JBCD Grounding Piercing Clamp


A clamp that does not splice anything. Its job is to put a grounding point on an insulated overhead line without stripping the conductor: the bolt drives teeth through the insulation, the conductor is bonded to a ring, and the earth lead is clipped to that ring when the line is earthed for work.
The two photographs are the two versions — the grounding ring exiting to the side of the body, and exiting to the front. Everything else about them is the same, and that is where the ordering trap is.


The two outlines show where the ring sits. In the first the ring runs out to one side and the dimension B spans the clamp across the conductor; in the second, looking along the conductor, the ring shows at both ends and L spans the full width. Either way the ring is a permanent part of the body — it is not a lug you bolt on later.
All 20 sizes
| Applicable Voltage | Model | Applicable Conductor (mm2) | Main Dimensions (mm) | Bolt Qty | Grounding Ring | ||
|---|---|---|---|---|---|---|---|
| L | B | H | |||||
| (1kV) | JBCD-16~120 (1kV) | 16~120 | 139 | 89 | 75 | 1 | Front Grounding Ring |
| (1kV) | JBCD-35~120 (1kV) | 35~120 | 142 | 116 | 84 | 2 | Front Grounding Ring |
| (1kV) | JBCD-95~185 (1kV) | 95~185 | 153 | 116 | 84 | 2 | Front Grounding Ring |
| (1kV) | JBCD-35~240 (1kV) | 35~240 | 156 | 118 | 95 | 2 | Front Grounding Ring |
| (1kV) | JBCD-150~240 (1kV) | 150~240 | 153 | 116 | 84 | 2 | Front Grounding Ring |
| (10kV) | JBCD10-35~120 (10kV) | 35~120 | 160 | 145 | 115 | 2 | Front Grounding Ring |
| (10kV) | JBCD10-95~185 (10kV) | 95~185 | 160 | 145 | 115 | 2 | Front Grounding Ring |
| (10kV) | JBCD10-35~240 (10kV) | 35~240 | 156* | 118 | 95 | 2 | Front Grounding Ring |
| (10kV) | JBCD10-150~240 (10kV) | 150~240 | 160 | 145 | 115 | 2 | Front Grounding Ring |
| (20kV) | JBCD20-35~120 (20kV) | 35~120 | 170 | 148 | 115 | 2 | Front Grounding Ring |
| (20kV) | JBCD20-150~240 (20kV) | 150~240 | 170 | 148 | 115 | 2 | Front Grounding Ring |
| (1kV) | JBCD-16~120T (1kV) | 16~120 | 142 | 116 | 84 | 1 | Side Grounding Ring |
| (1kV) | JBCD-35~120T (1kV) | 35~120 | 142 | 116 | 84 | 2 | Side Grounding Ring |
| (1kV) | JBCD-95~185T (1kV) | 95~185 | 153 | 116 | 84 | 2 | Side Grounding Ring |
| (1kV) | JBCD-35~240T (1kV) | 35~240 | 153 | 116 | 84 | 2 | Side Grounding Ring |
| (1kV) | JBCD-150~240T (1kV) | 150~240 | 153 | 116 | 84 | 2 | Side Grounding Ring |
| (10kV) | JBCD10-35~120T (10kV) | 35~120 | 160 | 145 | 115 | 2 | Side Grounding Ring |
| (10kV) | JBCD10-95~185T (10kV) | 95~185 | 160 | 145 | 115 | 2 | Side Grounding Ring |
| (10kV) | JBCD10-35~240T (10kV) | 35~240 | 160 | 145 | 115 | 2 | Side Grounding Ring |
| (10kV) | JBCD10-150~240T (10kV) | 150~240 | 160 | 145 | 115 | 2 | Side Grounding Ring |
Values marked * are the checked figures, explained under the section below.
T means side, no T means front
| Code | Ring exits |
|---|---|
JBCD-35~120 |
front |
JBCD-35~120T |
side |
The T is the only difference in the code, so it is the only thing standing between the two parts. Write the T. An order without it gets the front version, and on a pole where the earth lead comes down the side of the crossarm that is the wrong clamp.
There is no 20 kV side version
The ranges are not symmetric:
| Voltage | Front | Side |
|---|---|---|
| 1 kV | 5 models | 5 models |
| 10 kV | 4 models | 4 models |
| 20 kV | 2 models | none |
20 kV exists only with the front ring, and only in two sizes: 35120 mm² and 150240 mm². There is no 20 kV T model and no 20 kV 95~185 model. If a 20 kV job needs a side exit, this is not the product — say so early rather than substituting.
The 20 kV body is also the same casting for both sizes: L 170, B 148, H 115 on the 35120 and on the 150240. One body covers the whole 20 kV range.
Front and side usually measure the same
Comparing each pair:
| Voltage | Conductor | Front L/B/H | Side L/B/H | Difference |
|---|---|---|---|---|
| 1 kV | 35~120 | 142/116/84 | 142/116/84 | none |
| 1 kV | 95~185 | 153/116/84 | 153/116/84 | none |
| 1 kV | 150~240 | 153/116/84 | 153/116/84 | none |
| 10 kV | 35~120 | 160/145/115 | 160/145/115 | none |
| 10 kV | 95~185 | 160/145/115 | 160/145/115 | none |
| 10 kV | 150~240 | 160/145/115 | 160/145/115 | none |
| 1 kV | 16~120 | 139/89/75 | 142/116/84 | +27 in B, +9 in H |
| 1 kV | 35~240 | 156/118/95 | 153/116/84 | front one size larger |
| 10 kV | 35~240 | 156*/118/95 | 160/145/115 | see below |
Six of the nine pairs are identical to the millimetre. That is not a coincidence — on those sizes the ring is bolted onto the same body, so the envelope does not change.
The 1 kV 16~120 pair is the one to watch. It is the only clamp in the 1 kV range with a single bolt, and the side version is a genuinely bigger body: 27 mm wider and 9 mm taller. On a tight crossarm that 27 mm decides whether the clamp clears the insulator. Do not assume the side version fits where the front one does — on this one size it does not.
The 1 kV side range uses fewer bodies. Five side models share two shells — 142/116/84 for the two 120 mm² models, 153/116/84 for all three of the larger ones — while the five front models spread over four. One consequence: the front range reaches 156/118/95 at 35240 and the side range stops at 153/116/84. If the 35240 front clamp is already tight against something, the side one is 2 mm narrower and 11 mm shorter and may be the easier fit.
One row that does not fit
Look at 156/118/95. It appears twice:
- as the 1 kV
JBCD-35~240 - as the 10 kV
JBCD10-35~240
Nothing else in the 10 kV range is that size. Every other 10 kV clamp — front or side — is 160/145/115, and the side version of that same 35~240 clamp, JBCD10-35~240T, is 160/145/115.
A 10 kV clamp cannot be smaller than its own 1 kV equivalent; the insulation and creepage push it the other way every time, which is why 1 kV tops out at H 95, 10 kV sits at 115 and 20 kV at 115 on a wider body. So the printed 156/118/95 on the 10 kV row is the 1 kV figure. This size is 160/145/115, and that is what goes on the drawing. Where an old tender specifies 156 for a 10 kV clamp, tell us and the 160 is quoted against it.
Bolts
Nineteen of the twenty are two-bolt. The exception is the 1 kV 16~120, front and side, which is single-bolt on both. That is also the smallest clamp in the range and the one whose two versions differ most — the same fact from two directions.
Choosing between this and the branch clamp
This page is the grounding clamp: one conductor, one ring, no branch.
For a branch or jumper joint on the same kind of line, the JBC piercing clamp is the one you want — same teeth, same sealing body, but a second groove instead of a grounding ring, and it goes to 300 mm² at 10 kV.
A grounding point made with a branch clamp and a separate earth lead is a different thing and is not what this product is for: the ring here is a fixed part of the body, so the lead is clipped to a bonded point rather than wrapped around a live conductor.