PF Power Fittings Technical Reference

STY STYG Adjustable Equipment Clamp, Compression Type

Conductor OD: 49.00 / 51.00 / 51.36 mm · Reach: 88 or 188 mm · Plate: made to your H × A

STY and STYG adjustable equipment clamp, dimensioned drawing

STY is a two-piece clamp: two mirror-image halves, each a compression barrel on a swan-neck arm that ends in a flat plate. The two plates land together at the centre and bolt through, so the clamp straddles the terminal and picks up one conductor either side.

STY is aluminium. STYG is the copper-aluminium transition version, and the factory states in the sheet note that its dimensions are identical to STY. Same plate, same barrel, same reach — only the material of the plate changes.

H And A Are Yours To Set

The sheet prints B, D and L. It prints no H and no A, and that is deliberate. The factory note says, in the original:

“dimensions H, A (length, width) — please define them yourself, e.g. STY-1440N/100(H×A).”

H and A are the plate that lands on your equipment terminal — its length and its width. The drawing marks H on the vertical face and A across the base, so (H×A) is the footprint your pad has to accept, and the factory makes the plate to whatever you send.

Which means a purchase order reading only STY-1400/200 is incomplete. Every model in the table is written with the literal string (H×A) in it for exactly this reason: the row is a template, not a fixed part number. Send the pad size, or send a drawing of the terminal, before the order goes in.

Technical parameters

ModelApplicable conductor OD (mm)Main dimensions (mm)
BDL
STY/STYG-900K/100(H×A)49.00207488
STY/STYG-1400/100(H×A)51.00207688
STY/STYG-1440N/100(H×A)51.36248088
STY/STYG-900K/200(H×A)49.002074188
STY/STYG-1400/200(H×A)51.002076188
STY/STYG-1440N/200(H×A)51.362480188

All dimensions in millimetres. The sheet publishes no weight for these clamps.

Three conductors, two reaches, nothing else changes

The six codes collapse to three conductors × two reaches, and the two groups differ only in L:

Conductor OD (mm) B (mm) D (mm) L at /100 L at /200
900K 49.00 20 74 88 188
1400 51.00 20 76 88 188
1440N 51.36 24 80 88 188

B and D are identical either side of the divide — only the reach changes. And the numbers are tidy: the trailing /100 gives L = 88, the trailing /200 gives L = 188, so L is 12 mm less than the number in the code in both cases. The sheet publishes those two and no others.

Reading the drawing

The drawing labels five dimensions, and two of them are not in the table:

  • L (mm) — horizontal reach, from the vertical centreline out to the end of one barrel. 88 or 188.
  • B (mm) — thickness of the vertical plate, 20 mm on 900K and 1400, 24 mm on 1440N.
  • D (mm) — overall width across the compression barrel, 74 to 80. This is an outside dimension: the conductors here are 49.00 to 51.36 mm, so D is the body, not the groove.
  • H (mm) — height of the plate face. Not in the table — yours to specify.
  • A (mm) — width across the base of the plate. Not in the table — yours to specify.

Why 49 to 51 mm and not a section area

The sheet quotes the conductor outside diameter directly, and that is the only figure you can check against a stringing drawing: expanded hollow conductors with the same nominal area come in several strandings and several diameters.

The 900K and 1400 designations are the same ones that appear in the SY(G)-N heat-resistant clamp, where those conductors are listed as LGKK expanded hollow. So these are not general-purpose clamps — they are built around the large-diameter hollow conductor used on substation bus and heavy lines.

Fitting it

  • It is a compression body, not a bolted groove. It needs a press and the matching die; there are no bolts over the conductor.
  • Set both arms to the same reach before you tighten the centre joint. The two plates bolt face to face, and if one arm is a hole out the barrel sits skewed and the die will not seat squarely.
  • A and B are two plate thicknesses, so check the stud length on your pad: 20 or 24 mm of plate plus washer and nut.
  • Order the plate with the clamp, not after. H and A are made to order, so a plate mistake is a second lead time, not a second phone call.
  • No weight is published, so do not quote freight from the sheet. Ask for a weighing on the actual order.

The rest of the family

  • SY — the single-conductor compression clamp for ACSR, with A, B and C plates.
  • SYG — the same in copper-aluminium.
  • SY(G)-N, A/B/C — heat-resistant conductor, where these expanded hollow sizes are tabulated.
  • SYT — the all-copper compression clamp, plate at 0° or 30°.

Note: Quote STY or STYG, the conductor size and the reach — STY-1400/200 — and always send the pad size H × A. Without it the factory cannot start.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: