PF Power Fittings Technical Reference

FHJ Lightning Protection Fitting

Models: eight insulator models, two groups · Distances: D 260 or 320 mm, L 130–200 mm

Two Distances, Not a Size Range

This page does not list fittings. It lists insulators, and for each one it gives the two distances the lightning protection fitting has to be set to:

  • D — the main setting distance, printed 260 ± 10 mm in the first group and 320 ± 10 mm in the second.
  • L — the second distance, 130 to 200 mm depending on the insulator, with ± 10 or ± 20 mm tolerance.

There is no model number for the fitting itself anywhere on the sheet. It is ordered against an insulator, which is unusual in this catalogue and worth understanding before you ask for a price.

The Table Is Transposed

Read it sideways. The insulator models are the columns; D and L are the rows:

P15 P20 PS15/300 PS15/500
D 260 ± 10 260 ± 10 260 ± 10 260 ± 10
L 130 ± 10 160 ± 10 160 ± 10 160 ± 10
PS-150/12.5Z PS-170/12.5ZS FPS170/12.5 FPQ4-20/12.5
D 320 ± 10 320 ± 10 320 ± 10 320 ± 10
L 180 ± 20 200 ± 20 200 ± 20 180 ± 20

D is constant within a group. The whole 15–20 kV pin insulator family takes 260 mm; the 150–170 kN creepage class takes 320 mm. So D is set by the insulator family, not by the individual model, and there is nothing to calculate.

L is where the models differ — 130 or 160 in the first group, 180 or 200 in the second. L is the dimension you set on site, and it is the only cell that changes.

The Tolerances Are the Real Specification

± 10 mm on D and ± 20 mm on L is not a manufacturing tolerance. It is the installation setting tolerance for an air gap: too small and the fitting does not protect, too large and the arc strikes elsewhere.

That makes this page a commissioning document as much as a catalogue page. If you are buying the fitting for a retrofit, the insulator model on the pole decides which group you are in, and getting that wrong puts a 320 mm fitting on a 260 mm insulator.

Why There Is No Model Number

Because the fitting is a pair of horns or a rod set shaped to the insulator’s cap and pin. The same forging serves a range of insulators by being bent and set to D and L. The catalogue therefore specifies it by the insulator it serves.

When you enquire, send the insulator model. “FHJ for PS15/300” is a complete specification; “FHJ” alone is not.

Technical Parameters

15 to 20 kV pin insulators

Insulator ModelP15P20PS15/300PS15/500
Corresponding Distance D (mm)260±10260±10260±10260±10
Corresponding Distance L (mm)130±10160±10160±10160±10

150 and 170 kN class

Insulator ModelPS-150/12.5ZPS-170/12.5ZSFPS170/12.5FPQ4-20/12.5
Corresponding Distance D (mm)320±10320±10320±10320±10
Corresponding Distance L (mm)180±20200±20200±20180±20

The arcing horn itself: ZH arcing horn. The wider lightning protection range: Lightning protection fittings. Corona and grading hardware for the same terminals: Shielding ring 330 kV, FJ grading ring.

Note: the table is transposed — insulators across, distances down. D is fixed by the insulator family (260 or 320 mm); only L varies, 130 to 200 mm. No fitting model number is printed: order against the insulator model, and treat the ±10 and ±20 mm as installation tolerances.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: