JDBG Ground Wire Terminal
Models: JDBG-80 – JDBG-150 · Conductor: 80–150 mm² aluminium-clad steel strand · Bores: 13.0–17.5 mm · Reference Weight: 0.12–0.28 kg
A Tenth of the Mass
JDBG is the pressed and bolted ground wire terminal, and the weight is the whole story: 0.12 to 0.28 kg, against 0.4 to 1.3 kg for the cast DG terminal on the same conductors. At 80 mm² that is 0.12 kg against 0.6 kg — one fifth, and at 150 mm² it is 0.28 against 1.3.
The body is a thin pressed sleeve with a bolted palm rather than a casting. Nothing about the rating changes with it; what changes is how much metal is in your hand and on the freight manifest.
Use it where the joint is a grounding tap on aluminium-clad steel strand and the mechanical duty is light. Use the cast DG where the terminal is a load-bearing part of the earthing system, or where it will be crimped and then buried.
Bored to the Aluminium Side
The strand this terminal is made for is aluminium on the outside — LBGJ and the aluminium-clad steel ropes — so it takes the same bore as an aluminium conductor of that size, not the narrower one of a galvanised steel strand.
That shows up directly against the other two series:
| Size | JDBG | DG-BG series | DG-G series |
|---|---|---|---|
| 80 | 13.0 | 13.0 | 12.1 |
| 100 | 15.0 | 14.5 | 13.7 |
| 120 | 16.0 | 16.0 | 15.2 |
| 150 | 17.5 | 17.5 | 16.7 |
JDBG runs 0.8 to 1.3 mm wider than the galvanised steel terminal of the same number, and it matches the aluminium terminal exactly on three of the four sizes.
The exception is 100 mm², where JDBG is 0.5 mm wider than DG-100BG — 15.0 against 14.5. Small, but these are fixed-bore terminals with no adapter, so half a millimetre decides whether the strand goes in.
The Columns It Adds
Beyond D and d, the JDBG sheet prints two dimensions the cast series does not:
- b — the palm thickness: 8 mm on the two smaller sizes, 10 mm on the two larger.
- S and a — the palm and the offset behind it, 40 and 65 mm on the two smaller sizes, 50 and 85 mm on the two larger.
Together with L1 they fix the shape of the bolted palm: 40 × 65 mm behind a 70 to 80 mm body on the small pair, 50 × 85 mm behind an 80 to 90 mm body on the large pair. If the terminal has to clear a plate edge or land on a flat bar of a given width, S is the number to check — it is the one dimension that does not exist on the cast part.
Technical Parameters


| General Design Model | Main Dimensions (mm) | Reference Weight (kg) | |||||
|---|---|---|---|---|---|---|---|
| D | d | b | S | a | L1 | ||
| JDBG-80 | 22 | 13.0 | 8 | 40 | 65 | 70 | 0.12 |
| JDBG-100 | 26 | 15.0 | 8 | 40 | 65 | 80 | 0.16 |
| JDBG-120 | 26 | 16.0 | 10 | 50 | 85 | 80 | 0.21 |
| JDBG-150 | 30 | 17.5 | 10 | 50 | 85 | 90 | 0.28 |
Related Pages
The cast terminal in two materials, 35 to 185 mm²: DG ground wire terminal. The bolted short terminal for bare steel strand: JDG ground wire terminal. Splice sleeves for the same strand: JY-BG. Insulated grounding clamps: JDL grounding clamp.
Note: JDBG is a pressed and bolted body at 0.12 to 0.28 kg, against 0.4 to 1.3 kg cast for the same conductors — a fifth of the mass at the small end. It is bored to the aluminium side of the strand: 0.8 to 1.3 mm wider than the DG-G terminal of the same number, and matching DG-BG on three of four sizes, 0.5 mm wider on 100. S and a, the bolted palm dimensions, exist only on this sheet.