PF Power Fittings Technical Reference

DTLB Copper-Aluminum Terminal (Explosion Welding)

DTLB explosion welded copper-aluminium terminal

Models: DTLB-16 – DTLB-500 (13 sizes)

DTLB is the explosion-welded member of the DTL family. Same job as any bimetal terminal — an aluminium cable landing on a copper or brass equipment terminal — but the transition is made by a different process, and that changes what the part is good for.

Part of the DTL copper-aluminium terminal family.

How the joint is made, and why it matters here

In explosion welding a controlled charge drives the copper and the aluminium together at an angle and at very high velocity. The impact strips the oxide film off both surfaces and ejects it as a jet, and the two metals bond directly in the solid state. No filler metal, no melting of the parent metals, no heat-affected zone to speak of.

Two consequences follow, and both are the reason to specify DTLB:

  • The joint is not limited by a weld pool. Friction welding and brazing both put heat into the section; explosion welding does not, so the palm and the transition can be heavy without the process running out of energy. That is why the DTLB palm is dimensioned by W alone — the catalogue does not fix a palm thickness S, because the palm is a plate and its thickness follows the drawing rather than a standard figure.
  • The bond is over the whole interface. There is no narrow fused band to carry the current; the load is spread across the joint face. On a joint that has to take short-circuit forces as well as normal current, that is worth paying for.

Where it is not the right choice: on small conductors there is nothing to gain. Below 50 mm² the standard DTL does the job with a lighter, cheaper palm, and DTLB starts at 16 mm² only because the range is kept complete.

What the dimensions tell you

  • Ø (mm) — palm hole as catalogued, Ø 8.5 to 21.0. Custom drilling applies as on every DTL: it is the palm hole that gets changed, not the bore.
  • D (mm) — outside diameter over the transition, and the figure that selects the die. It runs 10 to 42 mm across the range.
  • d (mm) — barrel bore. DTLB runs a slightly larger bore than the standard DTL size for size — 21.0 mm against 20.0 at 240 mm², 9.7 against 9.5 at 50 mm². Small, but it matters if you are choosing between the two on a cable that is already close to the limit of the bore.
  • L (mm) — overall length, 70 to 190 mm.
  • W (mm) — palm width. It takes a jump at DTLB-300, from 40 to 50 mm, and stays there through 400 and 500.

No S column. If palm thickness is a contractual figure, ask for the drawing rather than inferring it from D and d.

Palm hole and palm form

The same rule as everywhere in this family: the hole is made to order, the bore is not.

  • Hole diameter follows the stud: Ø 8.5 for M8, 10.5 for M10, 12.5 for M12, 14.5 for M14, 16.5 for M16, 21.0 for M20.
  • On the largest sizes — DTLB-300, 400 and 500 — the palm is wide enough that a two-hole or four-hole pad is a normal request rather than a special.
  • The limit is the metal left either side of the hole: at least half the hole diameter, or the palm deforms under bolt preload and the joint goes loose.

Because the palm is a plate rather than a forging, a change of palm width or hole pattern on DTLB is a cutting change rather than a die change — shorter lead time than the same request on a cast or forged palm. Ask for a drawing-based quote if your pad is non-standard.

Standards and testing

The terminal falls under GB/T 14315-2008 with test methods from GB/T 9327-2008 (international counterpart IEC 61238-1): resistance ratio against an equal length of conductor, temperature rise, resistance after thermal cycling, and mechanical pull-out.

On an explosion-welded joint the thermal-cycling resistance test is the one to watch. A joint with incomplete bonding at the edges of the interface passes a cold measurement and grows resistance as the interface opens under cycling. If you are qualifying a supplier, ask for the cycling curve rather than a single resistance figure.

Installation

  1. Strip to the barrel depth — insulation finishing at the barrel mouth.
  2. Brush the aluminium conductor and the bore, and apply contact paste to the aluminium side.
  3. Insert fully.
  4. Crimp with the die that matches D, from the transition end toward the mouth, one crimp per 15–20 mm of barrel, overlapping by a third. The heavy palm does not change the crimping: the barrel is still an aluminium tube.
  5. Check hexagonal closure with the die faces meeting.
  6. Seal the mouth on outdoor and buried joints.

Where these joints fail

  • Using a DTL die on a DTLB. D differs at several sizes, and a die that is close but not matching gives an oval crimp with poor contact.
  • Assuming the palm thickness. S is not catalogued; a palm thinner than the bolt load requires crushes and the joint loosens.
  • No oxide removal on the aluminium side. The crimp looks right and measures badly.
  • No seal outdoors. Water wicks into the barrel and the conductor corrodes from inside — the weld is fine, the cable end is not.

FAQ

DTLB or DTL? DTLB where the palm carries heavy mechanical or short-circuit load, or where the palm pattern is non-standard and you want it cut rather than formed. DTL everywhere else — it is lighter and cheaper for the same conductor.

Is the explosion weld visible? The interface shows as a wavy line at the transition. A straight, flat interface with voids is a process fault, not a cosmetic one.

Can the palm be drilled to my stud? Yes — that is the normal order. Give the stud size, hole count and spacing.

Does DTLB come in a two-hole palm? Two holes on the DTLB palm are quoted as a cutting pattern. The catalogued two-hole series is DTL-S.

Technical Parameters

DTLB terminal drawing

Model Main Dimensions (mm)
Ø D d L W
DTLB-168.5105.57016
DTLB-258.5127.07518
DTLB-3510.5148.58520
DTLB-5010.5169.79023
DTLB-7012.51811.510226
DTLB-9512.52113.511228
DTLB-12014.52315.012030
DTLB-15014.52516.512634
DTLB-18516.52718.513337
DTLB-24016.53021.014040
DTLB-30021.03423.016550
DTLB-40021.03426.517050
DTLB-50021.04229.519060

Note: The palm is a plate, so its thickness S is not a catalogue column — take it from the drawing. Hole diameter, hole count and palm width are made to order; the bore is not. Dimensions may vary slightly with manufacturing tolerance.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: