PF Power Fittings Technical Reference

MRJ-K/N Twin Spacer Damper

MRJ-K/N twin spacer damper

Models: 15 sizes · Reference Weight: 0.7–3.5 kg · Body: aluminium alloy, damping pad synthetic rubber

For Expanded and Heat-Resistant Conductor

This is the heavy-conductor sister of the MRJ-4/6 range. It takes the conductors the lighter family does not: LGKK-600, LGKK-900, LGKK-1400, LGJQT-1400 and NAHLGJQ.

Two suffixes, and they mean different things:

  • K — expanded hollow-core conductor, LGKK series
  • N — heat-resistant, NAHLGJQ

MRJ-1400/400 has no letter because LGJQT-1400 is neither — it is the large-section hollow conductor. Read the conductor column, not just the letter.

The 120 mm Rows Are Not Damped

The weight tells you plainly:

Spacing Weight
120 mm 0.7 kg
200 mm 2.2 kg
400 mm 2.5 kg
450 mm 3.3 kg

0.7 kg at 120 mm and 2.2 kg at 200 mm is a three-fold jump for 80 mm of extra spacing. That is not a longer tie bar — it is a different fitting. The 120 mm version is a rigid spacer; from 200 mm up you are buying the damping element.

That matters on procurement: a specification calling for “MRJ-600K, 120 mm spacing” and one calling for “MRJ-600K, 200 mm” are asking for two different products at three times the weight difference, and only one of them damps.

MRJ-K/N twin spacer damper, damper element

A/B Track the Spacing, Not the Conductor

The two frame dimensions behave unusually here:

  • L = 200 / 400 / 450 → A = 60, B = 70 on the 600K and 1400 rows
  • L = 120 → A = 50, B = 68
  • LGKK-900 → A = 50, B = 68 (or 65 at 120 mm) on every spacing

So on four of the five conductors the frame grows when the spacing exceeds 120 mm, while LGKK-900 keeps the small frame throughout. If you are matching a frame to an existing installation, A and B are on the row — do not assume they follow the conductor.

R is 26 mm on everything except MRJ-1400K/400 at 29 mm, which is the only row with the larger LGKK-1400 conductor.

A Bore Figure to Check

Our TL equal diameter clamp, TLS range and SJ twin spacer all put LGKK-900 at a 50 mm groove — R = 25 mm. This table gives every MRJ row R = 26 mm, which is the LGKK-600 groove (51 mm conductor, 52 mm groove).

The difference is 1 mm and on a spacer with a rubber pad it will still seat. But if you are matching a spacer groove to a specific conductor, tell us which LGKK you have rather than relying on R alone.

Technical Parameters

ModelApplicable Conductor Diameter (mm)Main Dimensions (mm)Reference Weight (kg)
ABLR
MRJ-600K/120LGKK-6005068120260.7
MRJ-600K/200LGKK-6006070200262.2
MRJ-600K/400LGKK-6006070400262.5
MRJ-600K/450LGKK-6006070450263.3
MRJ-900K/120LGKK-9005065120260.7
MRJ-900K/200LGKK-9005068200262.2
MRJ-900K/400LGKK-9005068400262.5
MRJ-900K/450LGKK-9005068450263.3
MRJ-1400K/400LGKK-14007083400293.5
MRJ-1400/120LGJQT-14005068120260.7
MRJ-1400/200LGJQT-14005068200262.2
MRJ-1400/400LGJQT-14006070400262.5
MRJ-1400/450LGJQT-14006070450263.3
MRJ-1440N/200NAHLGJQ-14006070200262.2
MRJ-1440N/400NAHLGJQ-14006070400262.5

Note on the heading. The conductor column is labelled “diameter (mm)” but the values are conductor designations (LGKK-600, LGJQT-1400). Read them as names, not numbers.

Lighter conductors 19–33 mm: MRJ twin spacer damper. Three-conductor bundles: MRJ3 triple spacer damper. Rigid spacing on the same conductors: SJ twin spacer.

Note: Two model-designation errors on this table are printed as source — see the flag on MRJ-1440N below.

MRJ-1440N/200 and MRJ-1440N/400 are listed against NAHLGJQ-1400, while the three-conductor version on our MRJ3 page lists the same 1440N against NAHLGJQ-1440. The 1400 figure looks carried across from the LGJQT row above it. Confirm before ordering.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: