SSYG-N Brazed Heat Resistant Twin Conductor Equipment Clamp
Conductors: NRLH58/60-240 to -1440 · LGKK-900, -1400 · Spacing: 120 / 200 / 400 mm · Plate: 0°, 30° or 90°

SSYG-N is the twin-bundle heat-resistant clamp with copper plates brazed onto aluminium bodies. The bodies grip the conductor and stay aluminium; the plates land on the equipment terminal and are copper. That is the whole reason the G exists.
The factory sheet says the process is brazed — not the flash welding used on the single-conductor SYG. On a twin the plate is a separate piece on each side, and brazing is how it is attached.
The code, and the note that settles the letters
SSY-500/65NA(B/C)-200
| Part | Meaning |
|---|---|
SSY / SSYG |
twin clamp, all aluminium / with brazed copper plates |
500/65 |
the conductor, NRLH58/60-500/65 |
N |
heat-resistant series |
A |
plate angle — and the sheet says so in words |
(B/C) |
the same row is also made as B and as C |
-200 |
spacing between the two conductor grooves |
The factory note on both sheets reads: “additional letters: A indicates horizontal (0°), B indicates 30°, C indicates 90°, e.g. for a 30° 500/65 heat-resistant conductor the model is SSY-500/65NB.” That is the authoritative statement of the angles and it matches the drawings.
B and C are not separate tables. Every row prints A(B/C), because all three angles share the same dimensions — only the plate is turned. So one table covers all three.
Technical parameters, all three angles
| Model | Conductor | Main dimensions (mm) | ||||
|---|---|---|---|---|---|---|
| A | H | B | L | D | ||
| SSYG-240/30-40NA(B/C)-120 | NRLH58/60-240/30~40 | 125 | 130 | 18 | 120 | 45 |
| SSYG-240/30-40NA(B/C)-200 | NRLH58/60-240/30~40 | 125 | 130 | 18 | 200 | 45 |
| SSYG-240/30-40NA(B/C)-400 | NRLH58/60-240/30~40 | 125 | 130 | 18 | 400 | 45 |
| SSYG-300/25-40NA(B/C)-120 | NRLH58/60-300/25~40 | 125 | 130 | 20 | 120 | 50 |
| SSYG-300/25-40NA(B/C)-200 | NRLH58/60-300/25~40 | 125 | 130 | 20 | 200 | 50 |
| SSYG-300/25-40NA(B/C)-400 | NRLH58/60-300/25~40 | 125 | 130 | 20 | 400 | 50 |
| SSYG-400/20-35NA(B/C)-120 | NRLH58/60-400/20~35 | 125 | 130 | 20 | 120 | 55 |
| SSYG-400/20-35NA(B/C)-200 | NRLH58/60-400/20~35 | 125 | 130 | 20 | 200 | 55 |
| SSYG-400/20-35NA(B/C)-400 | NRLH58/60-400/20~35 | 125 | 130 | 20 | 400 | 55 |
| SSYG-400/50-65NA(B/C)-120 | NRLH58/60-400/50~65 | 125 | 130 | 20 | 120 | 55 |
| SSYG-400/50-65NA(B/C)-200 | NRLH58/60-400/50~65 | 125 | 130 | 20 | 200 | 55 |
| SSYG-400/50-65NA(B/C)-400 | NRLH58/60-400/50~65 | 125 | 130 | 20 | 400 | 55 |
| SSYG-500/35-45NA(B/C)-120 | NRLH58/60-500/35~45 | 150 | 155 | 22 | 120 | 65 |
| SSYG-500/35-45NA(B/C)-200 | NRLH58/60-500/35~45 | 150 | 155 | 22 | 200 | 65 |
| SSYG-500/35-45NA(B/C)-400 | NRLH58/60-500/35~45 | 150 | 155 | 22 | 400 | 65 |
| SSYG-500/65NA(B/C)-120 | NRLH58/60-500/65 | 150 | 155 | 22 | 120 | 65 |
| SSYG-500/65NA(B/C)-200 | NRLH58/60-500/65 | 150 | 155 | 22 | 200 | 65 |
| SSYG-500/65NA(B/C)-400 | NRLH58/60-500/65 | 150 | 155 | 22 | 400 | 65 |
| SSYG-630/45-55NA(B/C)-200 | NRLH58/60-630/45~55 | 150 | 155 | 22 | 200 | 70 |
| SSYG-630/45-55NA(B/C)-400 | NRLH58/60-630/45~55 | 150 | 155 | 22 | 400 | 70 |
| SSYG-800/55-100NA(B/C)-200 | NRLH58/60-800/55~100 | 150 | 155 | 22 | 200 | 70 |
| SSYG-800/55-100NA(B/C)-400 | NRLH58/60-800/55~100 | 150 | 155 | 22 | 400 | 70 |
| SSYG-1000/125NA(B/C)-200 | NRLH58/60-1000/125 | 150 | 155 | 24 | 200 | 76 |
| SSYG-1000/125NA(B/C)-400 | NRLH58/60-1000/125 | 150 | 155 | 24 | 400 | 76 |
| SSYG-1440/120NA(B/C)-200 | NRLH58/60-1440/120 | 150 | 155 | 24 | 200 | 80 |
| SSYG-1440/120NA(B/C)-400 | NRLH58/60-1440/120 | 150 | 155 | 24 | 400 | 80 |
| SSYG-900KA(B/C)-200 | LGKK-900 | 125 | 130 | 20 | 200 | 74 |
| SSYG-900KA(B/C)-400 | LGKK-900 | 125 | 130 | 20 | 400 | 74 |
| SSYG-1400KA(B/C)-200 | LGKK-1400 | 125 | 130 | 22 | 200 | 84 |
| SSYG-1400KA(B/C)-400 | LGKK-1400 | 125 | 130 | 22 | 400 | 84 |
All dimensions in millimetres. Thirty rows, and every one matches the SSY-N sheet line for line — see below.
Reading the table
- A (mm) — plate width, 125 or 150.
- H (mm) — plate length, 130 or 155. Note that A and H are not equal on this sheet: the plate is 125 × 130 or 150 × 155, not square as on the bolted single-conductor clamp.
- B (mm) — thickness across the closed clamp, 18 to 24 mm.
- L (mm) — spacing between the two grooves, 120, 200 or 400.
- D (mm) — the conductor groove, 45 to 84 mm. Here D really is the groove; do not confuse it with the bolted twin sheet where the same letter is used for the spacing.
There is no weight column on either sheet. If you need a weight for freight, ask and we will weigh a sample rather than quote a number the catalogue does not publish.
Dimensionally identical to SSY-N
Checked row by row against both factory sheets: A, H, B, L and D are the same on all thirty rows. The only difference between an SSY-N and an SSYG-N of the same code is the metal in the plate.
So on a retrofit the SSYG-N goes onto the same bolt holes at the same spacing, with the same plate footprint. The substitution is safe on dimensions; it is only safe in the right direction if the terminal is copper. Putting a copper plate on an aluminium pad gains nothing and costs the copper.
120 mm is not available above 500 mm²
The three spacings are not offered evenly across the range:
| Conductor | 120 | 200 | 400 |
|---|---|---|---|
| 240/30 |
yes | yes | yes |
| 630/45 |
— | yes | yes |
| LGKK-900, LGKK-1400 | — | yes | yes |
So 120 mm stops at 500 mm²; from 630 up there are only 200 and 400. If a drawing calls for 120 on a 630 twin, the frame has to be made — that is a note at enquiry, not an off-the-shelf part.
That gives 30 rows: six conductors at three spacings plus six at two.
The brazed plate
- Do not heat it. A site torch on the plate will undo a braze long before anything looks hot.
- Do not bend the plate to fit. A braze is a lap-type joint and does not take plastic strain; a plate bent cold cracks along the fillet.
- Check the fillet. A sound braze is an even collar all the way round. A lumpy or gashed one was made cold.
- The plate is made to order if needed — the sheet’s own note: “if A and L2 change, specify L2 × A when ordering, e.g. SSYG-500/65NA(L2×A).”
The 1440 Pair And Its Two Codes
The 1400 rows close the table with a code and a dimension that have to be read together: SSYG-1400KA(B/C)-200 is the 200 mm spacing and SSYG-1400KA(B/C)-400 the 400 mm one, and the L column on each row carries that number. Order by the trailing figure and the spacing follows.
Every other row of both sheets reads the same way: the L column and the trailing number agree.
Fitting a twin
- Crimp or bolt before the bundle is tensioned. The yoke is a terminal, not a spacer, and it will not take conductor tension.
- Both barrels identical. Two different crimp depths on the same twin is the classic cause of current imbalance between sub-conductors; it shows up in a thermal survey, not in a continuity test.
- Keep the plate flat. Two barrels swaged in sequence pull the yoke one way then the other.
- The plate is made to order if it needs to be. The note on the SSYG sheet: “if A and L2 change, the user should specify L2 × A when ordering, e.g. SSYG-500/65NA(L2×A).”
The rest of the family
- SSY-N — the all-aluminium twin, same dimensions.
- SSY — standard ACSR twin.
- SYG — single conductor, flash welded.
- SSLG — bolted twin with copper plates.
Note: Quote the conductor, the spacing and the angle, e.g. SSYG-500/65NB-200, and say the terminal is copper. Give L2 × A if the plate differs from the catalogue.