SY Compression Aluminium Equipment Clamp
Models: SY-35/6A – SY-800/70~100A · Conductor: LGJ 35–800 mm² · Palm: inline, 30° or 90°

SY is the compression equipment clamp for aluminium and ACSR: the conductor end is crimped into a tube barrel and the flat palm is bolted to the equipment terminal. There are no bolts on the conductor and no clamp plates to lose — which is why it is the default on substation work where the joint has to stay tight for twenty years without being looked at.
It is the aluminium half of a pair. For a copper conductor or a copper-to-aluminium transition, that is SYG, which is a bimetallic clamp, not this one with a different label.
The model code is the conductor, not the clamp
SY-400/20~35A is not a 400 mm² clamp. It is the clamp for LGJ-400/20, LGJ-400/25 and LGJ-400/35 — three ACSR conductors that share one body because their outside diameters differ by 0.3 mm. The two numbers are the standard ACSR designation: aluminium area over steel area.
That is why the tables below have 32 rows for 24 model codes. If you are matching an existing installation, quote the conductor, not the clamp size — LGJ-240/30 tells us the code, 240 mm² does not.
Three palms: A, B and C
All three use the same barrel and the same crimp. Only the palm changes:
| Type | Palm angle | Sizes | Barrel L1 | Note |
|---|---|---|---|---|
| A | inline, 0° | 35–800 mm², 32 rows | 60–170 mm | the default straight clamp |
| B | bent 30° | 35–800 mm², 32 rows | 60–170 mm | same numbers as A, palm pre-bent |
| C | right angle, 90° | 120–800 mm², 25 rows | 95–210 mm | palm turned square to the barrel |

Two things are worth knowing before you pick, both of them checked row by row against the factory sheet rather than assumed:
- A and B are the same clamp. Every dimension and every weight is identical across the two tables; the only difference is that B comes out of the press with the palm bent 30°. If the pad is on a slope, B saves you shimming.
- C is A with the palm turned 90° and the barrel stretched. L2 stays exactly as it is on A at every size; L1 grows by 35 mm from 120 to 630 mm² and by 40 mm at 800. The extra length is what lets the palm clear the equipment body once it is square to the barrel.
C does not exist below 120 mm². On small conductors the bend radius is tight enough that A or B reaches the pad anyway.
Technical parameters
A type, inline palm
| Model | Applicable Conductor (mm2) | Main Dimensions (mm) | Reference Weight (kg) | |||||
|---|---|---|---|---|---|---|---|---|
| Conductor | OD (mm) | A | B | D | L1 | L2 | ||
| SY-35/6A | LGJ-35/6 | 8.16 | 30 | 6.5 | 16 | 60 | 60 | 0.1 |
| SY-50/8A | LGJ-50/8 | 9.60 | 30 | 6.5 | 18 | 60 | 60 | 0.1 |
| SY-70/10A | LGJ-70/10 | 11.40 | 40 | 8 | 22 | 70 | 60 | 0.1 |
| SY-95/15A | LGJ-95/15 | 13.61 | 40 | 8 | 26 | 80 | 60 | 0.2 |
| SY-120/7A | LGJ-120/7 | 14.50 | 50 | 10 | 26 | 80 | 80 | 0.3 |
| SY-120/20A | LGJ-120/20 | 15.07 | 50 | 10 | 26 | 80 | 80 | 0.3 |
| SY-150/8A | LGJ-150/8 | 16.00 | 50 | 10 | 30 | 90 | 80 | 0.3 |
| SY-150/20A | LGJ-150/20 | 16.67 | 50 | 10 | 30 | 90 | 80 | 0.3 |
| SY-185/10A | LGJ-185/10 | 18.00 | 50 | 12 | 32 | 90 | 80 | 0.3 |
| SY-185/25~30A | LGJ-185/25 | 18.90 | 50 | 12 | 32 | 90 | 80 | 0.3 |
| SY-185/25~30A | LGJ-185/30 | 18.88 | 50 | 12 | 32 | 90 | 80 | 0.3 |
| SY-210/10A | LGJ-210/10 | 19.00 | 50 | 12 | 34 | 100 | 80 | 0.4 |
| SY-210/25A | LGJ-210/25 | 19.98 | 50 | 12 | 34 | 100 | 80 | 0.4 |
| SY-240/30~40A | LGJ-240/30 | 21.60 | 50 | 12 | 36 | 100 | 80 | 0.5 |
| SY-240/30~40A | LGJ-240/40 | 21.66 | 50 | 12 | 36 | 100 | 80 | 0.5 |
| SY-300/15A | LGJ-300/15 | 23.01 | 63 | 14 | 40 | 110 | 100 | 0.6 |
| SY-300/20A | LGJ-300/20 | 23.43 | 63 | 14 | 40 | 110 | 100 | 0.6 |
| SY-300/25~40A | LGJ-300/25 | 23.76 | 63 | 14 | 40 | 110 | 100 | 0.6 |
| SY-300/25~40A | LGJ-300/40 | 23.94 | 63 | 14 | 40 | 110 | 100 | 0.6 |
| SY-400/20~35A | LGJ-400/20 | 26.91 | 63 | 16 | 45 | 120 | 100 | 0.7 |
| SY-400/20~35A | LGJ-400/25 | 26.64 | 63 | 16 | 45 | 120 | 100 | 0.7 |
| SY-400/20~35A | LGJ-400/35 | 26.82 | 63 | 16 | 45 | 120 | 100 | 0.7 |
| SY-400/50~65A | LGJ-400/50 | 27.63 | 63 | 16 | 45 | 120 | 100 | 0.7 |
| SY-400/50~65A | LGJ-400/65 | 28.00 | 63 | 16 | 45 | 120 | 100 | 0.7 |
| SY-500/35~45A | LGJ-500/35 | 30.00 | 80 | 16 | 52 | 130 | 100 | 1.0 |
| SY-500/35~45A | LGJ-500/45 | 30.00 | 80 | 16 | 52 | 130 | 100 | 1.0 |
| SY-500/65A | LGJ-500/65 | 30.96 | 80 | 16 | 52 | 130 | 100 | 1.0 |
| SY-630/45A | LGJ-630/45 | 33.60 | 100 | 20 | 60 | 150 | 100 | 1.5 |
| SY-630/55A | LGJ-630/55 | 34.32 | 100 | 20 | 60 | 150 | 100 | 1.5 |
| SY-800/55A | LGJ-800/55 | 38.40 | 125 | 22 | 65 | 170 | 125 | 2.5 |
| SY-800/70~100A | LGJ-800/70 | 38.58 | 125 | 22 | 65 | 170 | 125 | 2.5 |
| SY-800/70~100A | LGJ-800/100 | 38.98 | 125 | 22 | 65 | 170 | 125 | 2.5 |
B type, 30° palm
Identical to A in every dimension and weight; palm pre-bent 30°.
| Model | Applicable Conductor (mm2) | Main Dimensions (mm) | Reference Weight (kg) | |||||
|---|---|---|---|---|---|---|---|---|
| Conductor | OD (mm) | A | B | D | L1 | L2 | ||
| SY-35/6B | LGJ-35/6 | 8.16 | 30 | 6.5 | 16 | 60 | 60 | 0.1 |
| SY-50/8B | LGJ-50/8 | 9.60 | 30 | 6.5 | 18 | 60 | 60 | 0.1 |
| SY-70/10B | LGJ-70/10 | 11.40 | 40 | 8 | 22 | 70 | 60 | 0.1 |
| SY-95/15B | LGJ-95/15 | 13.61 | 40 | 8 | 26 | 80 | 60 | 0.2 |
| SY-120/7B | LGJ-120/7 | 14.50 | 50 | 10 | 26 | 80 | 80 | 0.3 |
| SY-120/20B | LGJ-120/20 | 15.07 | 50 | 10 | 26 | 80 | 80 | 0.3 |
| SY-150/8B | LGJ-150/8 | 16.00 | 50 | 10 | 30 | 90 | 80 | 0.3 |
| SY-150/20B | LGJ-150/20 | 16.67 | 50 | 10 | 30 | 90 | 80 | 0.3 |
| SY-185/10B | LGJ-185/10 | 18.00 | 50 | 12 | 32 | 90 | 80 | 0.3 |
| SY-185/25~30B | LGJ-185/25 | 18.90 | 50 | 12 | 32 | 90 | 80 | 0.3 |
| SY-185/25~30B | LGJ-185/30 | 18.88 | 50 | 12 | 32 | 90 | 80 | 0.3 |
| SY-210/10B | LGJ-210/10 | 19.00 | 50 | 12 | 34 | 100 | 80 | 0.4 |
| SY-210/25B | LGJ-210/25 | 19.98 | 50 | 12 | 34 | 100 | 80 | 0.4 |
| SY-240/30~40B | LGJ-240/30 | 21.60 | 50 | 12 | 36 | 100 | 80 | 0.5 |
| SY-240/30~40B | LGJ-240/40 | 21.66 | 50 | 12 | 36 | 100 | 80 | 0.5 |
| SY-300/15B | LGJ-300/15 | 23.01 | 63 | 14 | 40 | 110 | 100 | 0.6 |
| SY-300/20B | LGJ-300/20 | 23.43 | 63 | 14 | 40 | 110 | 100 | 0.6 |
| SY-300/25~40B | LGJ-300/25 | 23.76 | 63 | 14 | 40 | 110 | 100 | 0.6 |
| SY-300/25~40B | LGJ-300/40 | 23.94 | 63 | 14 | 40 | 110 | 100 | 0.6 |
| SY-400/20~35B | LGJ-400/20 | 26.91 | 63 | 16 | 45 | 120 | 100 | 0.7 |
| SY-400/20~35B | LGJ-400/25 | 26.64 | 63 | 16 | 45 | 120 | 100 | 0.7 |
| SY-400/20~35B | LGJ-400/35 | 26.82 | 63 | 16 | 45 | 120 | 100 | 0.7 |
| SY-400/50~65B | LGJ-400/50 | 27.63 | 63 | 16 | 45 | 120 | 100 | 0.7 |
| SY-400/50~65B | LGJ-400/65 | 28.00 | 63 | 16 | 45 | 120 | 100 | 0.7 |
| SY-500/35~45B | LGJ-500/35 | 30.00 | 80 | 16 | 52 | 130 | 100 | 1.0 |
| SY-500/35~45B | LGJ-500/45 | 30.00 | 80 | 16 | 52 | 130 | 100 | 1.0 |
| SY-500/65B | LGJ-500/65 | 30.96 | 80 | 16 | 52 | 130 | 100 | 1.0 |
| SY-630/45B | LGJ-630/45 | 33.60 | 100 | 20 | 60 | 150 | 100 | 1.5 |
| SY-630/55B | LGJ-630/55 | 34.32 | 100 | 20 | 60 | 150 | 100 | 1.5 |
| SY-800/55B | LGJ-800/55 | 38.40 | 125 | 22 | 65 | 170 | 125 | 2.5 |
| SY-800/70~100B | LGJ-800/70 | 38.58 | 125 | 22 | 65 | 170 | 125 | 2.5 |
| SY-800/70~100B | LGJ-800/100 | 38.98 | 125 | 22 | 65 | 170 | 125 | 2.5 |
C type, 90° palm
From 120 mm² up. L2 equals the A type at the same conductor; L1 is 35 mm longer, 40 mm at 800.
| Model | Applicable Conductor (mm2) | Main Dimensions (mm) | Reference Weight (kg) | |||||
|---|---|---|---|---|---|---|---|---|
| Conductor | OD (mm) | A | B | D | L1 | L2 | ||
| SY-120/7C | LGJ-120/7 | 14.50 | 50 | 10 | 26 | 115 | 80 | 0.3 |
| SY-120/20C | LGJ-120/20 | 15.07 | 50 | 10 | 26 | 115 | 80 | 0.3 |
| SY-150/8C | LGJ-150/8 | 16.00 | 50 | 10 | 30 | 125 | 80 | 0.4 |
| SY-150/20C | LGJ-150/20 | 16.67 | 50 | 10 | 30 | 125 | 80 | 0.4 |
| SY-185/10C | LGJ-185/10 | 18.00 | 50 | 12 | 32 | 125 | 80 | 0.5 |
| SY-185/25~30C | LGJ-185/25 | 18.90 | 50 | 12 | 32 | 125 | 80 | 0.5 |
| SY-185/25~30C | LGJ-185/30 | 18.88 | 50 | 12 | 32 | 125 | 80 | 0.5 |
| SY-210/10C | LGJ-210/10 | 19.00 | 50 | 12 | 34 | 135 | 80 | 0.6 |
| SY-210/25C | LGJ-210/25 | 19.98 | 50 | 12 | 34 | 135 | 80 | 0.6 |
| SY-240/30~40C | LGJ-240/30 | 21.60 | 50 | 12 | 36 | 135 | 80 | 0.7 |
| SY-240/30~40C | LGJ-240/40 | 21.66 | 50 | 12 | 36 | 135 | 80 | 0.7 |
| SY-300/15C | LGJ-300/15 | 23.01 | 63 | 16 | 40 | 145 | 100 | 0.7 |
| SY-300/20C | LGJ-300/20 | 23.43 | 63 | 16 | 40 | 145 | 100 | 0.7 |
| SY-300/25~40C | LGJ-300/25 | 23.76 | 63 | 16 | 40 | 145 | 100 | 0.7 |
| SY-300/25~40C | LGJ-300/40 | 23.94 | 63 | 16 | 40 | 145 | 100 | 0.7 |
| SY-400/20~35C | LGJ-400/20 | 26.91 | 63 | 16 | 45 | 155 | 100 | 0.8 |
| SY-400/20~35C | LGJ-400/25 | 26.64 | 63 | 16 | 45 | 155 | 100 | 0.8 |
| SY-400/20~35C | LGJ-400/35 | 26.82 | 63 | 16 | 45 | 155 | 100 | 0.8 |
| SY-500/35~45C | LGJ-500/35 | 30.00 | 80 | 16 | 52 | 165 | 100 | 1.0 |
| SY-500/35~45C | LGJ-500/45 | 30.00 | 80 | 16 | 52 | 165 | 100 | 1.0 |
| SY-630/45C | LGJ-630/45 | 33.60 | 100 | 20 | 60 | 185 | 100 | 1.7 |
| SY-630/55C | LGJ-630/55 | 34.32 | 100 | 20 | 60 | 185 | 100 | 1.7 |
| SY-800/55C | LGJ-800/55 | 38.40 | 125 | 22 | 65 | 210 | 125 | 2.5 |
| SY-800/70~100C | LGJ-800/70 | 38.58 | 125 | 22 | 65 | 210 | 125 | 2.5 |
| SY-800/70~100C | LGJ-800/100 | 38.98 | 125 | 22 | 65 | 210 | 125 | 2.5 |
All dimensions in millimetres. Weight is per piece, reference only.
Reading the drawing
- A (mm) — palm width, 30 to 125 mm. It sets the footprint on the pad and the room for the bolt.
- B (mm) — palm thickness, 6.5 to 22 mm. This is the number that decides bolt preload, not the width.
- D (mm) — barrel outside diameter, 16 to 65 mm. This selects the die.
- L1 (mm) — barrel length, i.e. the crimp zone and therefore the strip length.
- L2 (mm) — palm length, 60 to 125 mm.
Note that B is used twice on this sheet: as the palm thickness in the table, and as the type letter in the model code. They are not related. SY-400/20~35B has a 16 mm thick palm, not a 20 mm one.
The palm hole is drilled to your pad
The A and B drawings show a plain palm with no hole, and none of the three tables carries a Φ column — while the terminal pages next door all do. That is the same arrangement as the STR copper compression clamp: the palm is a made-to-pattern item, drilled to whatever the equipment pad is.
The C sheet does draw a single hole in the palm, because at 90° the palm has to be a defined shape to clear the equipment body.
Either way, send the stud size and the hole centres with the enquiry. A Ø18 hole in the 30 mm palm leaves 6 mm of metal each side; a Ø24 leaves 3 mm and we will say so rather than drill it.
Crimping
- Strip to L1 minus 1–2 mm. On SY-240/30 that is a 98 mm strip against a 100 mm barrel.
- Die from D. One barrel diameter, one die; the conductor size does not enter into it.
- Two or three indents per barrel, worked from the palm end toward the mouth so the strands are not pushed back out.
- Do not crimp over the neck. The transition from barrel to palm is where the wall thins; an indent there cracks it.
- Aluminium on aluminium only. An SY on a copper conductor is a galvanic cell with a 1.2 V head start, and it fails quietly under the insulation tape.

The rest of the family
- SYG — copper-to-aluminium transition, same barrel, bimetallic palm.
- SSY — twin bundle, two barrels on one palm.
- SY/SYG-N — heat-resistant conductor grade, for operating temperatures above 80 °C.
- SL — the bolted version, when there is no press on site.
- STR — the copper compression clamp for electrified railway.
Note: Quote by conductor designation (LGJ-240/30) and palm type (A, B or C), and send the pad stud size. Dimensions in the tables are catalogue values; the palm is drilled to your drawing.