Models: FDN-1/G, 2/G, 3/G, 1/2, 2/3, 3/4, 4/5, 4/6 · Rows: 46 conductor sizes · Reference Weight: 1.7–5.4 kg

This Is a Lookup Table
Every other damper page gives you dimensions. This one gives you a matching table: you bring the conductor, it tells you which damper.
Read it as four parallel columns — ACSR, aluminium strand, galvanised steel strand, aluminium-clad steel strand — and forty-six rows of conductor codes. The damper model appears once at the top of each block and the cells below it are blank on purpose: a blank means “the same damper as the model above”.
The block for FDN-2/3, for example, runs from LGJ-120/70 down to LGJ-185/10 and across to LJ-185, GJ-185 and GLB-185. One damper, eight conductor sizes.
Do not read a blank as “not applicable”. Only a genuinely empty conductor code means the damper is not offered for that conductor type.
Eight Models, Not Fourteen
The heading says fourteen sizes. The table carries eight model numbers — 1/G, 2/G, 3/G, 1/2, 2/3, 3/4, 4/5, 4/6 — and eight weights.
The larger number probably counts conductor families or catalogue variants. Quote a model number, never a count.
The G Models Are for Steel Strand
The three /G models — FDN-1/G, 2/G, 3/G — are the ones that appear in the steel strand and aluminium-clad steel strand columns with matching sizes, and in the ACSR column only for the small 35–95 mm² conductors.
That is the same split as on the FD page: a damper tuned for steel strand is not the same as one tuned for ACSR of the same nominal area. FDN-1/G and FDN-2/G both weigh 1.7 kg and are not interchangeable — one is for 35 mm², the other reaches 70 mm².
From FDN-1/2 upward the carbon-steel strand columns thin out and then stop: FDN-3/4 has no GJ or GLB entry beyond 185, FDN-4/5 and 4/6 have none at all. Above 185 mm² of steel strand this table no longer offers a damper; those conductors are earth wires and take the FD/FG family instead.
Some Cells Hold Two Codes
Several cells print two conductor codes run together: GJ-95GJ-100, GLB-95GLB-100, LJ-120LJ-150, LJ-210LJ-240.
Each is two sizes with the separator lost in the original typesetting — GJ-95 and GJ-100, LJ-120 and LJ-150. They are two conductors, both covered by the damper on that row. Nothing is missing; the cell is just crowded.
Worth knowing when you search the table for a code: a plain text search for GJ-100 will not find GJ-95GJ-100. Search for the numeric part.
The Weights Are the Model’s, Not the Conductor’s
1.7, 1.7, 2.0, 2.5, 3.4, 4.2, 5.1, 5.4 kg — eight figures for eight models, and the conductor inside a block does not change the damper.
So a 120 mm² ACSR and a 150 mm² ACSR take the same 2.5 kg unit, and the weight tells you which model you have, not which conductor it was bought for. On site, that is the only way to tell an FDN-1/2 from an FDN-2/3 without reading the marking: 2.5 kg against 3.4 kg.
Technical Parameters

| Model | Reference Weight(kg) | Applicable Conductor(mm2) | |||
|---|---|---|---|---|---|
| ACSR | Aluminum Strand | Galvanized Steel Strand | Aluminum-Clad Steel Strand | ||
| FDN-1/G | 1.7 | LGJ-35/6 | LJ-35 | GJ-35 | GLB-35 |
| FDN-2/G | 1.7 | LGJ-50/8 | LJ-50 | GJ-50 | GLB-50 |
| GJ-55 | GLB-55 | ||||
| LGJ-50/30 | LJ-70 | GJ-70 | GLB-70 | ||
| LGJ-70/10 | GJ-80 | GLB-80 | |||
| FDN-3/G | 2.0 | LGJ-70/40 | LJ-95 | GJ-95GJ-100 | GLB-95GLB-100 |
| LGJ-95/15 | |||||
| LGJ95/20 | |||||
| FDN-1/2 | 2.5 | LGJ-95/55 | LJ-120LJ-150 | GJ-120GJ-150 | GLB-120GLB-150 |
| LGJ-120/7 | |||||
| LGJ-120/20 | |||||
| LGJ-120/25 | |||||
| LGJ-150/8 | |||||
| FDN-2/3 | 3.4 | LGJ-120/70 | LJ-185 | GJ-185 | GLB-185 |
| LGJ-150/20 | |||||
| LGJ-150/25 | |||||
| LGJ-150/35 | |||||
| LGJ-185/10 | |||||
| FDN-3/4 | 4.2 | LGJ-185/25 | LJ-210LJ-240 | ||
| LGJ-185/30 | |||||
| LGJ-185/45 | |||||
| LGJ-210/10 | |||||
| LGJ-210/25 | |||||
| LGJ-210/35 | LJ-300 | ||||
| LGJ-210/50 | |||||
| LGJ-240/30 | |||||
| LGJ-240/40 | |||||
| LGJ-240/55 | |||||
| FDN-4/5 | 5.1 | LGJ-300/15 | |||
| LGJ-300/20 | |||||
| LGJ-300/25 | |||||
| LGJ-300/40 | |||||
| LGJ-300/50 | |||||
| LGJ-300/70 | |||||
| LGJ-400/20 | LJ-400 | ||||
| LGJ-400/25 | |||||
| LGJ-400/35 | |||||
| LGJ-400/50 | |||||
| LGJ-400/65 | |||||
| FDN-4/6 | 5.4 | LGJ-400/95 | LJ-500 | ||
| LGJ-500/35 | |||||
| LGJ-500/45 | |||||
| LGJ-500/65 | |||||
| LGJ-630/45 | LJ-630 | ||||
| LGJ-630/55 | |||||
| LGJ-630/80 | |||||