PF Power Fittings Technical Reference

SL / SLG Bolted Heat Resistant Single Conductor Equipment Clamp — 0°, 45° and 90°

Conductors: NRLH58/60-630N, -1000N, -1440N · LGKK-600, -900, -1400 · Plate: 125×125 or 150×150 · Bolts: 6 · Angle: 0°, 45° or 90°

SL SLG bolted heat resistant equipment clamp, 0 degree, drawing SL and SLG bolted clamp with 45 degree plate, both versions drawn side by side SL SLG bolted heat resistant clamp, 90 degree, side view

This is the bolt-on alternative to a compression equipment clamp: two plates, six bolts, the conductor laid in a groove between them. No press, no die, no crimp length to get wrong. On heat-resistant conductor up to 1440 mm², where a press is heavy and slow, that is often the deciding argument.

The plate angle is the only thing that changes across the three types — 0° in line with the conductor, 45° turned off it, 90° square to it. Dimensions and weights are the same on every row of all three, so the angle is a choice about the pad, never about capacity.

The code

SL-630NA-125×125 is: SL all aluminium, 630N the conductor (NRLH58/60-630), A the 0° plate, and 125×125 the plate size, A × H in millimetres.

Part of the code Meaning
SL all aluminium, body and plate
SLG aluminium body, copper plate brazed on
630N / 600K / 1400 the conductor — NRLH58/60 or LGKK
A plate at 0°, in line with the conductor
B plate at 45°
C plate at 90°, square to the conductor
(B/C) the same row is also made as the other two angles
-125×125 the terminal plate, A × H in millimetres

Every conductor on this sheet comes in both plate sizes — 125×125 and 150×150 — and both metals. So there are 24 rows for six conductors. The trailing pair is the part people drop, and it is the part that decides whether the plate covers the pad: 125×125 and 150×150 are the only two on the sheet, and if neither covers your pad the plate has to be made, so say so at enquiry.

Conductors covered: NRLH58/60-630N, -1000N, -1440N and LGKK-600, LGKK-900, LGKK-1400. These are heat-resistant alloy and expanded hollow conductor — not ACSR. The OD column is given so the groove can be checked against the actual cable.

Technical parameters, all three angles

ModelConductor OD (mm)Main dimensions (mm)Reference weight (kg)
AHBD
SL-630NA(B/C)-125×12534.8212512520355.7
SL-630NA(B/C)-150×15034.8215015020356.2
SL-1000NA(B/C)-125×12542.0812512520436.5
SL-1000NA(B/C)-150×15042.0815015024437.0
SL-600KA(B/C)-125×12551.0012512522519.1
SL-600KA(B/C)-150×15051.0015015024519.6
SL-900KA(B/C)-125×12549.0012512520498.1
SL-900KA(B/C)-150×15049.0015015024498.6
SL-1400A(B/C)-125×12551.0012512522517.5
SL-1400A(B/C)-150×15051.0015015024518.0
SL-1440NA(B/C)-125×12551.3612512522528.7
SL-1440NA(B/C)-150×15051.3615015024529.2
SLG-630NA(B/C)-125×12534.8212512520356.0
SLG-630NA(B/C)-150×15034.8215015020356.6
SLG-1000NA(B/C)-125×12542.0812512520436.8
SLG-1000NA(B/C)-150×15042.0815015024437.4
SLG-600KA(B/C)-125×12551.0012512522519.4
SLG-600KA(B/C)-150×15051.00150150245110.0
SLG-900KA(B/C)-125×12549.0012512520498.4
SLG-900KA(B/C)-150×15049.0015015024499.0
SLG-1400A(B/C)-125×12551.0012512522517.8
SLG-1400A(B/C)-150×15051.0015015024518.4
SLG-1440NA(B/C)-125×12551.3612512522529.0
SLG-1440NA(B/C)-150×15051.3615015024529.6

All dimensions in millimetres. The 24 rows are six conductors × two plate sizes × two materials. B and C are the same row as A with the plate turned — no dimension is repeated per angle because none of them changes.

SL and SLG: the same clamp, one plate different

The 45° drawing prints both versions side by side and labels the SLG one Al on the body and Cu on the plate. That is the whole difference:

  • SL — all aluminium, body and plate.
  • SLG — aluminium body, copper plate, brazed on.

Measured against the sheet, SLG is dimensionally identical to SL at every row. It is 0.3 kg heavier on the 125×125 plate and 0.4 kg on the 150×150 — that is the cost of the copper, and it is the only number that moves.

Pick SLG when the equipment terminal is copper. An aluminium plate bolted to a copper pad is the joint that corrodes invisibly and then runs hot.

Which angle

  • 0° (A) — plate in line with the conductor. The default: use it whenever the pad faces along the run.
  • 45° (B) — the pad faces at an angle to the run, the 0° plate would foul something behind it, or you are replacing an existing 45° fitting. A 45° turn buys clearance without a longer conductor tail.
  • 90° (C) — the conductor runs past the equipment face rather than toward it. Common on busbar supports and on equipment whose terminal is on the side of the box.

Two rules that apply to all three:

  • Do not force an angle onto a pad that is not at that angle. A 45° or 90° clamp bolted to a square pad contacts only along its leading edge and loads the bolts unevenly.
  • The angle is set at the factory. Do not straighten or re-bend a plate to make it fit: the plate is 20 to 24 mm thick across the clamped pair and will not take a cold bend, and on SLG the copper plate is brazed to an aluminium body — cold bending cracks the fillet.

Reading the drawing

  • A (mm) — plate width, 125 or 150.
  • H (mm) — plate length, the free face that lands on the equipment pad. Also 125 or 150. On the 45° and 90° types H is still measured along the plate from the bend to the end, so the 125 and 150 options mean the same thing as on the 0°.
  • B (mm) — thickness across the closed clamp, 20 to 24 mm, both plates and the conductor between them.
  • D (mm) — the conductor groove, 35 to 52 mm.

The Φ at the top of the side view is the groove, not a bolt hole. This clamp has six bolts in three rows of two and no crimp, so there is no die to select — D only has to match the conductor.

That is the whole point of the SL series: no press, no die, no crimp length. A lineman with two spanners can fit it, which is why it is used where the work is done live or where a press cannot reach.

Fitting it

  • Grease the conductor, not the bolt threads. On aluminium and on LGKK the oxide film is the contact resistance; a jointing compound under the plates is what keeps it down.
  • Six bolts, and torque them in a cross pattern — top left, bottom right, and so on — not round the perimeter. Bolting one side down first tilts the plate and the groove closes on one edge of the conductor.
  • Check the gap closes evenly. A clamp with a visible wedge-shaped gap was not seated; slack it off and start again rather than adding torque.
  • D is generous by design. It runs 0 to 0.9 mm over the conductor OD, so the plates close onto the conductor rather than bottoming out on each other. Do not substitute a clamp whose groove matches the cable exactly — it will bottom before it grips.
  • On the 90° type the plate is a lever. At 0° the conductor pulls along the plate; at 90° it pulls across it. Support the cable so the plate is not carrying the conductor weight into the pad.

The family in one line each

  • SL/SLG bolted, A/B/C — this page. Plate at 0°, 45° or 90°, six bolts, no crimp.
  • SSL/SSLG — the twin-bundle version, twelve bolts, spacing 200 or 400 mm.
  • SY(G)-N — the compression equivalent, plate also at 0°, 30° or 90°.
  • SSY-N — compression twin bundle, heat-resistant.

Note: Quote the conductor, the material (SL aluminium or SLG copper plate), the angle letter and the plate size. All four are in the code: SLG-1000NB-150×150.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: