JCS Terminal Clamp
Conductors: JKLYJ, LJ/TJ, JKLGYJ, LGJ · Bodies: 6 size classes, grooves 1–7

JCS connects a busbar down-lead to the outgoing terminal of electrical equipment — circuit breakers, current and voltage transformers, disconnectors, wall bushings. The body is a C-shape: the conductor sits in the groove, a keeper closes over it, and two bolts pull the whole body onto the equipment pad.
The catalogue offers it as a single-conductor outlet or a twin-conductor outlet, and the same body can be ordered with an insulating cover that clips over it.
Materials and features, from the factory sheet:
- Made of high-strength aluminium alloy, so there is no magnetic hysteresis loss at the joint.
- C-shaped body, for a splice the sheet describes as reliable.
- Takes many combinations of conductor, which is why the catalogue lists it as a matrix rather than a size list.
- Large contact area between clamp and conductor, so the splice resistance is low.
The standard body and the temperature-measuring body
There are two versions of the same clamp. The standard one is what you see above. The temperature-measuring version carries an over-temperature alarm element that operates when the joint runs hot, as a warning rather than a measurement.

That variant exists because a terminal clamp is the joint that fails quietly: it is bolted, not compressed, and a joint that has lost preload cooks itself without changing shape. If you are specifying for a station where the down-leads are hard to reach for thermographic survey, this is the version to quote.
How to read these tables
This is the part that catches people out. The tables are not a size list — they are a pair lookup.
Each table runs one conductor family across the top and the same family down the side, and the cell where the two meet is the clamp code:
- Find the conductor on the equipment side down the left.
- Find the conductor on the busbar side across the top.
- Read the code in the cell.
Two things follow from the way they are drawn:
- Only the upper half is filled. The lower half is dashes, because the clamp is symmetrical — the code for A on B is the same as B on A. A dash does not mean “not available”, it means “look at the mirror cell”.
- Several different pairs share one code. That is the design, not a slip: one groove covers a band of conductor diameters, so a clamp is listed against every pair it will accept — for example
JCS-2-23serves both JKLYJ-50 on JKLYJ-95 and JKLYJ-70 on JKLYJ-70.
So do not construct the code from the two section areas. Look it up. The code format is JCS-<body class 1–6>-<groove number>, and the groove number is not an arithmetic function of the conductor size.
The code follows the outside diameter, not the nominal area
This is the single most useful thing on the page, and it is why there are four tables instead of one. Take the same nominal conductor, 35 mm², in all four families:
| Family | Outside diameter at 35 mm² | Code for 35 on 35 |
|---|---|---|
| JKLYJ, insulated aerial | 7.0 mm | JCS-1-11 |
| LJ / TJ, bare aluminium or copper | 7.5 mm | JCS-1-12 |
| JKLGYJ, insulated steel-cored | 7.75 mm | JCS-1-12 |
| LGJ, bare ACSR | 8.16 mm | JCS-1-13 |
Same 35 mm², four different outside diameters, three different clamps. The groove has to close on the conductor you actually have, and insulation plus stranding change the diameter without changing the area.
Which means: when a customer says “35 square”, ask for the conductor type. JKLYJ-35 will not sit in the clamp that fits LGJ-35/6, and vice versa.
JKLYJ, insulated aerial conductor
| Conductor A | Conductor B | |||||||
|---|---|---|---|---|---|---|---|---|
| JKLYJ-35 | JKLYJ-50 | JKLYJ-70 | JKLYJ-95 | JKLYJ-120 | JKLYJ-150 | JKLYJ-185 | JKLYJ-240 | |
| Outside diameter (mm) | 7 | 8.4 | 10 | 11.6 | 13 | 14.6 | 16.2 | 18.4 |
| JKLYJ-35 | JCS-1-11 | JCS-1-12 | JCS-2-21 | JCS-2-22 | JCS-3-31 | JCS-4-41 | JCS-5-51 | JCS-6-61 |
| JKLYJ-50 | — | JCS-1-13 | JCS-2-22 | JCS-2-23 | JCS-3-32 | JCS-4-41 | JCS-5-52 | JCS-6-61 |
| JKLYJ-70 | — | — | JCS-2-23 | JCS-2-24 | JCS-3-33 | JCS-4-42 | JCS-5-52 | JCS-6-62 |
| JKLYJ-95 | — | — | — | JCS-2-25 | JCS-3-33 | JCS-4-43 | JCS-5-53 | JCS-6-63 |
| JKLYJ-120 | — | — | — | — | JCS-3-34 | JCS-4-43 | JCS-5-54 | JCS-6-63 |
| JKLYJ-150 | — | — | — | — | — | JCS-4-44 | JCS-5-54 | JCS-6-64 |
| JKLYJ-185 | — | — | — | — | — | — | JCS-5-55 | JCS-6-64 |
| JKLYJ-240 | — | — | — | — | — | — | — | JCS-6-65 |
LJ and TJ, bare aluminium and bare copper
| Conductor A | Conductor B | |||||||
|---|---|---|---|---|---|---|---|---|
| LJ(TJ)-35 | LJ(TJ)-50 | LJ(TJ)-70 | LJ(TJ)-95 | LJ(TJ)-120 | LJ(TJ)-150 | LJ(TJ)-185 | LJ(TJ)-240 | |
| Outside diameter (mm) | 7.5 | 9 | 10.8 | 12.48 | 14.25 | 15.75 | 17.5 | 20 |
| LJ(TJ)-35 | JCS-1-12 | JCS-1-13 | JCS-2-22 | JCS-2-23 | JCS-3-32 | JCS-4-42 | JCS-5-52 | JCS-6-62 |
| LJ(TJ)-50 | — | JCS-1-14 | JCS-2-23 | JCS-2-24 | JCS-3-33 | JCS-4-42 | JCS-5-52 | JCS-6-62 |
| LJ(TJ)-70 | — | — | JCS-2-24 | JCS-2-22 | JCS-3-34 | JCS-4-43 | JCS-5-53 | JCS-6-63 |
| LJ(TJ)-95 | — | — | — | JCS-2-26 | JCS-3-34 | JCS-4-44 | JCS-5-54 | JCS-6-63 |
| LJ(TJ)-120 | — | — | — | — | JCS-3-35 | JCS-4-44 | JCS-5-54 | JCS-6-64 |
| LJ(TJ)-150 | — | — | — | — | — | JCS-4-45 | JCS-5-55 | JCS-6-64 |
| LJ(TJ)-185 | — | — | — | — | — | — | JCS-5-56 | JCS-6-65 |
| LJ(TJ)-240 | — | — | — | — | — | — | — | JCS-6-66 |
JKLGYJ, insulated steel-cored conductor
| Conductor A | Conductor B | |||||||
|---|---|---|---|---|---|---|---|---|
| JKLGYJ-35 | JKLGYJ-50 | JKLGYJ-70 | JKLGYJ-95 | JKLGYJ-120 | JKLGYJ-150 | JKLGYJ-185 | JKLGYJ-240 | |
| Outside diameter (mm) | 7.75 | 9.12 | 10.83 | 12.93 | 14.32 | 15.84 | 17.96 | 20.52 |
| JKLGYJ-35/6 | JCS-1-12 | JCS-1-13 | JCS-2-22 | JCS-2-23 | JCS-3-32 | JCS-4-42 | JCS-5-52 | JCS-6-62 |
| JKLGYJ-50/8 | — | JCS-1-14 | JCS-2-23 | JCS-2-24 | JCS-3-33 | JCS-4-42 | JCS-5-52 | JCS-6-62 |
| JKLGYJ-70/10 | — | — | JCS-2-24 | JCS-2-25 | JCS-3-34 | JCS-4-43 | JCS-5-53 | JCS-6-63 |
| JKLGYJ-95/15, 20 | — | — | — | JCS-2-27 | JCS-3-34 | JCS-4-44 | JCS-5-54 | JCS-6-64 |
| JKLGYJ-120/20, 25 | — | — | — | — | JCS-3-35 | JCS-4-44 | JCS-5-55 | JCS-6-64 |
| JKLGYJ-150/20, 25 | — | — | — | — | — | JCS-4-45 | JCS-5-56 | JCS-6-64 |
| JKLGYJ-185/25, 30 | — | — | — | — | — | — | JCS-5-57 | JCS-6-65 |
| JKLGYJ-240/30, 40 | — | — | — | — | — | — | — | JCS-6-66 |
LGJ, bare ACSR
| Conductor A | Conductor B | |||||||
|---|---|---|---|---|---|---|---|---|
| LGJ-35/6 | LGJ-50/8 | LGJ-70/10 | LGJ-95/15, 20 | LGJ-120/20, 25 | LGJ-150/25 | LGJ-185/25, 30 | LGJ-240/30, 40 | |
| Outside diameter (mm) | 8.16 | 9.6 | 11.4 | 13.61,13.87 | 15.07,15.74 | 16.67,17.1 | 18.9,18.88 | 21.6,21.66 |
| LGJ-35/6 | JCS-1-13 | JCS-1-14 | JCS-2-23 | JCS-2-24 | JCS-3-33 | JCS-4-42 | JCS-5-52 | JCS-6-62 |
| LGJ-50/8 | — | JCS-1-14 | JCS-2-23 | JCS-2-25 | JCS-3-33 | JCS-4-43 | JCS-5-53 | JCS-6-63 |
| LGJ-70/10 | — | — | JCS-2-25 | JCS-2-26 | JCS-3-34 | JCS-4-43 | JCS-5-54 | JCS-6-64 |
| LGJ-95/15, 20 | — | — | — | JCS-2-27 | JCS-3-35 | JCS-4-44 | JCS-5-55 | JCS-6-64 |
| LGJ-120/20, 25 | — | — | — | — | JCS-3-36 | JCS-4-45 | JCS-5-56 | JCS-6-65 |
| LGJ-150/20, 25 | — | — | — | — | — | JCS-4-45 | JCS-5-57 | JCS-6-65 |
| LGJ-185/25, 30 | — | — | — | — | — | — | JCS-5-57 | JCS-6-66 |
| LGJ-240/30, 40 | — | — | — | — | — | — | — | JCS-6-67 |
When one side is an LGJ-300 or an LGJ-400
These three tables are separate from the four above because the code numbering changes. Where one side is a 300 or a 400 conductor the clamp is designated JCS-01, JCS-02, JCS-031, JCS-032, JCS-041 or JCS-042 — a different scheme from the JCS-x-yy used above, and one you cannot derive from the pair.
They cover the twin outlet case: two conductors of the same size leaving together on the equipment side, against one incoming lead.
Twin 300 against a lead up to 150
| Conductor A | Conductor B, with its outside diameter | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| LGJ-70/10 (11.4) | LGJ-70/40 (13.60) | LGJ-95/15 (13.61) | LGJ-95/20 (13.87) | LGJ-95/55 (16.0) | LGJ-120/7,20 (14.5,15.07) | LGJ-120/25 (15.74) | LGJ-150/8 (16.0) | LGJ-150/20 (16.67) | LGJ-150/25 (17.1) | |
| LGJ-300/15(23.01) | JCS-032 | JCS-032 | JCS-032 | JCS-032 | JCS-031 | JCS-031 | JCS-031 | JCS-031 | JCS-031 | JCS-031 |
| LGJ-300/20(23.43) | JCS-032 | JCS-032 | JCS-032 | JCS-032 | JCS-031 | JCS-031 | JCS-031 | JCS-031 | JCS-031 | JCS-031 |
| LGJ-300/25(23.76) | JCS-032 | JCS-032 | JCS-032 | JCS-032 | JCS-031 | JCS-031 | JCS-031 | JCS-031 | JCS-031 | JCS-02 |
| LGJ-300/40(23.94) | JCS-032 | JCS-032 | JCS-032 | JCS-031 | JCS-031 | JCS-031 | JCS-031 | JCS-031 | JCS-02 | JCS-02 |
| LGJ-300/50(24.26) | JCS-032 | JCS-031 | JCS-031 | JCS-031 | JCS-031 | JCS-031 | JCS-031 | JCS-031 | JCS-02 | JCS-02 |
| LGJ-300/70(25.20) | JCS-032 | JCS-031 | JCS-031 | JCS-031 | JCS-031 | JCS-031 | JCS-02 | JCS-02 | JCS-02 | JCS-02 |
Twin 300 against a lead from 150 to 300
| Conductor A | Conductor B, with its outside diameter | |||||||
|---|---|---|---|---|---|---|---|---|
| LGJ-150/35(17.5) | LGJ-185/10,25,30(18.0,18.9,18.88) | LGJ-185/45(19.6) | LGJ-240/30,40,55(21.6,21.66,22.4) | LGJ-300/15(23.01) | LGJ-300/20(23.43) | LGJ-300/25(23.76) | LGJ-300/40(23.94) | |
| LGJ-300/15(23.01) | JCS-031 | JCS-02 | JCS-02 | JCS-01 | JCS-01 | JCS-01 | JCS-01 | JCS-01 |
| LGJ-300/20(23.43) | JCS-02 | JCS-02 | JCS-02 | JCS-01 | — | JCS-01 | JCS-01 | JCS-01 |
| LGJ-300/25(23.76) | JCS-02 | JCS-02 | JCS-02 | JCS-01 | — | — | JCS-01 | JCS-01 |
| LGJ-300/40(23.94) | JCS-02 | JCS-02 | JCS-02 | JCS-01 | — | — | — | JCS-01 |
| LGJ-300/50(24.26) | JCS-02 | JCS-02 | JCS-02 | JCS-01 | — | — | — | — |
| LGJ-300/70(25.20) | JCS-02 | JCS-02 | JCS-01 | JCS-01 | — | — | — | — |
Twin 400
| Conductor A | Conductor B, with its outside diameter | ||||||
|---|---|---|---|---|---|---|---|
| LGJ-300/15,20,25,40,50 (23.01,23.43,23.76,23.94,24.26) | LGJ-300/70 (25.20) | LGJ-400/20 (26.91) | LGJ-400/25 (26.64) | LGJ-400/35 (26.82) | LGJ-400/50 (27.63) | LGJ-400/65 (28.0) | |
| LGJ-400/20(26.91) | JCS-042 | JCS-042 | JCS-041 | JCS-041 | JCS-041 | JCS-041 | JCS-041 |
| LGJ-400/25(26.64) | JCS-042 | JCS-042 | — | JCS-041 | JCS-041 | JCS-041 | JCS-041 |
| LGJ-400/35(26.82) | JCS-042 | JCS-042 | — | — | JCS-041 | JCS-041 | JCS-041 |
| LGJ-400/50(27.63) | JCS-042 | JCS-042 | — | — | — | JCS-041 | JCS-041 |
| LGJ-400/65(28.00) | JCS-042 | JCS-041 | — | — | — | — | JCS-041 |
JCSD, the single-outlet line
JCSD is the sheet’s single-conductor outlet clamp — 单出线 in the original. Instead of a matrix, each body is listed against every conductor it accepts, which makes it the quicker line to quote from when you only have one conductor to land.
| Model | Applicable conductor |
|---|---|
| JCSD-1-11 | JKLYJ-25, JKLJ-35, JKLGJ-35, LJ-35 |
| JCSD-1-12 | JKLYJ-50, LGJ-50, LJ-50, JKLGJ-50, LGJ-35 |
| JCSD-2-25 | JKLYJ-95, LJ-95, LJ-70, LGJ-70, JKLYJ-70, JKLGYJ-70 |
| JCSD-3-35 | JKLYJ-120, LGJ-95, JKLGYJ-120, LJ-120, JKLGYJ-95 |
| JCSD-4-45 | LGJ-120, JKLYJ-150, LJ-150, JKLGYJ-150 |
| JCSD-5-54 | LJ-185, LGJ-150, JKLYJ-185, JKLYJ-240, LGJ-185, JKLGYJ-185 |
| JCSD-6-66 | JKLYJ-300, LGJ-240, LJ-240, LJ-300, JKLGYJ-240 |
Note how few bodies there are: seven JCSD models against the dozens of JCS codes. The D line trades choice for simplicity — one body covers a spread of conductors, so it is easier to stock and harder to get wrong.
The Decimal In The Factory Notation
The dot in the factory’s notation means “or”, and once you read it that way the conductor labels make sense:
JKLGYJ-150/20.25is one clamp for JKLGYJ-150/20 or JKLGYJ-150/25 — two strandings, one body.LGJ-240/30.40is LGJ-240/30 or LGJ-240/40, same body.- The JKLGYJ table also carries a row written
JKLGYJ-/20.25with the section left out; it is the 150 row, which is what the column header on the same sheet reads, and it is listed here asJKLGYJ-150/20, 25.
So a slash-dot label is a coverage statement, not a tolerance. Order by the conductor you are running and the body is the one printed.
Fitting it
- Look the code up, do not calculate it. A code built from the section area will be wrong about as often as it is right.
- Say which family the conductor is — JKLYJ, LJ, JKLGYJ or LGJ. It changes the clamp at the same nominal size.
- The clamp is bolted, not compressed. It needs the right torque and a re-check after the first load cycle, which is exactly what the temperature-measuring version is for.
- Order the insulating cover as a separate line. It is an option on the same body, and it is not in the code.
- For a twin outlet, go to the JCS-0xx tables. The four main tables are single-conductor pairs only.
The rest of the family
- SLS — the bolted twin clamp for ACSR, with plate angles.
- SL — the bolted single clamp.
- SYT — compression, all copper.
- STY and STYG — the adjustable clamp for expanded hollow conductor.
Note: Quote the code from the table plus the conductor pair — JCS-3-35, for JKLYJ-120 on LGJ-95 — and say whether you need the standard or the temperature-measuring body.