SLS Bolted Twin Conductor Equipment Clamp
Conductors: LGJ-185240, 300400, 500~630, 800 · Spacing: 120 / 200 mm · Plate: 0°, 30° or 90°

SLS terminates a twin bundle onto one equipment pad without a press. Two aluminium alloy bodies, four bolts each, eight in total, a conductor groove in each body, and one plate that lands on the terminal.
It covers ACSR from LGJ-185 to LGJ-800 in four sizes. Above 800 the answer is the heat-resistant SSL or a compression twin.
Four sizes, two spacings, three angles
The code SLS-6C-200 carries three separate choices:
| Part | Meaning |
|---|---|
SLS |
bolted twin clamp, all aluminium |
4 / 5 / 6 / 7 |
the clamp size — it is the conductor range, not a section area |
A / B / C |
plate angle: 0°, 30°, 90° |
-120 or -200 |
spacing between the two conductor grooves |
The numbers 4 to 7 are size codes, and they map to conductor ranges: 4 is LGJ-185240, 5 is LGJ-300400, 6 is LGJ-500~630, 7 is LGJ-800. Do not read them as 4 mm² or 40 mm².
Size 7 exists only at 200 mm spacing. Sizes 4, 5 and 6 come in both 120 and 200. That gives 3 + 4 = 7 rows per angle, 21 in total across A, B and C.
Technical parameters
| Model | Conductor | Main dimensions (mm) | Reference weight (kg) | |||
|---|---|---|---|---|---|---|
| A | B | H | L | |||
| SLS-4A-120 | LGJ-185~240 | 80 | 16 | 85 | 120 | 2.0 |
| SLS-5A-120 | LGJ-300~400 | 100 | 16 | 105 | 120 | 2.15 |
| SLS-6A-120 | LGJ-500~630 | 125 | 20 | 130 | 120 | 3.7 |
| SLS-4A-200 | LGJ-185~240 | 80 | 16 | 85 | 200 | 2.15 |
| SLS-5A-200 | LGJ-300~400 | 100 | 16 | 105 | 200 | 2.35 |
| SLS-6A-200 | LGJ-500~630 | 125 | 20 | 130 | 200 | 4.05 |
| SLS-7A-200 | LGJ-800 | 125 | 22 | 130 | 200 | 5.55 |
| SLS-4B-120 | LGJ-185~240 | 80 | 16 | 85 | 120 | 2.0 |
| SLS-5B-120 | LGJ-300~400 | 100 | 16 | 105 | 120 | 2.15 |
| SLS-6B-120 | LGJ-500~630 | 125 | 20 | 130 | 120 | 3.7 |
| SLS-4B-200 | LGJ-185~240 | 80 | 16 | 85 | 200 | 2.15 |
| SLS-5B-200 | LGJ-300~400 | 100 | 16 | 105 | 200 | 2.35 |
| SLS-6B-200 | LGJ-500~630 | 125 | 20 | 130 | 200 | 4.05 |
| SLS-7B-200 | LGJ-800 | 125 | 22 | 130 | 200 | 5.55 |
| SLS-4C-120 | LGJ-185~240 | 80 | 16 | 85 | 120 | 2.0 |
| SLS-5C-120 | LGJ-300~400 | 100 | 16 | 105 | 120 | 2.15 |
| SLS-6C-120 | LGJ-500~630 | 125 | 20 | 130 | 120 | 3.7 |
| SLS-4C-200 | LGJ-185~240 | 80 | 16 | 85 | 200 | 2.15 |
| SLS-5C-200 | LGJ-300~400 | 100 | 16 | 105 | 200 | 2.35 |
| SLS-6C-200 | LGJ-500~630 | 125 | 20 | 130 | 200 | 4.05 |
| SLS-7C-200 | LGJ-800 | 125 | 22 | 130 | 200 | 5.55 |
All dimensions in millimetres. All 21 orderable codes are listed — the A, B and C rows are dimensionally identical, so the table is the same three times with a different letter.
Reading the drawing
- A (mm) — plate width, 80 to 125. It sets the footprint on the equipment pad.
- B (mm) — plate thickness, 16 to 22 mm. This is what carries bolt preload.
- H (mm) — plate length, 85 to 130, measured from the conductor section to the end of the plate.
- L (mm) — spacing between the two bodies, 120 or 200, and the same figure as the trailing number in the code.
What it is made of
The factory note on all three sheets: “clamp body and gland are aluminium alloy, other parts are hot-dip galvanised steel.”
So the two castings that grip the conductor are aluminium alloy and the bolts and keep plates are galvanised steel. That is the normal arrangement and it matters in two ways:
- The bolts are not stainless. On a coastal or industrial site, specify a finish upgrade or expect to replace them at first maintenance.
- The aluminium castings are the conductive path, so the conductor-to-body contact is what carries the current; the steel only provides the clamping force.
Fitting it
- Eight bolts, cross pattern. Four per body, and each body has to be pulled down evenly or the groove closes on one edge of the conductor.
- Do both bodies with the same torque. A pair clamped to different torques sits at different heights and the plate rocks on the pad.
- Grease the conductor. The oxide film on aluminium is the contact resistance; jointing compound under the bodies is what keeps the joint cool at load.
- Not a spacer. The plate carries current, not tension — fit it before the bundle is sagged.
- B is a two-plate thickness, so check the stud length on the pad before ordering: 16 to 22 mm of clamp plus a washer and nut is a lot of stud.
The rest of the family
- SLSG — the same clamp with copper plates, 5 mm shorter plate.
- SSL/SSLG — heat-resistant conductor, larger sizes, plate size carried in the code.
- SL — the single-conductor bolted clamp.
- SSY — the compression twin, when a press is available.
Note: Quote the size code, the angle and the spacing — SLS-6B-200. And say whether the pad is copper: on a copper pad this should be the SLSG.