PF Power Fittings Technical Reference

DG Ground Wire Terminal

Models: DG-35BG – DG-185G · Conductor: 35–185 mm² · Reference Weight: 0.4–1.3 kg · Bores: 9.0–19.0 mm

One Code, Two Materials

The DG terminal is named after the conductor it is made for. DG-120BG and DG-120G are both for a 120 mm² wire and they are two different pieces of hardware:

Series Body Material For
DG-xxBG Cast, short Aluminium alloy Aluminium and ACSR conductors, 35–185 mm²
DG-xxG Long body Hot-dip galvanised steel Steel strand, 70–185 mm²

The BG covers nine sizes from 35 up; the G starts at 70 and stops at 185, six sizes. Pick by the strand material first — a terminal for steel strand on an aluminium conductor is the wrong galvanic couple and the wrong bore, and no amount of re-drilling fixes the couple.

d Is the Wire, Not the Area

The second column, d, is printed to a tenth of a millimetre: 9.0, 10.5, 11.0, 12.5, 13.0, 14.5, 16.0, 17.5, 19.0.

That is the outside diameter of the conductor the terminal grips — not the cross-section, not the bolt, not the body. It is the one number you have to get exactly right, because these terminals are made to a size and are not range clamps: there is no second bore and no adapter.

Which makes this table the important one on the page:

Size Bore, aluminium (BG) Bore, steel (G) Difference
70 12.5 mm 11.2 mm 1.3 mm
80 13.0 12.1 0.9
100 14.5 13.7 0.8
120 16.0 15.2 0.8
150 17.5 16.7 0.8
185 19.0 18.3 0.7

The same model number is 0.7 to 1.3 mm narrower on the G series, and the gap shrinks as the size grows. The BG terminal is for aluminium strand and the G terminal for galvanised steel strand, and the two materials do not come out at the same diameter for the same nominal area.

So DG-120BG and DG-120G are not interchangeable, and the number alone does not tell you which wire you are holding. Measure the strand, then pick the series.

D and Φ Are the Palm and the Bolt

  • D — the outside width of the terminal body: 18 mm on the three smallest, then 20, 24, 26, 28, 32 and 38.
  • Φ — the bolt hole through the palm: 18, 20 or 22 mm on the BG, a flat 20 mm on the G. This is what the terminal is bolted down with and it has nothing to do with the conductor size.
  • L1 — the length of the body from the palm: 50 to 100 mm on the cast series, 60 to 105 mm on the G.

The G Series Is the Long Body

The G terminal runs L 125 to 170 mm overall against L1 50 to 100 mm on the cast part for the same conductor. That extra reach is the reason to take it: if the terminal has to clear a bundle spacer, a jumper or a second earth wire, the cast body will not get there.

Both are single-piece and both are bolted at the palm. The difference is body length and material, nothing else.

What The Weight Column Is For

The DG-BG masses read 0.4, 0.4, 0.4, 0.7, 0.6, 0.7, 0.6, 1.3, 1.2 kg, and they do not climb with the bore. That is the casting, not a slip: the mass follows the palm boss as much as the bore.

The nine rows fall into four boss sizes — D 18 with Φ 18 (35 to 55), D 20 with Φ 20 (70 and 80), D 24 with Φ 20 and 22 (100 and 120), D 28 with Φ 22 (150 and 185). Inside a boss group the bore takes metal out of the wall, so the larger conductor is the lighter casting: 80 below 70, 120 below 100, 185 below 150. Between groups the boss adds more than the bore removes, which is where the 0.7 and 1.3 kg steps come from.

So the column is a reference mass for freight, quoted to 0.1 kg, and it is consistent with the geometry row by row. For the connection, the number that matters is d.

The G series is a welded steel body quoted by dimension; unit masses are supplied with the quotation when freight has to be calculated.

Technical Parameters

DG-xxBG, aluminium alloy

DG Ground Wire TerminalDG Ground Wire Terminal DG Ground Wire Terminal

ModelMain Dimensions (mm)Reference Weight (kg)
DdΦL1
DG-35BG189.018500.4
DG-50BG1810.518500.4
DG-55BG1811.018600.4
DG-70BG2012.520600.7
DG-80BG2013.020600.6
DG-100BG2414.520800.7
DG-120BG2416.022800.6
DG-150BG2817.5221001.3
DG-185BG2819.0221001.2

DG-xxG, hot-dip galvanised steel

DG Ground Wire TerminalDG Ground Wire Terminal

ModelMain Dimensions (mm)
DdΦLL1W
DG-70G2611.2201256040
DG-80G2612.1201256040
DG-100G2813.7201357040
DG-120G2815.2201458040
DG-150G3216.7201559040
DG-185G3818.32017010540

The light pressed terminal for aluminium-clad steel strand: JDBG ground wire terminal. The bolted short terminal to GB 2008: JDG ground wire terminal. Insulated grounding clamps for the same conductors: JDL grounding clamp, FDJ fully insulated grounding device. Bolts and nut caps for the palm: FX anti-theft nut cap.

Note: d is the conductor outside diameter, not the area, and the same model number is 0.7 to 1.3 mm narrower on the G series — DG-120BG and DG-120G take different wires. Φ is the palm bolt hole, not the conductor. The BG weight column has no monotonic trend; the G series has no weight column at all, and its body runs 125 to 170 mm against L1 50 to 100 on the cast part.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: