PF Power Fittings Technical Reference

SLG Bolted Copper Aluminum Equipment Clamp

SLG bolted copper-aluminum equipment clamp

Models: SLG-1AQ – SLG-4AQ, repeat for BQ and CQ (12 codes) · Conductor: 35–240 mm²

This is the same brazed copper-to-aluminium clamp as the standard SLG, with two changes that matter at ordering time: the palm comes in three angles instead of two, and the model carries a Q suffix.

What the Q means

Q marks the brazed version. The transition between the aluminium body and the copper palm is a furnace brazed joint, made in the works, not a bolted interface. That is the only thing the letter tells you — it is not a size code, not a conductor code, and not a standard code.

Because it is a suffix on an otherwise familiar model, the trap is a quotation that says SLG-3A and a works order that reads SLG-3AQ. They are not the same sheet: SLG-3A is 6 mm plate on the standard sheet, SLG-3AQ is 7 mm. Write the Q.

Three palm angles: A, B, C

The A / B / C letter is the palm angle relative to the clamp body, and the drawings make it unambiguous:

Type Palm angle Drawing shows
A 0° palm straight down, parallel to the clamp body
B 30° palm turned down 30° from the body
C 90° palm turned a full right angle, landing horizontal

This is a bigger choice than it looks. On a 30° or 90° pad the palm has to meet the terminal without loading the clamp body, and bending a flat palm on site to fit is not an option — the brazed joint does not survive it. Pick the angle from the terminal, before you pick the conductor.

All three types share the same A, B, L and H for a given size, so the choice costs nothing in dimensions. It costs everything in fit.

Plate thickness: thicker than the standard sheet

Model B, standard SLG sheet B, this brazed sheet
SLG-1 5 mm 6 mm
SLG-2 5 mm 6 mm
SLG-3 6 mm 7 mm
SLG-4 6 mm 7 mm

Every size is 1 mm thicker here. On the small sizes that is 20% more section; on the large ones it is a plate that will not interchange with the standard part in a bolted assembly. If you are matching an existing installation, measure the plate before you order.

Technical parameters — Type A (0°)

SLG bolted copper-aluminum equipment clamp

ModelConductor (mm²)A (mm)B (mm)L (mm)H (mm)
SLG-1AQ35–504066565
SLG-2AQ70–954068080
SLG-3AQ120–15050712585
SLG-4AQ185–24050712585

Technical parameters — Type B (30°)

SLG bolted copper-aluminum equipment clamp

ModelConductor (mm²)A (mm)B (mm)L (mm)H (mm)
SLG-1BQ35–504066565
SLG-2BQ70–954068080
SLG-3BQ120–15050712585
SLG-4BQ185–24050712585

Technical parameters — Type C (90°)

SLG bolted copper-aluminum equipment clamp

ModelConductor (mm²)A (mm)B (mm)L (mm)H (mm)
SLG-1CQ35–504066565
SLG-2CQ70–954068080
SLG-3CQ120–15050712585
SLG-4CQ185–24050712585

Reading the columns

  • A (mm) — clamp width across the conductor.
  • B (mm) — plate thickness, 6 mm on the two small sizes and 7 mm on the two large.
  • L (mm) — clamp length over the conductor. The bolt rows cover this length; keep the strip inside it.
  • H (mm) — palm length from the transition to the tip. On the 90° type this is the dimension that decides whether the palm clears the equipment flange.
  • Bolts — not printed on this sheet. It follows the size: 4 on 1 and 2, 6 on 3 and 4.

Which of the three brazed sheets

There are three bolted SLG sheets in the catalogue and they are easy to confuse:

Sheet Codes Palm angles Plate B Extra dimensions
standard SLG SLG-xA/B, STL-x 0°, 30° 5, 6 or 6.3 L1, L2, L
this page SLG-xAQ / BQ / CQ 0°, 30°, 90° 6, 7 L, H
new brazing SLG-xA/B/C (no Q) 0°, 30°, 90° 6.0 throughout L3, L2, L1, L

The new-brazing sheet uses the same codes without the Q — SLG-1A there means 6.0 mm plate with an L2 of 34, while SLG-1A on the standard sheet means 5 mm plate with an L2 of 65. Same code, different part, and the difference is invisible unless someone measures. Quote the Q.

Ordering

Send the full code with both letters — angle and Q — plus the conductor size, stud size and palm hole pattern. If the project names a standard, name it back: this sheet does not carry a standard number, and assuming 2010 or 1985 for it is how the plate ends up 1 mm out.

FAQ

What does the Q stand for? Brazed. It marks the furnace-brazed version of the clamp, as opposed to the standard sheet’s part.

Is SLG-3AQ the same as SLG-3A? No. The Q version has 7 mm plate against 6 mm on the standard sheet. Same conductor range, different section.

Which palm angle do I need? The one that meets your terminal without stressing the brazed joint: 0° for a vertical drop onto a horizontal pad, 30° for a slight offset, 90° to land on a horizontal pad from the side. Measure the terminal, not the drawing.

Can I bend the palm on site to suit? No. It is a brazed assembly; bending it opens the joint. Order the angle you need.

Are bolts included? Clamp body is aluminium, the fasteners are hot-dip galvanised steel. They come with the clamp; state the finish for coastal sites.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: