PF Power Fittings Technical Reference

STR Copper Compression Equipment Clamp

Models: STR-25 – STR-240 (9 sizes)

STR copper compression equipment clamp

STR is the wide, thick-palm compression clamp in the railway family. It has the same crimped tube barrel as the DTR terminal, but the palm is a broad spade rather than a lug: 30 to 50 mm wide and 4 to 7 mm thick, against 20 to 48 mm and 3 to 8 mm on the DTR at the same conductor sizes.

Two things make it the page to quote on when the joint matters:

  • The sheet publishes L1, the barrel length. That is the crimp zone and the strip length, in one number, per size — the DTR sheet does not give it.
  • The palm is drawn plain, with no bolt hole. STR is a made-to-pattern item, not a catalogue drilling.

Part of the electrified railway equipment clamp family.

Technical parameters

ModeldDLL1L2WS
STR-258.5141155050304
STR-3510141256050304.5
STR-5011.5161256050404.5
STR-7013.5181457060404.5
STR-9515201557065405.5
STR-12016.8221657570406
STR-15019251757580507
STR-18521271858080507
STR-24024301858085507

All dimensions in millimetres.

Reading the drawing

The photograph above sits over the drawing on the same sheet: barrel on the right, palm on the left, and the three lengths marked off as L, L1 and L2.

  • L1 (mm) — barrel length, i.e. the crimp zone. 50 mm at 25 mm² up to 80 mm at 240.
  • L2 (mm) — palm length, 50 to 85 mm.
  • L (mm) — overall length, 115 to 185 mm. Across the nine sizes L is L1 + L2 plus a 15 to 25 mm neck — which is what the drawing shows, and a quick way to check any drawing you are sent against the catalogue.
  • W (mm) — palm width, 30 to 50 mm.
  • S (mm) — palm thickness, 4.0 to 7.0 mm.
  • d (mm) — bore, 8.5 to 24 mm.
  • D (mm) — barrel outside diameter, 14 to 30 mm. Selects the die.

Note that L1 and L2 are independent: at 25 mm² the barrel and the palm are both 50 mm; at 240 mm² the barrel is 80 and the palm 85. You cannot infer one from the other, and a short palm does not mean a short barrel.

The palm has no catalogue hole

The drawing shows a plain spade, the photograph shows a plain spade, and the table has no Φ column — while every terminal on the neighbouring pages does. That is not an omission: the palm hole on STR is a made-to-pattern item.

Which is the right way round for this clamp. The palm is wide and thick enough to be drilled to whatever the equipment pad happens to be — M10 on a small disconnector, M16 on a heavier terminal — and a catalogue hole would only fit one of them. Send the stud size and the hole centres with the enquiry and the palm is drilled to it.

The limit on how large the hole can go is the same arithmetic as everywhere on this site: (W − Φ)/2 is the metal either side. On the 30 mm wide palm a Ø18 hole leaves 6 mm each side, which is fine; a Ø24 leaves 3 mm, which is not. The thick palm (S up to 7 mm) buys you preload, not an unlimited hole.

STR against DTR

Same conductor, same crimp, different palm:

Size DTR palm W × S (mm) STR palm W × S (mm) DTR L (mm) STR L (mm)
25 mm² 20 × 3.0 30 × 4.0 79 115
120 mm² 34 × 5.5 40 × 6.0 118 165
240 mm² 48 × 8.0 50 × 7.0 160 185

The palm is broader and, at small sizes, half again as thick — but note that at 240 mm² the DTR palm is actually the thicker of the two (8.0 against 7.0). If the joint is the deciding factor at the top of the range, that is worth checking rather than assuming the heavier-looking clamp is heavier.

Crimping

This is the page where the sheet does the work for you:

  • Strip to L1, less 1 to 2 mm so the strands sit inside the barrel mouth rather than proud of it. On a 240 that is a 78 mm strip against a 80 mm barrel.
  • One die position per barrel diameter. An 80 mm barrel of Ø30 takes two or three positions; a 50 mm barrel of Ø14 takes two.
  • Work from the palm end toward the barrel mouth, so the copper flows toward the open end and the strand bundle is not pushed back out.
  • Check the palm is still flat after crimping. The barrel swaging pulls on the neck, and a palm that has bowed off the pad face will only contact at one edge — which is a hot joint waiting to happen.

Standards

Dimensioned against TB/T 2073-2020, tested to TB/T 2074-2020; general requirements GB/T 2314, mechanical tests GB/T 2317.1, load-cycling stability GB/T 2317.3. Copper T2 to GB/T 5231. Where the clamp forms part of the OCS electrical connection, TB/T 2075.11 (electrical connection devices) governs it.

The rest of the family

  • STR-S — the same clamp with two holes and a fixed hole spacing.
  • DTR — the single-hole terminal, narrower palm, no L1 on the sheet.
  • SST — plate type, for a twin bundle.

Note: Send the pad drawing with the stud size, the hole centres and the conductor class; the palm is drilled from it and the die is chosen from D.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: