MGTS Copper Steel Transition Plate

Models: 12 sizes · Reference Weight: 0.2–2.4 kg · Function: copper-to-steel transition for rectangular busbar
One Plate, Two Metals
Bolting a copper busbar straight onto galvanised steel puts two dissimilar metals in contact with an electrolyte between them, and the copper side loses. A transition plate is copper on one end and steel on the other, welded or brazed at the middle, so the joint at each end is the same metal.
The model number is the busbar it matches — 63×6.3 means 63 mm wide, 6.3 mm thick. That is the only thing you have to read to order: match the bar.
Copper End, Steel End, and the Bar Width
The legend on this table is three words — Copper, Steel, Width — and they map to L1, L2 and A:
| Bar width A | Copper end L1 | Steel end L2 |
|---|---|---|
| 50 mm | 50 | 60 |
| 63 mm | 68 | 85 |
| 80 mm | 85 | 100 |
| 100 mm | 105 | 120 |
| 125 mm | 130 | 140 |
L1 is A + 5 mm on every width except the 50, where it equals A. L2 is always the longer of the two — the steel end runs 10 to 22 mm beyond the bar width so the bolt sits clear of the joint.
So the plate is longer than the bar is wide at both ends. If L1 and L2 are measured from the joint, the plate is L1 + L2 long — check that against your clearance; a 125 mm bar is not a 125 mm plate.
Thickness Is the Third Choice
The same width comes in up to three thicknesses — 63 mm in 6.3, 8 and 10; 80 mm in 6.3, 8 and 10; 125 mm in 8, 10 and 12.5. The weight follows the thickness almost exactly:
| Size | Weight |
|---|---|
| 63×6.3 | 0.3 kg |
| 63×8 | 0.4 kg |
| 63×10 | 0.5 kg |
| 125×8 | 1.5 kg |
| 125×10 | 1.9 kg |
| 125×12.5 | 2.4 kg |
So a plate in the wrong thickness is a plate with the wrong current capacity — match both figures, not just the width.
50 × 5 Is the Outlier
The smallest size, 50×5, is the only one where L1 equals the bar width and L2 is only 60 mm. It is also the lightest at 0.2 kg. Every other width runs A+5 for L1.
If you are working to a tight space at 50 mm, this is the one to use — and the one not to extrapolate from.
Technical Parameters
| Model | Applicable Busbar | Main Dimensions (mm) | Reference Weight (kg) | |||
|---|---|---|---|---|---|---|
| A | L1 | L2 | B | |||
| MGTS-50×5 | 50×5 | 50 | 50 | 60 | 5 | 0.2 |
| MGTS-63×6.3 | 63×6.3 | 63 | 68 | 85 | 6.3 | 0.3 |
| MGTS-63×8 | 63×8 | 63 | 68 | 85 | 8 | 0.4 |
| MGTS-63×10 | 63×10 | 63 | 68 | 85 | 10 | 0.5 |
| MGTS-80×6.3 | 80×6.3 | 80 | 85 | 100 | 6.3 | 0.5 |
| MGTS-80×8 | 80×8 | 80 | 85 | 100 | 8 | 0.7 |
| MGTS-80×10 | 80×10 | 80 | 85 | 100 | 10 | 0.8 |
| MGTS-100×8 | 100×8 | 100 | 105 | 120 | 8 | 1.0 |
| MGTS-100×10 | 100×10 | 100 | 105 | 120 | 10 | 1.3 |
| MGTS-125×8 | 125×8 | 125 | 130 | 140 | 8 | 1.5 |
| MGTS-125×10 | 125×10 | 125 | 130 | 140 | 10 | 1.9 |
| MGTS-125×12.5 | 125×12.5 | 125 | 130 | 140 | 12.5 | 2.4 |
Related Pages
Copper-aluminium transition plates: MG brazed, MGB explosion welded. Dual-metal sheets: TLYP copper aluminium composite. Rectangular busbar supports: MNP indoor flat, MWP outdoor flat.
Note: The model number is the busbar width × thickness — match both. L1 and L2 are longer than the bar is wide, so the plate needs clearance beyond the bar at both ends.