reaches 156/118/95 at 35240 and the side range stops at 153/116/84. If the 35240 front clamp is already tight against something, the side one is 2 mm narrower and 11 mm shorter and may be the easier fit.

One row that does not fit

Look at 156/118/95. It appears twice:

  • as the 1 kV JBCD-35~240
  • as the 10 kV JBCD10-35~240

Nothing else in the 10 kV range is that size. Every other 10 kV clamp — front or side — is 160/145/115, and the side version of that same 35~240 clamp, JBCD10-35~240T, is 160/145/115.

A 10 kV clamp cannot be smaller than its own 1 kV equivalent; the insulation and creepage push it the other way every time, which is why 1 kV tops out at H 95, 10 kV sits at 115 and 20 kV at 115 on a wider body. So the printed 156/118/95 on the 10 kV row is the 1 kV figure. This size is 160/145/115, and that is what goes on the drawing. Where an old tender specifies 156 for a 10 kV clamp, tell us and the 160 is quoted against it.

Bolts

Nineteen of the twenty are two-bolt. The exception is the 1 kV 16~120, front and side, which is single-bolt on both. That is also the smallest clamp in the range and the one whose two versions differ most — the same fact from two directions.

Choosing between this and the branch clamp

This page is the grounding clamp: one conductor, one ring, no branch.

For a branch or jumper joint on the same kind of line, the JBC piercing clamp is the one you want — same teeth, same sealing body, but a second groove instead of a grounding ring, and it goes to 300 mm² at 10 kV.

A grounding point made with a branch clamp and a separate earth lead is a different thing and is not what this product is for: the ring here is a fixed part of the body, so the lead is clipped to a bonded point rather than wrapped around a live conductor.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: