MRJ-K/N Twin Spacer Damper

Models: 15 sizes · Reference Weight: 0.7–3.5 kg · Body: aluminium alloy, damping pad synthetic rubber
For Expanded and Heat-Resistant Conductor
This is the heavy-conductor sister of the MRJ-4/6 range. It takes the conductors the lighter family does not: LGKK-600, LGKK-900, LGKK-1400, LGJQT-1400 and NAHLGJQ.
Two suffixes, and they mean different things:
- K — expanded hollow-core conductor, LGKK series
- N — heat-resistant, NAHLGJQ
MRJ-1400/400 has no letter because LGJQT-1400 is neither — it is the large-section hollow conductor. Read the conductor column, not just the letter.
The 120 mm Rows Are Not Damped
The weight tells you plainly:
| Spacing | Weight |
|---|---|
| 120 mm | 0.7 kg |
| 200 mm | 2.2 kg |
| 400 mm | 2.5 kg |
| 450 mm | 3.3 kg |
0.7 kg at 120 mm and 2.2 kg at 200 mm is a three-fold jump for 80 mm of extra spacing. That is not a longer tie bar — it is a different fitting. The 120 mm version is a rigid spacer; from 200 mm up you are buying the damping element.
That matters on procurement: a specification calling for “MRJ-600K, 120 mm spacing” and one calling for “MRJ-600K, 200 mm” are asking for two different products at three times the weight difference, and only one of them damps.

A/B Track the Spacing, Not the Conductor
The two frame dimensions behave unusually here:
- L = 200 / 400 / 450 → A = 60, B = 70 on the 600K and 1400 rows
- L = 120 → A = 50, B = 68
- LGKK-900 → A = 50, B = 68 (or 65 at 120 mm) on every spacing
So on four of the five conductors the frame grows when the spacing exceeds 120 mm, while LGKK-900 keeps the small frame throughout. If you are matching a frame to an existing installation, A and B are on the row — do not assume they follow the conductor.
R is 26 mm on everything except MRJ-1400K/400 at 29 mm, which is the only row with the larger LGKK-1400 conductor.
A Bore Figure to Check
Our TL equal diameter clamp, TLS range and SJ twin spacer all put LGKK-900 at a 50 mm groove — R = 25 mm. This table gives every MRJ row R = 26 mm, which is the LGKK-600 groove (51 mm conductor, 52 mm groove).
The difference is 1 mm and on a spacer with a rubber pad it will still seat. But if you are matching a spacer groove to a specific conductor, tell us which LGKK you have rather than relying on R alone.
Technical Parameters
| Model | Applicable Conductor Diameter (mm) | Main Dimensions (mm) | Reference Weight (kg) | |||
|---|---|---|---|---|---|---|
| A | B | L | R | |||
| MRJ-600K/120 | LGKK-600 | 50 | 68 | 120 | 26 | 0.7 |
| MRJ-600K/200 | LGKK-600 | 60 | 70 | 200 | 26 | 2.2 |
| MRJ-600K/400 | LGKK-600 | 60 | 70 | 400 | 26 | 2.5 |
| MRJ-600K/450 | LGKK-600 | 60 | 70 | 450 | 26 | 3.3 |
| MRJ-900K/120 | LGKK-900 | 50 | 65 | 120 | 26 | 0.7 |
| MRJ-900K/200 | LGKK-900 | 50 | 68 | 200 | 26 | 2.2 |
| MRJ-900K/400 | LGKK-900 | 50 | 68 | 400 | 26 | 2.5 |
| MRJ-900K/450 | LGKK-900 | 50 | 68 | 450 | 26 | 3.3 |
| MRJ-1400K/400 | LGKK-1400 | 70 | 83 | 400 | 29 | 3.5 |
| MRJ-1400/120 | LGJQT-1400 | 50 | 68 | 120 | 26 | 0.7 |
| MRJ-1400/200 | LGJQT-1400 | 50 | 68 | 200 | 26 | 2.2 |
| MRJ-1400/400 | LGJQT-1400 | 60 | 70 | 400 | 26 | 2.5 |
| MRJ-1400/450 | LGJQT-1400 | 60 | 70 | 450 | 26 | 3.3 |
| MRJ-1440N/200 | NAHLGJQ-1400 | 60 | 70 | 200 | 26 | 2.2 |
| MRJ-1440N/400 | NAHLGJQ-1400 | 60 | 70 | 400 | 26 | 2.5 |
Note on the heading. The conductor column is labelled “diameter (mm)” but the values are conductor designations (LGKK-600, LGJQT-1400). Read them as names, not numbers.
Related Clamps
Lighter conductors 19–33 mm: MRJ twin spacer damper. Three-conductor bundles: MRJ3 triple spacer damper. Rigid spacing on the same conductors: SJ twin spacer.
Note: Two model-designation errors on this table are printed as source — see the flag on MRJ-1440N below.
MRJ-1440N/200 and MRJ-1440N/400 are listed against NAHLGJQ-1400, while the three-conductor version on our MRJ3 page lists the same 1440N against NAHLGJQ-1440. The 1400 figure looks carried across from the LGJQT row above it. Confirm before ordering.