SY / SYG-N Heat Resistant Single Conductor Equipment Clamp — A, B and C Types

Models: SY(G)-120/7NA(B/C) to SY(G)-1440/120NA(B/C) · Conductor: NRLH58/60, LGKK · Palm: A 0°, B 30°, C 90°

SY heat resistant single conductor equipment clamp, straight palm SYG heat resistant single conductor equipment clamp, copper palm SY SYG-N heat resistant clamp, C type, 90 degree palm SY SYG-N heat resistant clamp, C type drawing

The N series is for conductors that run hotter than ACSR. Standard SY is sized against LGJ; this one is sized against NRLH58/60 heat-resistant aluminium alloy and LGKK expanded hollow conductor, and the barrels run from 120 mm² up to 1440 mm² — bigger than anything on the standard sheet.

The code

SY(G)-500/65NA(B/C)

Part of the code Meaning
SY single conductor equipment clamp, compression, all aluminium
SYG the same clamp with a copper-aluminium brazed palm
(G) printed in the catalogue to mean “either of the two above”
500/65 the conductor, NRLH58/60-500/65
N heat-resistant series
A palm at 0° — horizontal, in line with the barrel
B palm at 30°
C palm at 90° — square to the barrel
(B/C) the same row is also made as the other two angles

The factory note reads: “additional letters: A indicates horizontal (0°), B indicates 30°, C indicates 90°”, and the drawings agree. The three letters are one product in three palm angles, so they are one table here, not three.

SY and SYG share the table, and that is official

Every row carries both model prefixes and both weights because the factory note states it outright: the SYG type is the copper-aluminium brazed clamp and “its dimensions are identical with SY type.”

So the (G) in the code does not change A, B, D, L1 or L2. It changes the metal at the palm and adds 0.1 to 0.3 kg. Choose SY for an aluminium terminal, SYG for a copper terminal, and the barrel, the die and the strip length are the same either way.

Technical parameters, all three angles

ModelConductorMain dimensions (mm)Reference weight (kg)
ABDL1 A·BL1 CL2SY typeSYG type
SY(G)-120/7NA(B/C)NRLH58/60-120/7801436120150850.60.7
SY(G)-150/8~20NA(B/C)NRLH58/60-150/8~20801436130160850.60.7
SY(G)-185/10NA(B/C)NRLH58/60-185/10801440140170850.80.9
SY(G)-185/25~30NA(B/C)NRLH58/60-185/25~30801440140170850.80.9
SY(G)-210/10NA(B/C)NRLH58/60-210/1010016451501801051.11.2
SY(G)-240/30~40NA(B/C)NRLH58/60-240/30~4010016451601901051.11.2
SY(G)-300/20~40NA(B/C)NRLH58/60-300/20~4010018501702001051.41.5
SY(G)-400/20~35NA(B/C)NRLH58/60-400/20~3510020551802151051.71.8
SY(G)-400/50~65NA(B/C)NRLH58/60-400/50~6510020551802151051.71.8
SY(G)-500/35~45NA(B/C)NRLH58/60-500/35~4512522651902301302.72.8
SY(G)-500/65NA(B/C)NRLH58/60-500/6512522651902301302.72.8
SY(G)-630/45~55NA(B/C)NRLH58/60-630/45~5512522702002801303.23.4
SY(G)-800/55~100NA(B/C)NRLH58/60-800/55~10012522702002801303.23.4
SY(G)-1000/125NA(B/C)NRLH58/60-1000/12515024762102951554.24.5
SY(G)-1440/120NA(B/C)NRLH58/60-1440/12015024802103251554.64.9
SY(G)-600KA(B/C)LGKK-60012520761801801304.24.4
SY(G)-900KA(B/C)LGKK-90012520741801801303.94.1
SY(G)-1400KA(B/C)LGKK-140012524842602601305.05.2

All dimensions in millimetres. SY(G) means the row covers both SY-…N and SYG-…N. L1 is printed twice because the C palm needs a longer barrel on the large sizes — take the column that matches the angle you are ordering.

Reading the table

  • A (mm) — palm width, 80 to 150 mm.
  • B (mm) — palm thickness, 14 to 24 mm.
  • D (mm) — barrel outside diameter, 36 to 84 mm. This selects the die, and note how far it runs: 84 mm on the LGKK-1400 against 65 on the largest standard SY.
  • L1 (mm) — barrel length, 120 to 325 mm. This is the crimp zone and the strip length.
  • L2 (mm) — palm length, 85 to 155 mm.

The last three rows are LGKK — expanded-diameter hollow conductor, the kind used on substation busbar connections. They are not ACSR and not NRLH, they are a separate conductor family, and they are why D jumps to 84 mm.

Why C has a longer barrel

Turning the plate square to the barrel means the barrel has to stand off the equipment body far enough for the plate to land flat. How much that costs depends on the size:

Conductor class L1 added against A/B
120/7 up to 300/20~40 +30 mm
400/2035, 400/5065 +35 mm
500/35~45, 500/65 +40 mm
630/4555, 800/55100 +80 mm
1000/125 +85 mm
1440/120 +115 mm
LGKK-600, LGKK-900, LGKK-1400 no change at all

That last row is the one worth remembering. On the three expanded-hollow-conductor sizes the C palm is a straight substitution — the barrel is already long enough. On the large NRLH sizes it is not: a 1440 C has a 325 mm barrel against 210 mm on the A/B, which is a different press setup and a different strip length.

A, B, D and L2 do not move at all. All three angles take the same die, which is why they are one part number with a letter on the end rather than three parts.

L2 × A is a made-to-order dimension

The factory note applies to the whole series: “if changed, the user should specify L2 × A value when ordering, e.g. SY(G)-500/65NC (L2 × A).”

On a substation the equipment pad is often deeper or narrower than the catalogue plate, and the answer is to write the plate size into the model code rather than to shim it on site. Give us L2 and A and the code carries them — SY(G)-500/65NC(90×60) is cheaper than a site adapter plate and it keeps the earth path in one piece.

What the copper palm costs

SY(G)-1000/125NA(B/C) is 4.5 kg with the brazed copper plate.

The rest of the weight column is consistent — SYG runs 0.1 to 0.3 kg heavier than SY at every size, which is what a copper palm costs you.

Crimping heat-resistant conductor

  • Do not use an ACSR die. NRLH is alloy, not steel-cored aluminium; the strand bundle compresses differently and the die is chosen from D, but the indent depth should be set for alloy.
  • Strip to L1. This sheet publishes it, so use it: 190 mm on the 500/65 A or B, 230 mm on the C, less 1 to 2 mm.
  • Heat-resistant conductor is more creep-resistant but less forgiving of nicks. Score a NRLH strand at the strip and you have made a stress riser that the higher operating temperature will find.
  • Do not interchange L1 between C and A/B rows. A 630 C has an 80 mm longer barrel than the 630 A; ordering an A against a C drawing is an 80 mm error that only shows up at installation.
  • Support the barrel behind a C palm. A 325 mm barrel on the 1440 leaves a long lever behind the joint; the palm should not carry the conductor weight into the pad.
  • Do not infer the conductor from the code alone. SY(G)-800/55~100NA covers three NRLH conductors; SY(G)-600KA is an LGKK. The A suffix on the LGKK rows is not a conductor size.

The rest of the family

  • SY — standard ACSR, 35–800 mm².
  • SYG — standard ACSR, copper-aluminium, flash welded.
  • SSY-N — the twin-bundle heat-resistant clamp, also A/B/C.
  • SSYG-N — twin bundle, brazed copper-aluminium.

Note: Quote the conductor by its full designation (NRLH58/60-500/65 or LGKK-1400), give the palm angle letter with the model, say whether the terminal is copper, and give L2 × A if the pad is not the catalogue plate.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: