PF Power Fittings Technical Reference

SL Aluminum Equipment Clamp

SL aluminum equipment clamp

Models: SL-1A/1B – SL-4A/4B (4 sizes) · Conductor: 35–240 mm² · Bolts: 4 or 6

SL is the bolted aluminium equipment clamp: the conductor is clamped between two plates by bolts instead of being crimped into a barrel. It is the oldest and still the most common way to land an aluminium jumper or downlead on a transformer, a disconnector or a busbar terminal, because it needs no press, no die and no conductor preparation beyond cleaning.

Two things about this sheet confuse buyers, and both are covered below: what the A and B suffixes mean, and why the factory prints two tables with the same numbers.

A and B are palm angles, not sizes

SL-3A and SL-3B are the same clamp with the same conductor range and the same four dimensions. The difference is the palm — the flat plate that bolts to the equipment terminal. On the drawing the flat version and a version turned down 30° are both shown against one table, which is why they share a row.

That 30° matters on site: it decides whether the palm lands flat on a horizontal terminal or has to reach down to a vertical one without putting a bend in the jumper. On a DR terminal or a transformer cover the palm usually sits horizontal and you want the flat version; where the clamp hangs off the side of a structure and the jumper falls away, the turned palm keeps the conductor out of the hardware.

Confirm which one your structure needs before ordering. It is the same casting, so nobody will flag it for you.

Why two tables with identical numbers

The factory sheet carries the clamp to two standards: the 2010 specification and the 1985 specification — and every figure is the same on both, row for row. SL-1A/1B is 35–50 mm² with 4 bolts and L = 145 under either standard.

That is not a printing error and it is not a choice you have to make. It means the clamp has not changed across the two standards, so a clamp made to the 1985 sheet satisfies a 2010 specification without a drawing change. For a project that names either standard, order the same part.

The old SL-1 to SL-8 numbering

There is a second, older designation on the sheet — the 74-type range, numbered SL-1 to SL-8. This one is not organised by conductor first; it is organised by how many holes the palm carries:

  • SL-1 and SL-2 — single hole palm
  • SL-3 to SL-6 — double hole palm
  • SL-7 and SL-8 — four hole palm

The conductor ranges overlap between numbers, which is the trap: SL-3 (double hole) and SL-5 (double hole) both cover 120–150 mm² in the older listing, and the difference is the palm, not the conductor. If a customer quotes an old drawing with SL-5, do not assume it maps to SL-5A — check the palm against the table.

Technical parameters — 2010 and 1985 standard (identical)

SL aluminum equipment clamp

ModelConductor (mm²)BoltsA (mm)B (mm)L1 (mm)L (mm)
SL-1A/1B35–50440665145
SL-2A/2B70–95440680175
SL-3A/3B120–1506507125225
SL-4A/4B185–2406507125225

Technical parameters — 74-type numbering

SL aluminum equipment clamp

ModelPalmConductor (mm²)A (mm)B (mm)L1 (mm)L (mm)
SL-1single hole35–5040665120
SL-2single hole70–9540680136
SL-3double hole35–5040665145
SL-4double hole70–9540680175
SL-5double hole120–150507125225
SL-6double hole185–240507125225
SL-7four hole120–150807125240
SL-8four hole185–240807125240

Reading the columns

  • A (mm) — palm width. It is the plate that meets the equipment terminal, so it sets the footprint on a narrow pad.
  • B (mm) — plate thickness, 6 mm on the two small sizes and 7 mm on the two large ones. Not a conductor dimension.
  • L1 (mm) — clamped length over the conductor. This is the dimension that decides whether the clamp holds the conductor or sits half on it.
  • L (mm) — overall length, palm tip to clamp end.
  • Bolts — 4 on the two small bodies, 6 on the two large. The bolt count follows the clamp, not the conductor.

Bolted or compression

SL is the bolted answer. The compression answer is SY for aluminium conductor in one or two plates, and SYG where the conductor is aluminium and the terminal is copper.

SL bolted SY compressed
Tooling spanner press and die
Conductor preparation clean and grease clean, strip, insert
Joint resistance depends on bolt torque depends on die and insertion
Re-workable on site yes, unbolt and re-clamp no, cut and re-terminate
Best for jumpers, retrofits, small quantities volume work, tight resistance budgets

The bolted clamp is easier to inspect and easier to get wrong — a bolt left at half torque looks fine and is not. Torque them in a cross pattern and mark them.

Ordering

Send the model with the A or B suffix, the conductor size, and the palm hole requirement if it is not the catalogue pattern. If the drawing you are working to is the old 74-type, send the palm hole count rather than the number — the numbers overlap.

FAQ

What is the difference between SL-1A and SL-1B? The palm angle. Same conductor range, same A, B, L1 and L — one is flat and one is turned down 30° on the drawing. It is the same casting.

Why are the 2010 and 1985 tables identical? Because the clamp did not change between them. A part to either sheet meets both standards; there is no separate 1985 variant to stock.

Does SL-5 mean 120–150 mm²? In the old 74-type numbering, SL-5 is the double-hole palm for 120–150 mm². But SL-5A is not its equivalent — the A/B range only runs to four sizes. Check the palm, not the number.

Can I use SL on copper conductor? No. It is an aluminium clamp. For copper on copper use ST; for aluminium conductor onto copper equipment, use SLG or SYG with the transition built in.

Are the bolts included? Yes, with nuts and washers. State the finish if the site is coastal — the clamp is aluminium, the bolts are not.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: