PF Power Fittings Technical Reference

DTL-S Two-Hole Copper-Aluminum Terminal

DTL-S two-hole copper-aluminium terminal

Models: DTL-16S – DTL-500S (13 sizes)

DTL-S is the two-hole palm version of the bimetal terminal: an aluminium barrel welded to a copper palm that is bolted down at two points instead of one. The electrical job is the same as any DTL; the reason to specify it is mechanical.

Part of the DTL copper-aluminium terminal family.

Why two holes, not one

A single-hole palm has one bolt holding it, and that bolt has to do two jobs at once: carry the contact pressure and stop the palm rotating. On a busbar pad, a breaker terminal or a disconnector, vibration and thermal cycling work at that single bolt, and the palm creeps round.

A two-hole palm separates the two jobs. The pair of bolts locks the angle, so the palm cannot rotate and the contact faces cannot rock, and the clamping load is shared over twice the area. That is why the two-hole pattern is the default on switchgear and busbar work even where a single-hole lug would physically fit.

The practical cost is that L3 — the distance between the two hole centres — is fixed by the catalogue. If your equipment pad is drilled to a different spacing, the palm has to be changed, not just re-drilled. Send the pad drawing.

Reading the palm dimensions

  • L1 (mm) — barrel length.
  • L2 (mm) — palm length. This is the figure that decides whether the palm reaches across your pad.
  • L3 (mm) — centre-to-centre spacing of the two holes. It steps in fixed increments across the range: 20 mm up to 50 mm², 25 at 70–95, 30 at 120–150, 35 at 185–240, 40 at 300–400, 45 at 500. So a 120 mm² palm will not bolt onto a pad drilled at 20 mm centres, whatever the stud size.
  • W (mm) — palm width, 18 to 60 mm.
  • S (mm) — palm thickness, 3.0 to 9.5 mm. It has to survive the bolt preload without crushing; the jump from 3.0 to 9.5 across the range is not cosmetic.
  • Ø (mm) — hole diameter, Ø 8.4 to 21.0. Drilled to your stud as on every DTL.
  • D (mm) — outside diameter over the transition. Selects the die.
  • d (mm) — bore. Set by the conductor, not a custom dimension.
  • L (mm) — overall length.

Note that L1 and L2 are measured to the shoulder between barrel and palm, so L is not simply L1 + L2 — there is a transition zone between them.

What can and cannot be changed

Made to order: hole diameter, hole count (a third or fourth hole on the larger palms), palm length, the angle of the palm to the barrel, and a rotated hole pair — two holes in line with the barrel becomes two holes across it.

Not negotiable: the bore d, and the wall that surrounds it. Opening the bore to clear a bigger stud destroys the crimp.

The limit around the hole is the same rule as everywhere in this family — at least half the hole diameter of metal between hole and palm edge. At DTL-16S that is (18 − 8.4) / 2 = 4.8 mm each side, which is already snug; at DTL-500S it is (60 − 21) / 2 = 19.5 mm and there is room to work.

Two levels of change, two lead times: a different hole diameter is a drilling change on the same palm — short lead time. A different L3, a different palm length or a third hole means a new forming die and a minimum quantity.

Send with the enquiry: the pad drawing (hole spacing matters more than anything else), stud size, palm orientation, quantity.

Standards and testing

GB/T 14315-2008 for the terminal, GB/T 9327-2008 / IEC 61238-1 for the test methods: resistance ratio against an equal length of conductor, temperature rise, resistance after thermal cycling, mechanical pull-out.

The two-hole palm does not change any of these limits — it changes the mechanical behaviour of the joint under load, which the pull-out and thermal-cycling tests do not fully capture. Torque both bolts; that part is on the installer.

Installation

  1. Strip to the barrel depth, insulation finishing at the barrel mouth.
  2. Clean the conductor and bore; contact paste on the aluminium side.
  3. Insert fully, then crimp with the die matching D, from the transition end toward the mouth.
  4. Bolt both holes, and torque in two passes — snug one, snug the other, then torque both. One bolt in a two-hole palm is worse than a single-hole palm: the free end lifts, the contact area halves and the palm can still rotate about the one bolt.
  5. Re-torque after the first thermal cycle on aluminium conductors. Aluminium creeps under preload; copper does not to the same degree.
  6. Seal the barrel mouth outdoors and in buried joints.

Where these joints fail

  • One bolt used in a two-hole palm. Rotation, a lifted free end, and half the contact area.
  • Hole spacing matched to nothing. The palm is bolted down strained, and the second bolt never seats.
  • Bore matched to the nominal mm² rather than the conductor diameter — flexible cable is fatter and the crimp collapses the outer strands.
  • No seal outdoors. Water wicks down the strands into the barrel.

FAQ

Can I get a two-hole palm below 16 mm²? Not in the catalogue — DTL-S starts at 16 mm². On small conductors a single-hole palm with a spring or star washer is the usual answer.

What is the hole spacing on DTL-240S? 35 mm centre to centre, with 16.5 mm holes. If your pad is drilled at 44 or 50 mm, the palm has to change.

Can the second hole be at 90° to the first? Yes, as a palm change rather than a drilling change — die cost and a minimum quantity.

Is this the same body as the single-hole DTL? Same conductor sizes, same bore, but the palm is longer and the hole pattern different. The die is selected by D, which is the same for both.

Technical Parameters

DTL-S terminal drawing DTL-S terminal dimensions

Model Main Dimensions (mm)
Ø D d L L1 L2 L3 W S
DTL-16S8.4105.590324520183.0
DTL-25S8.4127.093.5384420183.2
DTL-35S10.5148.51044248.520203.6
DTL-50S10.5169.5112465020234.0
DTL-70S12.51812.0125475925264.5
DTL-95S12.52113.0136536025284.8
DTL-120S14.52315.0145556930305.5
DTL-150S14.52516.0150557430346.0
DTL-185S14.52718.0162627635376.5
DTL-240S14.53020.0170658235407.0
DTL-300S16.53423.0190728740458.5
DTL-400S16.53826.0195758740508.5
DTL-500S21.04229.02258011045609.5

Note: L3 is fixed per size and is the dimension that decides whether the palm fits your pad. Hole diameter and palm length are made to order; the bore is not. Dimensions may vary slightly with manufacturing tolerance.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: