ACAR Conductor Table, ASTM B524, 4/3 Stranding
13 rows · 30.58 to 246.9 kcmil · ASTM B524 · 4 aluminium over 3 alloy wires
ACAR is Aluminium Conductor Alloy Reinforced. Two metals again, but not the ACSR pair: the core is 6201 aluminium alloy and the outer layer is 1350 aluminium, both of them aluminium. There is no steel anywhere in the conductor, so there is no bimetallic joint to corrode and no magnetic core to add loss.
The point of the combination is that the two wires do different jobs. The 1350 outer wires conduct at about 61 per cent IACS; the 6201 core carries about 295 N/mm² of tensile strength. ACAR is stronger than AAC and lighter than ACSR, with the corrosion behaviour of an all-aluminium conductor. Where a line runs along a coast and still needs a long span, this is the type that answers both.
| Area kcmil | Total Area mm2 | 1350 Al mm2 | 6201 Alloy mm2 | Single Wire Dia. mm | Wires Al / Alloy | Overall Dia. mm | Weight kg/km | Rated Strength kN | DC Resistance at 20 °C Ω/km |
|---|---|---|---|---|---|---|---|---|---|
| 30.58 | 15.5 | 8.9 | 6.6 | 1.679 | 4 / 3 | 5.04 | 42.4 | 3.67 | 1.980 |
| 41.74 | 21.1 | 12.1 | 9.1 | 1.961 | 4 / 3 | 5.88 | 57.9 | 4.97 | 1.450 |
| 48.69 | 24.7 | 14.1 | 10.6 | 2.118 | 4 / 3 | 6.35 | 67.5 | 5.76 | 1.240 |
| 66.36 | 33.7 | 19.2 | 14.4 | 2.474 | 4 / 3 | 7.42 | 92.1 | 7.79 | 0.909 |
| 77.47 | 39.3 | 22.4 | 16.8 | 2.672 | 4 / 3 | 8.02 | 107.5 | 8.94 | 0.778 |
| 105.6 | 53.5 | 30.6 | 22.9 | 3.119 | 4 / 3 | 9.36 | 146.5 | 12.00 | 0.571 |
| 123.3 | 62.5 | 35.7 | 26.8 | 3.371 | 4 / 3 | 10.11 | 171.1 | 13.65 | 0.489 |
| 133.1 | 67.5 | 38.6 | 28.9 | 3.503 | 4 / 3 | 10.51 | 184.7 | 14.70 | 0.453 |
| 155.4 | 78.8 | 45.0 | 33.8 | 3.785 | 4 / 3 | 11.36 | 215.7 | 17.10 | 0.387 |
| 167.8 | 85.0 | 48.6 | 36.4 | 3.932 | 4 / 3 | 11.80 | 232.8 | 18.30 | 0.361 |
| 195.7 | 99.2 | 56.7 | 42.5 | 4.247 | 4 / 3 | 12.74 | 271.6 | 21.30 | 0.309 |
| 211.6 | 107.3 | 61.3 | 46.0 | 4.417 | 4 / 3 | 13.25 | 293.7 | 23.00 | 0.285 |
| 246.9 | 125.1 | 71.5 | 53.6 | 4.770 | 4 / 3 | 14.31 | 342.6 | 26.90 | 0.245 |
Every Cell Reproduces From The Stranding
The two section columns are the four outer wires and the three core wires, each from its own diameter:
- 4 × π/4 × 1.679² = 8.86 mm², printed 8.9.
- 3 × π/4 × 1.679² = 6.64 mm², printed 6.6.
- Their sum, 15.5 mm², is the total in the second column.
That holds down the whole page: 4 × π/4 × 4.770² = 71.5 and 3 × π/4 × 4.770² = 53.6, printed 71.5 and 53.6, summing to 125.1. All thirteen rows close to the printed tenth. The overall diameter is exactly three wire diameters, 3 × 1.679 = 5.04 through 3 × 4.770 = 14.31, so there is no allowance for the outer layer standing proud.
The Mix Is Fixed, The Strength Is Not
The aluminium share of the section barely moves — 57.4 per cent on the first row, 57.2 per cent on the last — because the stranding stays at four over three all the way down.
The rated strength does not stay flat with it. It falls from 237 to 214 N/mm² of total section, a tenth of the value, while the proportion of strong wire to weak wire is unchanged.
- 30.58 kcmil: 3.67 kN over 15.5 mm² = 236.8 N/mm².
- 105.6 kcmil: 12.00 over 53.5 = 224.3 N/mm².
- 246.9 kcmil: 26.90 over 125.1 = 215.0 N/mm².
With the mix constant, the decline cannot come from the mix. It is in the wire itself: a 6201-T81 wire loses tensile strength as its diameter grows, and the same 4/3 pattern therefore gets weaker per square millimetre as it is scaled up. Anyone who assumes a single strength per type, and carries the small-size figure up to a 4/0, will overstate the break by about ten per cent.
Resistance Is Section, Not Mix
The resistance column tracks the total section almost exactly inversely:
- 1.980 Ω/km × 15.5 mm² = 30.7.
- 0.245 Ω/km × 125.1 mm² = 30.6.
That product is the equivalent resistivity of the conductor in Ω·mm²/km, and it is flat to a tenth of a per cent across the page. Divided out, the conductor behaves as though it were a single metal of 0.0307 Ω·mm²/m at 20 °C.
Two things sit behind that number. The two wires in parallel would give 0.0301 — between the 0.0283 of the 1350 outer wires and the 0.0328 of the 6201 core, weighted by how much of each is in the section. The printed figures are about two per cent above that, which is the length of extra wire in the lay.
So resistance is set by total section, and the alloy ratio barely moves it. Against the same section in all aluminium, a 4/3 ACAR conducts roughly six per cent worse — the price of the stronger core — which is a far smaller difference than the strength it gains.
One Stranding Out Of Fourteen
ASTM B524 does not list one conductor per size. It lists a size per stranding, and the same area appears several times under different wire counts: 12/7, 15/4, 18/19, 24/13, 30/7, 33/4, 33/28, 42/19, 48/13, 54/7, 54/37, 63/28 and 72/19 all appear in the standard beside this 4/3 group.
This page reproduces the 4/3 group only — 30.58 to 246.9 kcmil, which is #6 AWG up to 4/0 AWG, the range a distribution line is actually built from. Everything above 246.9 kcmil is stranded differently and is not on this page. A purchase order that names only the kcmil figure does not yet name a conductor; the stranding has to be added.
What Is Missing
- No code words. ACAR is quoted by area and stranding here, not by the bird names used for ACSR.
- No ampacity.
- No modulus, expansion or sag.
- No rows above 246.9 kcmil, and no stranding other than 4/3.
Related Pages
The other conductor tables: AAAC, ACSR, AAC, AACSR/AW, GSW, TACSR. Back to the designation reference.
Note: Thirteen rows of the 4/3 stranding, 30.58 to 246.9 kcmil. Each section column reproduces from four and three wires of the stated diameter, and every overall diameter is exactly 3d. Rated strength falls from 237 to 214 N/mm² of section across the page while the aluminium share of the section stays at 57 per cent, so the decline is in the wire and not in the mix. Resistance times section is flat at 30.6 to 30.7 across all thirteen rows.