SSL / SSLG Bolted Heat Resistant Twin Conductor Equipment Clamp — 0°, 45° and 90°
Conductors: NRLH58/60-630N, -1000N, -1440N · LGKK-600, -900, -1400 · Spacing: 200 / 400 mm · Plate: 150×150 · Bolts: 12 · Angle: 0°, 45° or 90°

This is the bolt-on way to terminate a twin bundle. Two clamp bodies, six bolts each, a conductor groove in each, and one plate that lands on the equipment pad. No press, no die, no crimp length. On heat-resistant conductor up to 1440 mm² a crimp needs a heavy press and a long reach; this needs two spanners.
As with the single-conductor clamp, the plate angle is the only thing that changes across the three types. Dimensions and weights are identical on every row, so the angle is a choice about the pad, never about capacity.
Four numbers in the code
SSL-630N/400A-150×150
| Part | Meaning |
|---|---|
SSL |
twin clamp, all aluminium |
SSLG |
twin clamp, aluminium body with copper plates |
630N |
the conductor, NRLH58/60-630N (or LGKK-600, or NRLH58/60-1440N) |
/400 |
the spacing between the two conductor grooves |
A |
plate at 0°, in line with the conductor |
B |
plate at 45° |
C |
plate at 90° |
(B/C) |
the same row is also made as the other two angles |
-150×150 |
the terminal plate, A × H in millimetres |
There are 24 rows because there are six conductors × two spacings (200 and 400 mm) × two materials (SSL and SSLG). Only one plate size is offered on this sheet: 150×150.
Technical parameters, all three angles
| Model | Conductor OD (mm) | Main dimensions (mm) | Reference weight (kg) | |||
|---|---|---|---|---|---|---|
| A | H | B | D * | |||
| SSL-630N/200A(B/C)-150×150 | 34.82 | 150 | 150 | 20 | 200 | 10.5 |
| SSL-1000N/200A(B/C)-150×150 | 42.08 | 150 | 150 | 24 | 200 | 11.0 |
| SSL-600K/200A(B/C)-150×150 | 51.00 | 150 | 150 | 24 | 200 | 15.2 |
| SSL-900K/200A(B/C)-150×150 | 49.00 | 150 | 150 | 24 | 200 | 16.1 |
| SSL-1400/200A(B/C)-150×150 | 51.00 | 150 | 150 | 24 | 200 | 14.0 |
| SSL-1440N/200A(B/C)-150×150 | 51.36 | 150 | 150 | 24 | 200 | 14.0 |
| SSL-630N/400A(B/C)-150×150 | 34.82 | 150 | 150 | 20 | 400 | 11.4 |
| SSL-1000N/400A(B/C)-150×150 | 42.08 | 150 | 150 | 24 | 400 | 12.9 |
| SSL-600K/400A(B/C)-150×150 | 51.00 | 150 | 150 | 24 | 400 | 18.2 |
| SSL-900K/400A(B/C)-150×150 | 49.00 | 150 | 150 | 24 | 400 | 17.1 |
| SSL-1400/400A(B/C)-150×150 | 51.00 | 150 | 150 | 24 | 400 | 14.9 |
| SSL-1440N/400A(B/C)-150×150 | 51.36 | 150 | 150 | 24 | 400 | 14.9 |
| SSLG-630N/200A(B/C)-150×150 | 34.82 | 150 | 150 | 20 | 200 | 10.9 |
| SSLG-1000N/200A(B/C)-150×150 | 42.08 | 150 | 150 | 24 | 200 | 11.4 |
| SSLG-600K/200A(B/C)-150×150 | 51.00 | 150 | 150 | 24 | 200 | 15.6 |
| SSLG-900K/200A(B/C)-150×150 | 49.00 | 150 | 150 | 24 | 200 | 16.5 |
| SSLG-1400/200A(B/C)-150×150 | 51.00 | 150 | 150 | 24 | 200 | 14.4 |
| SSLG-1440N/200A(B/C)-150×150 | 51.36 | 150 | 150 | 24 | 200 | 14.4 |
| SSLG-630N/400A(B/C)-150×150 | 34.82 | 150 | 150 | 20 | 400 | 11.8 |
| SSLG-1000N/400A(B/C)-150×150 | 42.08 | 150 | 150 | 24 | 400 | 13.3 |
| SSLG-600K/400A(B/C)-150×150 | 51.00 | 150 | 150 | 24 | 400 | 18.6 |
| SSLG-900K/400A(B/C)-150×150 | 49.00 | 150 | 150 | 24 | 400 | 17.4 |
| SSLG-1400/400A(B/C)-150×150 | 51.00 | 150 | 150 | 24 | 400 | 15.3 |
| SSLG-1440N/400A(B/C)-150×150 | 51.36 | 150 | 150 | 24 | 400 | 15.3 |
* The column printed as D on the factory sheet is the spacing; see below. All dimensions in millimetres.
Conductors covered: NRLH58/60-630N, -1000N, -1440N and LGKK-600, LGKK-900, LGKK-1400. These are heat-resistant alloy and expanded hollow conductor, not ACSR — the OD column is printed so the groove can be checked against the actual cable, and the batch runs from 34.82 mm to 51.36 mm.
One column heading to be careful with
The factory sheet prints the fourth dimension column as D. On this twin sheet its values are 200 and 400 — exactly the /200 and /400 in the model code. It is the spacing between the two clamp bodies, not a groove diameter.
The drawing calls the same measurement L, which is the clearer name for it. Compare the single-conductor SL/SLG sheet, where D really is the groove: the two sheets use the same column letter for two different things. In practice the model code settles it, but do not size a twin clamp from the D column thinking it is a groove.
SSL and SSLG
- SSL — all aluminium, body and plates.
- SSLG — aluminium body, copper plates, brazed.
The two are dimensionally identical at every row. SSLG is 0.3 to 0.4 kg heavier across the sheet, which is the copper and nothing else. Use SSLG when the equipment terminal is copper; an aluminium plate on a copper pad corrodes out of sight and runs hot two years later.
Which angle
- 0° (A) — plate in line with the conductor. The default.
- 45° (B) — the pad faces at an angle to the run, or the 0° plate would foul something behind it.
- 90° (C) — the conductor runs past the equipment face rather than toward it.
Do not force an angle onto a pad that is not at that angle. A turned plate bolted to a square pad touches along one edge only, and with two independent bodies the misload shows up as a plate that rocks on the pad. The angle is set at the factory; on SSLG the copper plates are brazed on and cold bending cracks the fillet.
Reading the drawing
- A (mm) — plate width, 150 on every row.
- H (mm) — plate length, the free face on the equipment pad, 150 on every row.
- B (mm) — thickness across the closed clamp, 20 or 24 mm.
- L (mm) — spacing between the two bodies, 200 or 400. Printed as D in the table.
Twelve bolts, six on each body in three rows of two. No press and no die: this clamp is fitted with spanners, which is why it is used on heat-resistant conductor up to 1440 mm² where a crimp would need a heavy press.
Fitting it
- Both grooves, same bolt pattern. Torque the two bodies in the same order, or the pair sits at different heights and the plate rocks on the pad.
- Cross-pattern torque, not perimeter. Three rows of two: pull the top pair, then the bottom, then the middle — never one side all the way down.
- Grease the conductor. On NRLH and on LGKK the oxide film is the contact resistance; jointing compound under the plates is what keeps the joint cool.
- Keep the plate flat. The two bodies are independent, so a plate that is bolted down on one side first will bow and touch the pad only along one edge.
- Groove is 0 to 0.9 mm over the conductor OD by design, so the plates close onto the conductor instead of bottoming on each other.
- On the 45° and 90° types the plate sits off the run. Support the cable so the plate is not carrying the conductor weight into the pad.
The family
- SSL/SSLG bolted, A/B/C — this page. Plate at 0°, 45° or 90°, twelve bolts, no crimp.
- SL/SLG — the single-conductor bolted clamp, same three angles.
- SSY-N — the compression twin, also A/B/C.
- SSY — standard conductor, compression twin.
Note: Quote the conductor, the spacing, the material and the angle — all four are in the code, e.g. SSLG-1000N/400C-150×150.