PF Power Fittings Technical Reference

MGTZ Tubular Busbar Support Fitting

MGTZ tubular busbar support fitting

Models: 2 sizes · Reference Weight: not published · Function: support fitting

Two Sizes, One Column of Dimensions

Model Applicable Tubular Busbar Bore Ø
MGTZ-200 200 / 180 200 mm
MGTZ-250 250 / 230 250 mm

The busbar column prints a pair of figures 20 mm apart. Read as outside diameter and bore, that is a tube with a 10 mm wall — which is the usual wall for a 200 or 250 mm aluminium bus.

What the clamp cares about is the first figure, the outside diameter. The bore is reference: useful when you are matching a run that already exists, not something you have to specify.

Where This Fitting Sits in the Run

The figure above is the assembly the fitting belongs to, not a part drawing: one tubular busbar with an end cap at one end, fixed clamps along it, sliding clamps between them, and support brackets carrying the whole thing.

Each of those parts has its own page:

If you are building a run rather than replacing one part, tell us the busbar diameter, the span and the fault level, and we will lay the supports out.

What the Catalogue Does Not Publish

This is the shortest table in the tubular busbar section, and that is worth stating plainly. It gives a model, a bore and nothing else:

  • No weight — so it cannot be costed for freight from this page
  • No height H — so it cannot be used to set the bus level
  • No bolt size, no base plate — so the anchor cannot be designed

The other support clamps on this site publish all three, which is why they are the ones to design from. Use MGTZ where a specification already calls for it, and ask us for the part drawing first.

Technical Parameters

ModelApplicable Tubular Busbar (mm)Main Dimensions (mm)
Ø
MGTZ-200200/180200
MGTZ-250250/230250

Support clamps with full dimensions and weights: MGG fixed, MGG1 sliding, MGG2 fixed at sliding height. End caps: MGF, MGF1 damping type. Expansion clamps: MGGD.

Note: Two sizes, bore only. Send the actual busbar outside diameter, and ask us for the part drawing before designing anchor or support steel from this page.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: