SLG Copper Aluminum Equipment Clamp

Models: SLG-1A/1B – SLG-4A/4B (4 sizes) · Conductor: 35–240 mm² · Bolts: 4 or 6
SLG is the clamp that lets an aluminium conductor land on a copper terminal. The conductor end sits in the aluminium body, the palm that bolts to the equipment is copper, and the two metals meet inside the clamp — brazed at the factory, not bolted together on site.
That sentence is the whole reason the part exists. Bolting copper directly onto aluminium makes a galvanic couple that corrodes under the plate where you cannot see it (see ST for that failure mode). SLG moves the dissimilar-metal interface into a controlled, factory-made joint.
Which side is which
The drawing labels the two halves: Al is the clamp body that grips the conductor, Cu is the palm that goes on the equipment terminal. So:
- Aluminium conductor → copper terminal — SLG as drawn.
- Copper conductor → aluminium terminal — the same clamp turned around, if the palm bolt pattern fits. Say so on the order; the transition is symmetric but the drilling is not.
- Aluminium on aluminium — do not spend the money. SL.
- Copper on copper — ST.
Two standards, one real difference
The factory sheet carries the clamp to the 2010 and 1985 specifications. Unlike the plain aluminium SL, where the two sheets are identical, here they differ in exactly one place:
| SLG-1 / 2 (35–95 mm²) | SLG-3 / 4 (120–240 mm²) | |
|---|---|---|
| 2010 standard, plate B | 5 mm | 6 mm |
| 1985 standard, plate B | 5 mm | 6.3 mm |
That is the whole difference: 0.3 mm of plate on the two large sizes. Everything else — A, L1, L2, L, bolt count — is the same on both sheets.
Practical consequence: if a project specifies the 1985 sheet and you supply the 2010 part, you are 0.3 mm thin on the palm of the two large sizes. It will bolt up and it will probably pass, but it is a deviation and should be agreed in writing rather than discovered at inspection. Tell us which standard the project names.
The old 74-type code is STL, not SLG
The third table on the sheet switches prefix: the older designation for this clamp is STL-1 to STL-8, sorted by palm hole count — single, double, four — exactly like ST and SL.
This catches people out because the conductor ranges repeat within the numbering: STL-3 and STL-5 are both double hole, for 35–50 and 120–150 mm² respectively. A drawing that says STL-5 is not asking for an SLG-5; there is no such size. Read the palm and the conductor, not the digit.
Technical parameters — 2010 standard
| Model | Conductor (mm²) | Bolts | A (mm) | B (mm) | L1 (mm) | L2 (mm) | L (mm) |
|---|---|---|---|---|---|---|---|
| SLG-1A/1B | 35–50 | 4 | 40 | 5 | 65 | 65 | 145 |
| SLG-2A/2B | 70–95 | 4 | 40 | 5 | 80 | 80 | 175 |
| SLG-3A/3B | 120–150 | 6 | 50 | 6 | 125 | 85 | 225 |
| SLG-4A/4B | 185–240 | 6 | 50 | 6 | 125 | 85 | 225 |
Technical parameters — 1985 standard

| Model | Conductor (mm²) | Bolts | A (mm) | B (mm) | L1 (mm) | L2 (mm) | L (mm) |
|---|---|---|---|---|---|---|---|
| SLG-1A/1B | 35–50 | 4 | 40 | 5 | 65 | 65 | 145 |
| SLG-2A/2B | 70–95 | 4 | 40 | 5 | 80 | 80 | 175 |
| SLG-3A/3B | 120–150 | 6 | 50 | 6.3 | 125 | 85 | 225 |
| SLG-4A/4B | 185–240 | 6 | 50 | 6.3 | 125 | 85 | 225 |
Technical parameters — 74-type (STL)

| Model | Palm | Conductor (mm²) | A (mm) | B (mm) | L1 (mm) | L2 (mm) | L (mm) |
|---|---|---|---|---|---|---|---|
| STL-1 | single hole | 35–50 | 40 | 5 | 65 | 42 | 120 |
| STL-2 | single hole | 70–95 | 40 | 5 | 80 | 45 | 136 |
| STL-3 | double hole | 35–50 | 40 | 5 | 65 | 65 | 145 |
| STL-4 | double hole | 70–95 | 40 | 5 | 80 | 80 | 175 |
| STL-5 | double hole | 120–150 | 50 | 6 | 125 | 85 | 225 |
| STL-6 | double hole | 185–240 | 50 | 6 | 125 | 85 | 225 |
| STL-7 | four hole | 120–150 | 80 | 6 | 125 | 85 | 240 |
| STL-8 | four hole | 185–240 | 80 | 6 | 125 | 85 | 240 |
Reading the columns
- A (mm) — clamp width, across the conductor. The four-hole STL sizes are 80 mm against 40–50 mm for the rest.
- B (mm) — plate thickness at the palm. This is where the two standards differ, and where a 6.3 mm requirement meets a 6 mm part.
- L1 (mm) — clamped length over the conductor. Keep the strip length inside it.
- L2 (mm) — palm length from the transition to the hole.
- L (mm) — overall length. Note that L is not L1 + L2: there is a transition zone between the clamp body and the palm that belongs to neither.
- A / B suffix — palm orientation, not size.
Ais the flat palm,Bthe 30° version; the dimensions are shared.
A and B, again
Same story as on SL: the suffix is the palm angle, and both angles share one row of dimensions. SLG-3A and SLG-3B are one clamp with the palm either flat or turned down 30°.
Pick it from the terminal, not from the catalogue: a palm that has to reach a vertical face wants the 30° version, and a horizontal pad wants the flat one. Ordering the wrong one is not a mistake anyone catches for you — the casting is the same and the sheet looks the same.
Which of the transition clamps
| Series | How it transitions | Palm angles | Best for |
|---|---|---|---|
| SLG (this page) | brazed, in the clamp body | A / B (0° and 30°) | standard bolted work |
| SLG brazed, Q series | brazed | A / B / C (0°, 30°, 90°) | where the palm must turn a corner |
| SLG new brazing | newer brazing process | A / B / C (0°, 30°, 90°) | projects specifying 6 mm plate throughout |
| SYG | brazed, crimped barrel | A / B / C | volume work, compressed not bolted |
One warning that applies across all of them: SLG-1A appears on more than one sheet with different plate thickness. The 2010/1985 sheet gives B = 5 mm for SLG-1A/1B; the new-brazing sheet gives B = 6.0 mm for SLG-1A/1B/1C. Same code, different part. Quote the standard or the process as well as the code.
Ordering
Send the model with the A/B suffix, the conductor size, the palm hole pattern and the stud size. State the standard — 2010 or 1985 — whenever the project names one, because the large sizes differ by 0.3 mm and that is exactly the kind of deviation an inspector finds.
FAQ
What is the difference between the 2010 and 1985 sheets? Only the palm plate thickness on SLG-3 and SLG-4: 6 mm under 2010, 6.3 mm under 1985. Everything else matches.
Is STL a different clamp from SLG? It is the older designation for the same clamp, numbered by palm holes: single, double, four. Not interchangeable by digit — check the palm and the conductor range.
Can I use SLG for aluminium on aluminium? You can, but you would be paying for a copper palm you do not need. Use SL.
Why is L not L1 plus L2? Because there is a transition zone between the aluminium body and the copper palm that neither dimension covers. Use L when you need the overall envelope.
Which side goes on the conductor? The aluminium side. The copper palm is for the terminal.