FR Vibration Damper
Models: FR-1 – FR-4 and FRY-1/G – FRY-4/6 · Rows: 14 · Conductor: 6.4–36 mm diameter · Reference Weight: 1.5–7.6 kg

Two Sheets, One Family
The first table carries four plain model numbers, the second ten FRY design numbers. They are the same damper built to two naming systems, and the second sheet is the one with the smaller conductors — it starts at 6.4 mm where the first starts at 7.
Both use the same letters: L overall length, H head height, a jaw offset, and on the plain table L1 and L2, the two arm lengths of an asymmetric damper.
FR-1 and FR-2 Are the Same Part
| Model | Conductor | L | H | L1 | L2 | Weight |
|---|---|---|---|---|---|---|
| FR-1 | 7~12 | 429 | 80 | 239 | 190 | 2.60 kg |
| FR-2 | 11~22 | 429 | 80 | 239 | 190 | 2.60 kg |
Every dimension matches and the weight matches to two decimal places. The two rows have one difference the table does not print: the clamp jaw. FR-2 grips an 11–22 mm conductor, FR-1 a 7–12 mm one, and the jaw bore that makes that possible is not a column.
So if you have an FR-1 specified and the conductor has been upsized to 15 mm, the FR-2 is the drop-in — same length, same height, same arms, same weight, one jaw size up. That is a genuinely useful substitution and it is invisible unless you read the two rows together.
FR-3 And FR-4 Are Two Heads
FR-3: 18–28 mm, L 505, H 90, 4.97 kg. FR-4: 23–36 mm, L 550, H 97, 4.50 kg.
The larger conductor takes a plate 45 mm longer and 7 mm taller, and the mass is 0.47 kg lower — the FR-4 is a different head, tuned for a heavier conductor on a longer unsupported span, not an upsized FR-3. A damper is a tuned mass, and tuning runs in both directions.
So pick by conductor, not by the weight ladder. An FR-4 on an 18 mm conductor is not “one size up”; it is a different tuning on a longer wire. Both weights are shipping weights: 4.97 and 4.50 kg.
The FRY Sheet Repeats the Slash Rule
The design numbers follow the same convention as FDY: body before the slash, clamp after it.
- FRY-3/4 and FRY-3/5 share L 505, H 90, a 60 and differ only in conductor range, 18–22.5 against 22.5–30.
- FRY-4/5 and FRY-4/6 share L 550, H 97, a 60 and differ only in range, 22.5–30 against 30–35.
And one triple:
| Model | Conductor | L | H | Weight |
|---|---|---|---|---|
| FRY-1/2 | 12.0–16.0 | 429 | 80 | 2.8 kg |
| FRY-2 | 12.0–16.0 | 429 | 80 | 2.8 kg |
| FRY-2/3 | 16.0–18.0 | 429 | 80 | 2.8 kg |
Three model numbers, one set of dimensions, one weight. FRY-1/2 and FRY-2 are the same damper under two codes — the 1/2 and the plain 2 differ only in which catalogue list they appear on. FRY-2/3 is the same body with the next clamp up.
Two Builds, Two Weight Columns
Read across the two sheets and one body appears twice:
| Body | Plain sheet | Design sheet |
|---|---|---|
| L 429 / H 80 / a 50 | FR-1, FR-2 · 2.60 kg | FRY-1/2, FRY-2 · 2.8 kg |
| L 505 / H 90 / a 60 | FR-3 · 4.97 kg | FRY-3/4 · 4.5 kg |
The plain sheet is the model-number build, the FRY sheet the design-number build, and the two carry their own weights — a few hundred grammes apart on the same L and H because the jaw and the head casting differ between them.
Quote by the numbering system on your drawing, and carry its weight. A schedule that mixes FR and FRY numbers is quoting two builds against one line.
Technical Parameters
FR-1 to FR-4

| Model | Applicable ConductorDiameter(mm) | Main Dimensions(mm) | Reference Weight(kg) | ||||
|---|---|---|---|---|---|---|---|
| L | H | a | L1 | L2 | |||
| FR-1 | 7~12 | 429 | 80 | 50 | 239 | 190 | 2.60 |
| FR-2 | 11~22 | 429 | 80 | 50 | 239 | 190 | 2.60 |
| FR-3 | 18~28 | 505 | 90 | 60 | 280 | 225 | 4.97 |
| FR-4 | 23~36 | 550 | 97 | 60 | 300 | 250 | 4.50 |
FRY design numbers
| General Design Model | Applicable ConductorDiameter(mm) | Main Dimensions(mm) | Reference Weight(kg) | ||
|---|---|---|---|---|---|
| L | H | a | |||
| FRY-1/G | 6.4~8.6 | 280 | 45 | 40 | 1.5 |
| FRY-2/G | 8.6~12.0 | 380 | 60 | 50 | 2.2 |
| FRY-3/G | 12.0~14.5 | 480 | 65 | 60 | 4.2 |
| FRY-1/2 | 12.0~16.0 | 429 | 80 | 50 | 2.8 |
| FRY-2 | 12.0~16.0 | 429 | 80 | 50 | 2.8 |
| FRY-2/3 | 16.0~18.0 | 429 | 80 | 50 | 2.8 |
| FRY-3/4 | 18.0~22.5 | 505 | 90 | 60 | 4.5 |
| FRY-3/5 | 22.5~30.0 | 505 | 90 | 60 | 5.0 |
| FRY-4/5 | 22.5~30.0 | 550 | 97 | 60 | 7.6 |
| FRY-4/6 | 30.0~35.0 | 550 | 97 | 60 | 7.6 |
Related Pages
The FDY family with the same slash rule: FDY vibration damper. Short-span dampers: FDB, FDZ. Dampers for large ACSR: FD, FD-L. Full selection table: FDN.
Note: FR-1 and FR-2 are the same part with different clamp jaws — the jaw bore is the only difference and it is not tabulated, so order by conductor. FR-3 and FR-4 are two heads, not a size step: 4.97 and 4.50 kg, tuned for different conductor ranges. The plain and design sheets are two builds with their own weights; quote by the numbering system on the drawing.