PF Power Fittings Technical Reference

SSYG-N Brazed Heat Resistant Twin Conductor Equipment Clamp

Conductors: NRLH58/60-240 to -1440 · LGKK-900, -1400 · Spacing: 120 / 200 / 400 mm · Plate: 0°, 30° or 90°

SSYG-N brazed heat resistant twin conductor clamp, type A SSYG-N brazed heat resistant twin conductor clamp, type C

SSYG-N is the twin-bundle heat-resistant clamp with copper plates brazed onto aluminium bodies. The bodies grip the conductor and stay aluminium; the plates land on the equipment terminal and are copper. That is the whole reason the G exists.

The factory sheet says the process is brazed — not the flash welding used on the single-conductor SYG. On a twin the plate is a separate piece on each side, and brazing is how it is attached.

The code, and the note that settles the letters

SSY-500/65NA(B/C)-200

Part Meaning
SSY / SSYG twin clamp, all aluminium / with brazed copper plates
500/65 the conductor, NRLH58/60-500/65
N heat-resistant series
A plate angle — and the sheet says so in words
(B/C) the same row is also made as B and as C
-200 spacing between the two conductor grooves

The factory note on both sheets reads: “additional letters: A indicates horizontal (0°), B indicates 30°, C indicates 90°, e.g. for a 30° 500/65 heat-resistant conductor the model is SSY-500/65NB.” That is the authoritative statement of the angles and it matches the drawings.

B and C are not separate tables. Every row prints A(B/C), because all three angles share the same dimensions — only the plate is turned. So one table covers all three.

Technical parameters, all three angles

ModelConductorMain dimensions (mm)
AHBLD
SSYG-240/30-40NA(B/C)-120NRLH58/60-240/30~401251301812045
SSYG-240/30-40NA(B/C)-200NRLH58/60-240/30~401251301820045
SSYG-240/30-40NA(B/C)-400NRLH58/60-240/30~401251301840045
SSYG-300/25-40NA(B/C)-120NRLH58/60-300/25~401251302012050
SSYG-300/25-40NA(B/C)-200NRLH58/60-300/25~401251302020050
SSYG-300/25-40NA(B/C)-400NRLH58/60-300/25~401251302040050
SSYG-400/20-35NA(B/C)-120NRLH58/60-400/20~351251302012055
SSYG-400/20-35NA(B/C)-200NRLH58/60-400/20~351251302020055
SSYG-400/20-35NA(B/C)-400NRLH58/60-400/20~351251302040055
SSYG-400/50-65NA(B/C)-120NRLH58/60-400/50~651251302012055
SSYG-400/50-65NA(B/C)-200NRLH58/60-400/50~651251302020055
SSYG-400/50-65NA(B/C)-400NRLH58/60-400/50~651251302040055
SSYG-500/35-45NA(B/C)-120NRLH58/60-500/35~451501552212065
SSYG-500/35-45NA(B/C)-200NRLH58/60-500/35~451501552220065
SSYG-500/35-45NA(B/C)-400NRLH58/60-500/35~451501552240065
SSYG-500/65NA(B/C)-120NRLH58/60-500/651501552212065
SSYG-500/65NA(B/C)-200NRLH58/60-500/651501552220065
SSYG-500/65NA(B/C)-400NRLH58/60-500/651501552240065
SSYG-630/45-55NA(B/C)-200NRLH58/60-630/45~551501552220070
SSYG-630/45-55NA(B/C)-400NRLH58/60-630/45~551501552240070
SSYG-800/55-100NA(B/C)-200NRLH58/60-800/55~1001501552220070
SSYG-800/55-100NA(B/C)-400NRLH58/60-800/55~1001501552240070
SSYG-1000/125NA(B/C)-200NRLH58/60-1000/1251501552420076
SSYG-1000/125NA(B/C)-400NRLH58/60-1000/1251501552440076
SSYG-1440/120NA(B/C)-200NRLH58/60-1440/1201501552420080
SSYG-1440/120NA(B/C)-400NRLH58/60-1440/1201501552440080
SSYG-900KA(B/C)-200LGKK-9001251302020074
SSYG-900KA(B/C)-400LGKK-9001251302040074
SSYG-1400KA(B/C)-200LGKK-14001251302220084
SSYG-1400KA(B/C)-400LGKK-14001251302240084

All dimensions in millimetres. Thirty rows, and every one matches the SSY-N sheet line for line — see below.

Reading the table

  • A (mm) — plate width, 125 or 150.
  • H (mm) — plate length, 130 or 155. Note that A and H are not equal on this sheet: the plate is 125 × 130 or 150 × 155, not square as on the bolted single-conductor clamp.
  • B (mm) — thickness across the closed clamp, 18 to 24 mm.
  • L (mm) — spacing between the two grooves, 120, 200 or 400.
  • D (mm) — the conductor groove, 45 to 84 mm. Here D really is the groove; do not confuse it with the bolted twin sheet where the same letter is used for the spacing.

There is no weight column on either sheet. If you need a weight for freight, ask and we will weigh a sample rather than quote a number the catalogue does not publish.

Dimensionally identical to SSY-N

Checked row by row against both factory sheets: A, H, B, L and D are the same on all thirty rows. The only difference between an SSY-N and an SSYG-N of the same code is the metal in the plate.

So on a retrofit the SSYG-N goes onto the same bolt holes at the same spacing, with the same plate footprint. The substitution is safe on dimensions; it is only safe in the right direction if the terminal is copper. Putting a copper plate on an aluminium pad gains nothing and costs the copper.

120 mm is not available above 500 mm²

The three spacings are not offered evenly across the range:

Conductor 120 200 400
240/3040, 300/2540, 400/2035, 400/5065, 500/35~45, 500/65 yes yes yes
630/4555, 800/55100, 1000/125, 1440/120 — yes yes
LGKK-900, LGKK-1400 — yes yes

So 120 mm stops at 500 mm²; from 630 up there are only 200 and 400. If a drawing calls for 120 on a 630 twin, the frame has to be made — that is a note at enquiry, not an off-the-shelf part.

That gives 30 rows: six conductors at three spacings plus six at two.

The brazed plate

  • Do not heat it. A site torch on the plate will undo a braze long before anything looks hot.
  • Do not bend the plate to fit. A braze is a lap-type joint and does not take plastic strain; a plate bent cold cracks along the fillet.
  • Check the fillet. A sound braze is an even collar all the way round. A lumpy or gashed one was made cold.
  • The plate is made to order if needed — the sheet’s own note: “if A and L2 change, specify L2 × A when ordering, e.g. SSYG-500/65NA(L2×A).”

The 1440 Pair And Its Two Codes

The 1400 rows close the table with a code and a dimension that have to be read together: SSYG-1400KA(B/C)-200 is the 200 mm spacing and SSYG-1400KA(B/C)-400 the 400 mm one, and the L column on each row carries that number. Order by the trailing figure and the spacing follows.

Every other row of both sheets reads the same way: the L column and the trailing number agree.

Fitting a twin

  • Crimp or bolt before the bundle is tensioned. The yoke is a terminal, not a spacer, and it will not take conductor tension.
  • Both barrels identical. Two different crimp depths on the same twin is the classic cause of current imbalance between sub-conductors; it shows up in a thermal survey, not in a continuity test.
  • Keep the plate flat. Two barrels swaged in sequence pull the yoke one way then the other.
  • The plate is made to order if it needs to be. The note on the SSYG sheet: “if A and L2 change, the user should specify L2 × A when ordering, e.g. SSYG-500/65NA(L2×A).”

The rest of the family

  • SSY-N — the all-aluminium twin, same dimensions.
  • SSY — standard ACSR twin.
  • SYG — single conductor, flash welded.
  • SSLG — bolted twin with copper plates.

Note: Quote the conductor, the spacing and the angle, e.g. SSYG-500/65NB-200, and say the terminal is copper. Give L2 × A if the plate differs from the catalogue.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: