SST Double-Conductor Copper Equipment Clamp

Models: SST-7095, SST-120150, SST-185~240

SST double-conductor copper equipment clamp

SST is a different animal from the terminals on the neighbouring pages. DTR, DTGR and STR take one conductor into a crimped barrel. SST does not crimp anything: it clamps both conductors of a twin bundle between copper plates with nine bolts, and the flat tab at the end bolts to the equipment terminal.

That is the point of it. On a twin bundle you can bring the two conductors into one fitting — one bolt group, one contact face, one thing to torque and check — instead of two separate lugs stacked on the same stud, where the second one never sits flat on the first.

Part of the electrified railway equipment clamp family.

Technical parameters

ModelRPlate ThicknessPlate Width
SST-70~957681080100
SST-120~1508681080100
SST-185~24010.5681080100

All dimensions in millimetres.

R is the groove radius, and it is the only column that matters for fit

R is the radius of the groove the conductor lies in, so 2R is the conductor outside diameter the clamp is cut for:

Model R (mm) Nominal conductor Ø (2R)
SST-70~95 7 14 mm
SST-120~150 8 16 mm
SST-185~240 10.5 21 mm

Check your conductor’s actual outside diameter — not the nominal square millimetre figure, and not the figure in the aluminium table if you are running ACSR or a compacted conductor, because compaction takes 2 to 4 mm off the diameter at these sizes. A 95 mm² compacted conductor can be closer to a 120’s diameter than to a 70’s.

The groove is a compromise across the group it covers, and that compromise is asymmetric in one direction worth knowing:

  • Groove slightly tight on the conductor — the plates bite and the clamp grips, which is what you want.
  • Groove slightly loose — contact becomes a line along the top of the conductor rather than an arc around it. Resistance goes up, and under vibration the conductor frets in the groove and the joint walks.

So if your conductor sits at the bottom of a group, the groove is loose. If you are clamping one conductor size over a long run, say so and ask for a matched radius rather than accepting the group figure.

Plate thickness and width are a set, not a value per model

The header is grouped deliberately: three figures under Plate Thickness and two under Plate Width. Read them as the set the clamp is built from, not as one dimension per model:

  • Thickness 6, 8 or 10 mm — the plate that carries the bolt preload and the bending between bolts. Heavier plate resists the stack rocking under short-circuit load.
  • Width 80 or 100 mm — 80 mm is what the drawing dimensions; 100 mm is the wide option for a heavier bundle.

Tell us which combination you want when you order. Both are catalogue options, and quoting from a model code alone does not pin them down.

Reading the drawing

SST dimensioned drawing, plan and end view

  • Nine bolts, three rows of three — that is how the load gets spread along the clamp instead of being carried at two points. Torque them in stages, alternating ends and working toward the middle, or the plate bows and the middle of the conductor is never gripped.
  • 85 mm — the tab, from the bolt block to the end. This is the part that reaches the equipment terminal; check it against the reach you need, not just against the pad pattern.
  • 80 mm — across the plate, as drawn.
  • 100 mm — the overall height of the stack in the end view: plates and both conductors together. This is the figure that decides whether the assembly clears the terminal box.

The tab is drawn plain, with no bolt holes dimensioned. As with the STR, the holes are drilled to the equipment pad pattern — send the stud size and the centres.

Where it goes

A twin-bundle equipment clamp sits between the bundle and the equipment terminal: conductors in from one side, bolted tab to the other. Its enemies are not current — it carries what the bundle carries — but vibration and short-circuit impulse, both of which work at the bolt group. That is why the plate is 6 to 10 mm thick and why the torque sequence matters more here than on any lug on this site.

If the clamp is going onto a 220 kV bundle, corona and radio-interference performance is normally written into the specification as well. Tell us at enquiry stage rather than at inspection.

The copper-to-aluminium boundary

SST is copper throughout, so it expects a copper or tinned pad. Bolted directly to an aluminium terminal block in a damp location it will do what any copper-to-aluminium joint does — the aluminium goes, quietly, under the washer — and the answer is a bimetallic transition plate between them, or a tin-plated plate. Both are ordinary, off-the-shelf practice; neither is something to improvise on site. Where the same idea is built into the fitting, that is the SYG railway clamp — copper barrel, aluminium palm — but it only exists in the railway sizes, 120 and 150 mm².

Standards

General requirements GB/T 2314; mechanical tests GB/T 2317.1; joint stability under load cycling GB/T 2317.3. Copper T2 to GB/T 5231. Where the clamp forms part of the OCS electrical connection, TB/T 2075.11 governs it; where it lands on substation equipment, the equipment standard applies.

The rest of the family

  • DTR — single-hole copper terminal, 25–240 mm².
  • STR — single-conductor clamp with a plain, wider palm.
  • SYG — railway only, reverse type: copper barrel, aluminium palm.

Note: Send the conductor’s actual outside diameter, the plate thickness and width you want, and the pad drilling. Those four decide the clamp; the model code alone does not.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: