PF Power Fittings Technical Reference

SSY-N Heat Resistant Twin Conductor Equipment Clamp — A, B and C Types

Conductors: NRLH58/60-240 to -1440 · LGKK-900, -1400 · Spacing: 120 / 200 / 400 mm · Plate: 0°, 30° or 90°

SSY-N heat resistant twin conductor clamp, type A SSY-N heat resistant twin conductor clamp, type B

SSY-N is the twin-bundle clamp for heat-resistant conductor: two bodies, each gripping one sub-conductor, joined to a single plate that lands on the equipment pad. It is the conductor-side twin of the bolted SL/SLG clamp, and the heat-resistant twin of the standard SSY.

The code, and the note that settles the letters

SSY-500/65NA(B/C)-200

Part Meaning
SSY / SSYG twin clamp, all aluminium / with brazed copper plates
500/65 the conductor, NRLH58/60-500/65
N heat-resistant series
A plate angle — and the sheet says so in words
(B/C) the same row is also made as B and as C
-200 spacing between the two conductor grooves

The factory note on both sheets reads: “additional letters: A indicates horizontal (0°), B indicates 30°, C indicates 90°, e.g. for a 30° 500/65 heat-resistant conductor the model is SSY-500/65NB.” That is the authoritative statement of the angles and it matches the drawings.

B and C are not separate tables. Every row prints A(B/C), because all three angles share the same dimensions — only the plate is turned. So one table covers all three.

Technical parameters, all three angles

ModelConductorMain dimensions (mm)
AHBLD
SSY-240/30-40NA(B/C)-120NRLH58/60-240/30~401251301812045
SSY-240/30-40NA(B/C)-200NRLH58/60-240/30~401251301820045
SSY-240/30-40NA(B/C)-400NRLH58/60-240/30~401251301840045
SSY-300/25-40NA(B/C)-120NRLH58/60-300/25~401251302012050
SSY-300/25-40NA(B/C)-200NRLH58/60-300/25~401251302020050
SSY-300/25-40NA(B/C)-400NRLH58/60-300/25~401251302040050
SSY-400/20-35NA(B/C)-120NRLH58/60-400/20~351251302012055
SSY-400/20-35NA(B/C)-200NRLH58/60-400/20~351251302020055
SSY-400/20-35NA(B/C)-400NRLH58/60-400/20~351251302040055
SSY-400/50-65NA(B/C)-120NRLH58/60-400/50~651251302012055
SSY-400/50-65NA(B/C)-200NRLH58/60-400/50~651251302020055
SSY-400/50-65NA(B/C)-400NRLH58/60-400/50~651251302040055
SSY-500/35-45NA(B/C)-120NRLH58/60-500/35~451501552212065
SSY-500/35-45NA(B/C)-200NRLH58/60-500/35~451501552220065
SSY-500/35-45NA(B/C)-400NRLH58/60-500/35~451501552240065
SSY-500/65NA(B/C)-120NRLH58/60-500/651501552212065
SSY-500/65NA(B/C)-200NRLH58/60-500/651501552220065
SSY-500/65NA(B/C)-400NRLH58/60-500/651501552240065
SSY-630/45-55NA(B/C)-200NRLH58/60-630/45~551501552220070
SSY-630/45-55NA(B/C)-400NRLH58/60-630/45~551501552240070
SSY-800/55-100NA(B/C)-200NRLH58/60-800/55~1001501552220070
SSY-800/55-100NA(B/C)-400NRLH58/60-800/55~1001501552240070
SSY-1000/125NA(B/C)-200NRLH58/60-1000/1251501552420076
SSY-1000/125NA(B/C)-400NRLH58/60-1000/1251501552440076
SSY-1440/120NA(B/C)-200NRLH58/60-1440/1201501552420080
SSY-1440/120NA(B/C)-400NRLH58/60-1440/1201501552440080
SSY-900KA(B/C)-200LGKK-9001251302020074
SSY-900KA(B/C)-400LGKK-9001251302040074
SSY-1400KA(B/C)-200LGKK-14001251302220084
SSY-1400KA(B/C)-400LGKK-14001251302240084

All dimensions in millimetres.

Reading the table

  • A (mm) — plate width, 125 or 150.
  • H (mm) — plate length, 130 or 155. Note that A and H are not equal on this sheet: the plate is 125 × 130 or 150 × 155, not square as on the bolted single-conductor clamp.
  • B (mm) — thickness across the closed clamp, 18 to 24 mm.
  • L (mm) — spacing between the two grooves, 120, 200 or 400.
  • D (mm) — the conductor groove, 45 to 84 mm. Here D really is the groove; do not confuse it with the bolted twin sheet where the same letter is used for the spacing.

There is no weight column on either sheet. Weighing is done at the works for the sizes we ship: the weight goes on the packing list with the delivery, and we will send it ahead of time if you are costing freight.

120 mm is not available above 500 mm²

The three spacings are not offered evenly across the range:

Conductor 120 200 400
240/3040, 300/2540, 400/2035, 400/5065, 500/35~45, 500/65 yes yes yes
630/4555, 800/55100, 1000/125, 1440/120 — yes yes
LGKK-900, LGKK-1400 — yes yes

So 120 mm stops at 500 mm²; from 630 up there are only 200 and 400. If a drawing calls for 120 on a 630 twin, the frame has to be made — that is a note at enquiry, not an off-the-shelf part.

That gives 30 rows: six conductors at three spacings plus six at two.

The 1440 Pair And Its Two Codes

The LGKK and 1400 rows close the table with a code and a dimension that have to be read together: SSY-1400KA(B/C)-200 is the 200 mm spacing and SSY-1400KA(B/C)-400 the 400 mm one, and the L column on each row carries that number. Order by the trailing figure and the spacing follows.

Every other row of both sheets reads the same way: the L column and the trailing number agree.

Fitting a twin

  • Crimp or bolt before the bundle is tensioned. The yoke is a terminal, not a spacer, and it will not take conductor tension.
  • Both barrels identical. Two different crimp depths on the same twin is the classic cause of current imbalance between sub-conductors; it shows up in a thermal survey, not in a continuity test.
  • Keep the plate flat. Two barrels swaged in sequence pull the yoke one way then the other.
  • The plate is made to order if it needs to be. The note on the SSYG sheet: “if A and L2 change, the user should specify L2 × A when ordering, e.g. SSYG-500/65NA(L2×A).”

The rest of the family

  • SSYG-N — the same clamp with brazed copper plates, dimensionally identical.
  • SSY — the compression twin for standard ACSR.
  • SSL/SSLG — the bolted twin, where no press is available.
  • SY/SYG-N — the single-conductor heat-resistant clamp.

Note: Quote the conductor, the spacing and the angle — SSY-500/65NB-200 is a 30° clamp at 200 mm spacing. Send L2 × A if the plate is not the catalogue 125×130 or 150×155.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: