PF Power Fittings Technical Reference

Shielding Ring 330kV

Models: JP-330-N – P-330XL · Rows: 10 in 5 tables · Reference Weight: 2.1–10.6 kg

Five Tables, Four Column Sets

There are ten rings on this page in five separate tables, and no two tables use the same columns:

Table Columns Rings
1 L1 L2 H1 H2 a C D φ JP-330-N, J-330N, JP-330-NL
2 L B H a C D φ FJP-330XS, FJP-330XD
3 L L1 L2 H1 H2 C D Ø JP-330-X, FJP-330-NB, JP-330-XL800
4 L L1 L2 H C D Ø PV-330
5 L B H a C D φ P-330X, P-330XL

L is not the same measurement in all five. In tables 2 and 5 it is the ring’s overall length paired with B; in tables 1, 3 and 4 it is a plate length, with the ring itself described by L1 and L2 and its height by H1 and H2.

So a “800” in table 3 and a “800” in table 5 are not the same 800 mm. Read the header of the table you are in, every time — this is the same trap as on the LT and EB clevis page.

Two columns are common to all five and do mean the same thing: C (the ring tube) and D (the mounting stem). φ / Ø is the fixing hole.

Aluminium Is Half the Weight, Every Time

Three pairs on this page differ only in material, and the ratio is consistent:

Steel Aluminium Ratio
Table 1 JP-330-N · 5.2 kg JP-330-NL · 2.5 kg 2.08
Table 5 P-330X · 5.48 kg P-330XL · 2.70 kg 2.03
Table 3 JP-330-X · 4.2 kg JP-330-XL800 · 2.1 kg 2.00

Steel is 2.9 times the density of aluminium, but a ring is tube, so a like-for-like swap lands near 2:1 once the wall is adjusted. Two point zero is the aluminium signature on this page.

Which is why the third row is a problem. JP-330-XL800 is marked Steel in the material column and weighs exactly half of the JP-330-X above it, on identical dimensions — L 800, L1 270, L2 350, H1 220, H2 145, C 18, D 32, Ø 18.

XL is the suffix this page uses for aluminium and the weight sits exactly on the aluminium ratio: JP-330-XL800 is an aluminium ring. If your specification forbids aluminium hardware, take the steel ring in the same size instead — and where the material is contractual, ask for the certificate with the delivery.

The Two Heavy Ones

FJP-330XS at 10.6 kg and FJP-330XD at 9.6 kg are twice the weight of anything else here, on a 900 × 600 and a 700 × 600 envelope.

They are not just heavier rings: at 900 mm and 700 mm they sit between the 330 kV terminals and the larger JPL rings, and they are the only two rows on the page with a C of 22 and 20 against the 32 mm stem that is common to all five tables. Treat them as a different assembly — a shielding ring with its own bracket rather than a loop on a stem.

Technical Parameters

JP-330-N, J-330N and JP-330-NL

ModelMain Dimensions(mm)Reference Weight(kg)Material
L1L2H1H2aCDφ
JP-330-N652352392120802432185.2Steel
J-330N702320176136802432185.0Steel
JP-330-NL650270392120802432182.5Aluminum

FJP-330XS and FJP-330XD

ModelMain Dimensions(mm)Reference Weight(kg)Material
LBHaCDφ
FJP-330XS90060023112022321410.6Steel
FJP-330XD700600275802032189.6Steel

JP-330-X, FJP-330-NB and JP-330-XL800

ModelMain Dimensions(mm)Reference Weight(kg)Material
LL1L2H1H2CD Ø
JP-330-X8002703502201451832184.2Steel
FJP-330-NB8003203803921502632184.8Steel
JP-330-XL8008002703502201451832182.1Steel

PV-330

ModelMain Dimensions(mm)Reference Weight(kg)Material
LL1L2HCD Ø
PV-3308153003901302232184.8Steel

P-330X and P-330XL

ModelMain Dimensions(mm)Reference Weight(kg)Material
LBHaCDφ
P-330X8007002803801832185.48Steel
P-330XL8007002803801832182.70Aluminum

The general grading and shielding rings: JPL FJP grading shielding ring, FJ, FJV, FP shielding ring. Arcing protection for the same terminals: ZH arcing horn, FHJ lightning protection fitting.

Note: five tables, four column sets — L means the plate length in three of them and the ring length in two. Aluminium versions weigh about half the steel version, which is why JP-330-XL800 at 2.1 kg cannot be the steel part its material column claims. FJP-330XS and XD are a different assembly, not a size step.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: