DTLZ Copper-Aluminium Blade Terminal
Models: DTLZ-10 – DTLZ-50 (5 sizes)

DTLZ is the end of the family where the bolt disappears. There is no palm hole at all: the copper end is a solid blade, 5 mm thick and 17 mm wide, that slides under the breaker’s own terminal screw and is held by that clamp. The barrel behind it is aluminium, welded on, for an aluminium cable.
That makes it the fitting for the breakers that have no pad to bolt to — miniature and compact moulded-case frames, meter cabinets, distribution boards — where the terminal is a screw pressing down on whatever you push under it. Same bimetal direction as DTLC: aluminium barrel, copper blade. Not the reverse.
The blade is the whole design
- 5 mm thick, 17 mm wide. That is the biggest blade most of these clamps will take; the screw has to land on flat metal, not on an edge.
- No hole. Nothing is bolted. If your breaker has a drilled pad, this is the wrong part — use DTC or DTLC.
- L2, 17 or 19 mm — the blade dimension that grows on the 50 mm² size. The clamp opening is what L2 has to fit, so measure it rather than assuming.
- The blade is copper and it is the part that carries current into the breaker. Copper because the clamp and the conductor behind it are copper or tinned, as these terminals usually are — a bare aluminium blade under a screw is a galvanic joint in the one place you cannot inspect.
The barrel behind it is short: L1 is 20 mm on every size, the same as the smallest DTC, and L is 45 mm across the 10 to 35 mm² sizes. That is deliberate — this is a terminal for a tight enclosure, and the cable sits close to the breaker.
Five sizes, and why it stops at 50 mm²
The range ends at 50 mm², while DTC and DTLC run to 95. That is not a catalogue gap: in practice, above about 50 mm² the conductor is more than a terminal screw and a flat blade should be asked to carry, and the breaker frames at that size are built with a bolted pad instead. If you are being asked for a 70 or 95 mm² blade terminal, the question to ask is what the breaker terminal actually is — the answer is usually a pad, and then it is a DTC or DTLC job.
At the bottom of the range the limit is the other way round: a 10 mm² aluminium conductor in a 5 mm bore, with a 17 mm blade, is about as much metal as the small frames will take.
Reading the table
- d (mm) — bore, 5 to 9.5, sized for the aluminium conductor.
- D (mm) — outside diameter over the aluminium barrel, 10 to 14. This picks the die.
- L1 (mm) — barrel length, 20 mm on all five; it does not grow with the size.
- L (mm) — overall length, 45 mm, and 49 mm on the 50 mm².
- L2 (mm) — blade dimension, 17 mm, and 19 mm on the 50 mm².
- Blade thickness 5 mm, width 17 mm — fixed, dimensioned on the drawing.
Because L1 is fixed, the crimp schedule is the same on every size — one die position, one strip length — and only the die and the blade change. On a board where several circuits are being terminated that saves real time.
Working with the aluminium end
Everything that applies to an aluminium barrel applies here, and the blade does not change any of it:
- Brush the conductor and the bore immediately before crimping, and apply contact paste.
- Crimp to full die closure. Aluminium needs more deformation than copper to break the oxide and fill the barrel.
- Do not heat the shoulder. The weld between the blade and the aluminium barrel is the joint you are buying.
- Re-torque the terminal screw after the first thermal cycle. Aluminium creeps under preload, and on a clamped blade the screw is the only thing holding it.
Installation
- Strip to L1 (20 mm), less 1 to 2 mm.
- Clean, brush, paste on the conductor and in the bore.
- Insert fully — the blade end is closed, an over-strip has nowhere to go.
- Crimp from the blade end outward, one hexagonal crimp, die faces closed.
- Slide the blade fully under the clamp, so the screw lands well back from the tip, then torque to the breaker manufacturer’s figure. A blade clamped by its last few millimetres will heat.
- Seal the barrel mouth outdoors and in humid enclosures.
Standards
Made to GB/T 14315-2008 — compression terminal lugs and ferrules for power cable conductors up to 35 kV. Test methods GB/T 9327-2008, international counterpart IEC 61238-1: DC resistance across the joint no higher than an equal length of conductor, temperature rise no higher than the conductor, resistance inside limits after thermal cycling.
Low-voltage parts: these go into breaker and distribution-board terminals, not onto medium-voltage equipment.
FAQ
DTLZ or DTLC? Look at the breaker, not the cable. A pad with a hole → DTLC, bolted with an M8. A screw clamp with nothing to bolt to → DTLZ. Both take an aluminium cable and both are copper at the breaker end.
Can I drill the blade and bolt it? It is not a designed modification. The blade is 5 mm copper with the clamp pressing on the middle of it; drilling puts a hole exactly where the load is, and takes out the section the screw needs. If you need a bolted palm, that is DTLC.
How wide can the blade be made? 17 mm is the standard, 19 mm on the 50 mm². It is not a free dimension: the blade has to fit the clamp opening, and a wider blade will not seat. Send the terminal opening if you are unsure.
Why is L1 only 20 mm? Because the fitting has to sit inside a small enclosure, and the crimp only needs to be long enough for the conductor size it takes. Aluminium needs more deformation, not always more length — at these sizes 20 mm of barrel is enough for a full hexagon crimp.
Is the blade copper or aluminium? Copper. The aluminium is the barrel, where the aluminium cable goes. The blade sits against the breaker’s own copper or tinned clamp.
Technical Parameters
| Model | Main Dimensions (mm) | ||||
|---|---|---|---|---|---|
| D | d | L | L1 | L2 | |
| DTLZ-10 | 10 | 5 | 45 | 20 | 17 |
| DTLZ-16 | 10 | 5.5 | 45 | 20 | 17 |
| DTLZ-25 | 11 | 7 | 45 | 20 | 17 |
| DTLZ-35 | 12 | 8.5 | 45 | 20 | 17 |
| DTLZ-50 | 14 | 9.5 | 49 | 20 | 19 |
Blade, all five sizes: 5 mm thick, 17 mm wide, no hole. L1 (barrel) is 20 mm throughout.
Note: Dimensions may vary slightly with manufacturing tolerance. The blade fits the breaker’s clamp opening, so check L2 and the 17 mm width against the terminal before ordering; the bore d is set by the conductor and cannot be adjusted afterwards.