SC Copper Tube Compression Terminal(Cable Lug)

DTG Copper Tube Compression Terminal

Models: SC-4 – SC-800 (18 sizes)

The SC terminal is a plain copper tube with a flat palm at one end: strip the cable, push it into the barrel, and crimp with a hexagonal die. There is no screw, no spring and nothing to re-tighten, which is why it is the default termination for copper cable from 4 mm² control cores up to 800 mm² feeder cable.

It is a copper lug. On an aluminium conductor the copper barrel and the aluminium conductor form a galvanic cell at the joint; use a DTL copper-aluminium transition terminal for that.

The column that decides whether it fits

Look at d first — it is the bore of the barrel, and it has to match the actual outside diameter of the stranded conductor, not its nominal square millimetre figure.

For ordinary Class 2 stranded copper the two track closely: 240 mm² sits around 20 mm across, and the SC-240 bore is 21 mm. But for flexible Class 5 and Class 6 cable the strands are finer and the same 240 mm² is noticeably fatter, so the bore that fits a rigid conductor can be too tight for a flexible one. If you are terminating flexible cable, go up one size or tell us the conductor class when ordering — this is the single most common fitting error on cable lugs, and it is invisible until the crimp collapses the strands.

Reading the dimension table

  • d (mm) — barrel bore. Match to the measured conductor diameter.
  • D (mm) — barrel outside diameter. This is what selects the crimping die; the die is marked with the same size code as the lug.
  • L1 (mm) — barrel depth, i.e. the length of the compression zone. It also sets the strip length: strip to L1 so the insulation finishes right at the barrel mouth.
  • L (mm) — overall length from the palm end to the barrel mouth, for clearance inside the terminal box.
  • Ø (mm) — palm hole, to suit the stud on the equipment terminal.

The palm hole, not the barrel, is what gets customised

Almost every enquiry on a cable lug is about the palm hole, not the barrel. Switchgear, breakers and busbars are drilled for whatever stud their maker chose, and it is rarely the catalogue default. The hole is the part that gets changed; the barrel is not.

What can be changed

  • Hole diameter — drilled to your stud. The catalogue follows the common stud series: Ø 6.2 for M6, 8.2 for M8, 10.5 for M10, 12.5 for M12, 16.5 for M16, 20.5 for M20, 22.5 for M22. Each is a running clearance above the stud rather than the stud size itself, so a 10.5 mm hole takes an M10 bolt with its plating and thermal expansion accounted for.
  • Hole count and spacing — one hole, a two-hole NEMA pattern or a four-hole pad, and a pair can be turned 90° on the palm.
  • Palm length — a longer palm where the terminal box is deep and the stud sits far from the cable entry.

What cannot be changed is d. The bore is chosen from the conductor, not from the equipment. Open it up to clear a bigger stud and the crimp loses the interference it needs.

The limit is the metal left around the hole. Under bolt preload the palm is pulled onto the equipment face. If the strip between hole and palm edge is too thin it deforms or tears out, and the joint goes loose no matter how hard you torque it afterwards. The working rule — engineering practice, not a clause in GB/T 14315 — is that the edge distance on each side should be at least half the hole diameter. On a palm of width W with a centred hole, that puts the practical ceiling near half of W.

Which is why a small lug has almost no room and a large one has plenty. The SC table does not list the palm width, so if your stud is bigger than the catalogue hole, send the model and the stud size and we will tell you what that palm can take before you commit. Do not assume it can be opened up.

Two levels of change, two different costs

  • Drilling a different hole in the same palm changes the drill, not the die: short lead time, no minimum worth mentioning.
  • Changing the palm itself — its width, the number of holes, a square-head or offset pattern — means re-cutting the forming die, so it carries a minimum quantity and a longer lead time.

Send with the enquiry: stud size (M10) or hole diameter (10.5), number of holes and their spacing where there is more than one, the direction the palm points relative to the barrel, and the quantity. One drawing of the equipment terminal settles all four at once.

Choosing the model

  • SC-4 to SC-25 (4–25 mm²) — control and instrumentation cores, small motor leads.
  • SC-35 to SC-95 (35–95 mm²) — distribution cable, panel and switchgear terminations.
  • SC-120 to SC-300 (120–300 mm²) — feeder cable in LV distribution and transformer connections.
  • SC-400 to SC-800 (400–800 mm²) — heavy cable where the lug is often the mechanical support as well as the electrical termination.

Standards

The lug is made to GB/T 14315-2008 — the Chinese standard for compression-type terminal lugs and ferrules for power cable conductors, covering 35 kV and below, copper conductors 10–630 mm² and aluminium 16–630 mm². That standard calls up GB/T 9327-2008 for the electrical, mechanical and thermal-cycle test methods, and its international counterpart is IEC 61238-1, which covers the same tests for compression and mechanical connectors.

What is actually tested, and what each test is for:

  • DC resistance — across the finished joint, no more than an equal length of conductor. This is the pass/fail number.
  • Temperature rise — the joint must not run hotter than the conductor at rated current.
  • Thermal cycling — resistance has to stay within limits after repeated heating and cooling. A crimp that was marginal when cold drifts above the limit here, which is why a joint that passes on the bench can still fail in service.
  • Mechanical — pull-out and, for the larger sizes, short-circuit withstand.

Installation

  1. Strip to L1, not longer. Bare conductor showing outside the barrel is a corrosion site and a hot spot, and it is the most common visible defect on a finished joint.
  2. Clean the conductor and, if the cable is paper-insulated or the joint will be exposed, apply contact paste before insertion.
  3. Insert fully — the conductor must reach the bottom of the barrel, which you can confirm through the inspection hole where the lug has one.
  4. Crimp with the correct hexagonal die, in stages along the barrel. As a rule of thumb, allow one crimp per 15–20 mm of barrel length, with each crimp overlapping the previous by about a third. Start at the palm end and work outward, so that the conductor is not pushed back out of the barrel as you compress. The figure that matters is L1 from the table: SC-95 with a 23.5 mm barrel takes one to two crimps, SC-800 with 64 mm takes four.
  5. Check the die closure — the finished crimp should be a regular hexagon with the die faces meeting, not a rounded oval. An oval means the wrong die or an under-stroke of the tool.
  6. Seal and insulate — heat-shrink or tape over the barrel mouth on outdoor and buried joints. Water wicking down a stranded conductor into the barrel is what turns a good crimp into a green joint two years later.

Where these joints fail

  • Wrong die. Either an oval crimp that never develops full contact, or over-compression that splits the barrel. Both look plausible on the bench.
  • Stripping too long. Bare conductor outside the barrel corrodes and runs hot.
  • Conductor not fully home. The crimp then holds only part of the strand bundle, and the pull-out strength collapses.
  • A copper lug on an aluminium conductor. Galvanic corrosion at the interface — the exact job the DTL transition terminal exists for.
  • Wicking moisture. No seal, stranded conductor, outdoor joint: the barrel fills with water by capillary action over a season.

FAQ

Can SC lugs be used on aluminium cable? No. Use a copper-aluminium transition terminal, or an aluminium lug with a bimetallic barrier, depending on what the equipment terminal is made of.

How many crimps does one lug need? Follow the barrel depth: roughly one hexagonal crimp per 15–20 mm of L1, overlapping by a third. On the small sizes one crimp is correct; do not add more, it only work-hardens the barrel.

What is the difference between SC and DT? Both are copper compression lugs. The DT/DTG series differs in palm and barrel proportions rather than in principle; either is correct for copper cable, and the choice usually comes down to the terminal box clearance and the die set you already carry.

Is tin plating available? Yes. It is worth specifying for outdoor, coastal and humid locations, and for joints landing on a different metal.

Can the palm hole be drilled to my stud size? Usually, within what the palm can carry — see the palm hole above. The limit is the metal left between hole and palm edge, and it is tight on the small sizes.

Technical Parameters

DTG Copper Tube Compression TerminalDTG Copper Tube Compression Terminal

Model Main Dimensions (mm)
Ø D d L L1
SC-46.24.83.121.06.4
SC-66.25.53.824.09.0
SC-106.26.84.825.510.0
SC-168.27.56.530.512.0
SC-258.29.07.034.014.0
SC-3510.510.58.238.014.0
SC-5010.512.59.845.018.0
SC-7012.514.511.550.018.6
SC-9512.517.513.855.523.5
SC-12012.519.515.563.024.0
SC-15016.520.516.571.026.0
SC-18516.523.518.878.033.0
SC-24016.526.521.092.037.0
SC-30016.530.024.0102.039.5
SC-40016.534.026.5113.046.0
SC-50020.538.030.0123.050.0
SC-63020.545.035.0135.058.0
SC-80022.550.039.0170.064.0

Note: Dimensions may vary slightly with manufacturing tolerance. Hole diameter, hole count and palm length can be made to suit your equipment terminal; the palm width is not listed above, so ask before assuming a larger stud will fit.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: