NELJ Quick-Bolt Wedge Strain Clamp
Models: NELJ-1 – NELJ-4 · Conductor: covered JKLGYJ, 25–400 mm² · Voltage: 10 kV and 20 kV · Rated Failure Load: 50–120 kN

NELJ is the dead-end for covered overhead conductor — the insulated aluminium cable strung on 10 kV and 20 kV distribution lines. It is a wedge clamp: the conductor drops into the body, an aluminium alloy wedge core is driven in behind it, and the harder the conductor pulls, the tighter the wedge sets. No press, no dies, and no stripping — the insulation stays on, which is the whole reason the product exists.
One conductor, two clamps
This is the thing to understand before reading the table. The same conductor is a different size at 10 kV and at 20 kV, because the insulation is thicker:
| Conductor | 10 kV OD | 20 kV OD | Increase |
|---|---|---|---|
| 35/6 | 16.0 mm | 19.9 mm | +3.9 mm |
| 50/8 | 17.0 mm | 21.2 mm | +4.2 mm |
| 95/15 | 21.6 mm | 25.1 mm | +3.5 mm |
| 240/30 | 29.6 mm | 32.4 mm | +2.8 mm |
Four millimetres of extra insulation moves a 50 mm² conductor out of NELJ-1 and into NELJ-2. So the sheet has two diameter columns and two wedge-core columns, and half the rows are deliberately blank on one side:
- NELJ-1 at 50/8 and 70/10 is a 10 kV clamp only. At 20 kV those conductors are NELJ-2.
- NELJ-2 at 50/8 and 70/10 exists for 20 kV only. At 10 kV they are NELJ-1.
- NELJ-1 at 25/4 is 20 kV only — the 10 kV column is empty because a 25 mm² covered conductor is not used at 10 kV.
An order that says “NELJ-1 for 50/8” without a voltage is an incomplete order. Both are valid; they are different fittings.
The wedge core is a third number
Every row names a wedge core — NELJ-1-1, NELJ-2-1, NELJ-3-1, NELJ-3-2, NELJ-4-1, NELJ-4-2. The core is selected by the outside diameter including insulation, not by the body:
- NELJ-3 uses the -1 core up to 240/40 and switches to the -2 core at 300/15 on 10 kV.
- On 20 kV the switch happens earlier, at 240/30, because the insulated diameter is already past what the -1 core grips.
The body and the core ship together, and they are not interchangeable across voltage. A NELJ-3 body with a -1 core on a 20 kV 300/25 conductor will not hold, and it will look as if it has been fitted correctly.
Technical parameters
| Body | Conductor (mm²) | Covered conductor, 10 kV | Covered conductor, 20 kV | Grip Strength (kN) | Rated Failure Load (kN) | ||
|---|---|---|---|---|---|---|---|
| OD (mm) | Wedge core | OD (mm) | Wedge core | ||||
| NELJ-1 | 25/4 | 17.5 | NELJ-1-1 | 6.1 | 50 | ||
| NELJ-1 | 35/6 | 16.0 | NELJ-1-1 | 19.9 | NELJ-1-1 | 8.3 | 50 |
| NELJ-1 | 50/8 | 17.0 | NELJ-1-1 | 11.0 | 50 | ||
| NELJ-1 | 70/10 | 19.2 | NELJ-1-1 | 15.3 | 50 | ||
| NELJ-2 | 50/8 | 21.2 | NELJ-2-1 | 11.0 | 70 | ||
| NELJ-2 | 70/10 | 22.9 | NELJ-2-1 | 15.3 | 70 | ||
| NELJ-2 | 95/15 | 21.6 | NELJ-2-1 | 25.1 | NELJ-2-1 | 23.0 | 70 |
| NELJ-2 | 95/20 | 21.9 | NELJ-2-1 | 25.6 | NELJ-2-1 | 24.2 | 70 |
| NELJ-2 | 120/7 | 22.5 | NELJ-2-1 | 25.7 | NELJ-2-1 | 18.0 | 70 |
| NELJ-2 | 120/20 | 23.1 | NELJ-2-1 | 26.5 | NELJ-2-1 | 26.7 | 70 |
| NELJ-2 | 120/25 | 23.7 | NELJ-2-1 | 26.7 | NELJ-2-1 | 31.2 | 70 |
| NELJ-2 | 150/8 | 24.0 | NELJ-2-1 | 27.1 | NELJ-2-1 | 21.4 | 70 |
| NELJ-2 | 150/20 | 24.7 | NELJ-2-1 | 27.9 | NELJ-2-1 | 30.4 | 70 |
| NELJ-2 | 150/25 | 25.1 | NELJ-2-1 | 28.2 | NELJ-2-1 | 35.2 | 70 |
| NELJ-2 | 150/35 | 25.5 | NELJ-2-1 | 28.8 | NELJ-2-1 | 42.3 | 70 |
| NELJ-3 | 185/10 | 26.0 | NELJ-3-1 | 29.0 | NELJ-3-1 | 26.6 | 100 |
| NELJ-3 | 185/25 | 26.9 | NELJ-3-1 | 29.7 | NELJ-3-1 | 38.7 | 100 |
| NELJ-3 | 185/30 | 26.9 | NELJ-3-1 | 29.7 | NELJ-3-1 | 42.5 | 100 |
| NELJ-3 | 240/30 | 29.6 | NELJ-3-1 | 32.4 | NELJ-3-2 | 49.2 | 100 |
| NELJ-3 | 240/40 | 29.7 | NELJ-3-1 | 32.5 | NELJ-3-2 | 54.2 | 100 |
| NELJ-3 | 300/15 | 29.8 | NELJ-3-2 | 33.5 | NELJ-3-2 | 44.3 | 100 |
| NELJ-3 | 300/20 | 29.8 | NELJ-3-2 | 33.9 | NELJ-3-2 | 49.2 | 100 |
| NELJ-3 | 300/25 | 30.3 | NELJ-3-2 | 34.2 | NELJ-3-2 | 54.3 | 100 |
| NELJ-3 | 300/40 | 30.5 | NELJ-3-2 | 34.7 | NELJ-3-2 | 60.0 | 100 |
| NELJ-4 | 400/20 | 32.5 | NELJ-4-1 | 37.7 | NELJ-4-2 | 57.8 | 120 |
| NELJ-4 | 400/25 | 33.0 | NELJ-4-1 | 37.5 | NELJ-4-2 | 62.4 | 120 |
| NELJ-4 | 400/35 | 33.0 | NELJ-4-1 | 37.6 | NELJ-4-2 | 67.6 | 120 |
All dimensions in millimetres. A blank cell means the combination is not made — the conductor is covered by a different body at that voltage.
Grip and rated failure load are two different numbers
The last two columns are often confused, and they are not the same thing:
- Grip strength is what the clamp holds on that conductor. On 185/30 it is 42.5 kN; on 185/10 it is 26.6 kN. Same body, different conductor, so the number moves.
- Rated failure load is what the body is built to take: 50 kN for NELJ-1, 70 for NELJ-2, 100 for NELJ-3, 120 for NELJ-4.
The grip figure is the one to check against the span tension. The rated failure load is the one to check against the string’s ultimate requirement.
Fitting it
- Do not strip the insulation. NELJ grips the covered conductor. A stripped conductor in this clamp is a conductor with no grip.
- Match the wedge core to the model and voltage. The core is stamped; check it against the table, not against the box.
- Drive the wedge home with the proper tool, not a hammer. It is a quick-bolt wedge: it needs to seat square and to the mark.
- One body, one conductor. The wedge takes a set; the sheet says the clamp can be dismantled and re-used, but the core should be matched again each time.
- No press, no dies, no crimp length. On a covered-conductor line that is the whole point.
One anomaly on the sheet
The three NELJ-4 rows on 20 kV read 37.7, 37.5 and 37.6 mm for 400/20, 400/25 and 400/35. The diameters should climb with the steel area, so the 400/20 figure looks like a slip. All three take the same -2 core, so it does not change the order — but if 37.7 mm is on your drawing, check it against the conductor actually supplied.
Related
- NEL — the same wedge principle for bare ACSR, with no insulation to leave on.
- NXL — wedge clamp with a U-bolt body for insulated cable.
- NXJ — bundled covered conductor.
- NLL — bolted clamp for bare conductor.
Note: Quote body, conductor and voltage. The wedge core follows from the three, and it is not interchangeable between 10 kV and 20 kV at the same conductor.