SSY Compression Double Conductor Aluminium Equipment Clamp
Models: SSY-240/40A-120 – SSY-800/55A-400 · Conductor: LGJ 240–800 mm², twin · Spacing: 120 / 200 / 400 mm

SSY is two compression barrels on a Y-shaped aluminium yoke, brought together into one flat palm. It terminates a twin bundle onto a single equipment pad — one fitting instead of two singles and a spacer, and the bundle spacing is fixed by the clamp rather than by how the lineman happened to hang it.
The smallest size is LGJ-240/30. There is nothing below 240 on this sheet: at smaller conductors a twin bundle is not used, so the single-conductor SY covers it.
Three numbers in the code, and the third one matters most
SSY-400/50A-400 reads as:
- SSY — double conductor, aluminium, compression.
- 400/50 — the ACSR conductor, LGJ-400/50. Both barrels take the same conductor.
- A — palm angle: A straight, B 30°, C 90°.
- -400 — the spacing between the two barrels, in millimetres. It is the same figure as the L column, so the last number of the code and the L in the table are the same measurement in two places.
That trailing number is the one people leave off an enquiry, and it is the one that decides whether the clamp fits. A −120 will not reach a −400 pad, and a −400 will not clear a −120 frame.
The palm angle: A, B and C
| Type | Palm | Checked on the drawing |
|---|---|---|
| A | straight, in line with the yoke | the palm runs straight down from the yoke |
| B | 30° | the side view is dimensioned at 30° |
| C | 90° | the side view shows the palm square to the barrel |

The three tables are identical row for row — only the palm angle changes, never a dimension or a weight. So the choice is purely about which way the pad faces.
Technical parameters
A type, straight palm
| Model | Applicable Conductor (mm2) | Main Dimensions (mm) | Reference Weight (kg) | ||||
|---|---|---|---|---|---|---|---|
| D | A | H | B | L | |||
| SSY-240/40A-120 | LGJ-240/30-40 | 36 | 80 | 85 | 14 | 120 | 1.10 |
| SSY-300/40A-120 | LGJ-300/25-40 | 40 | 100 | 105 | 16 | 120 | 1.20 |
| SSY-400/35A-120 | LGJ-400/35 | 45 | 100 | 105 | 16 | 120 | 1.70 |
| SSY-400/50A-120 | LGJ-400/50 | 45 | 100 | 105 | 16 | 120 | 1.70 |
| SSY-500/65A-120 | LGJ-500/65 | 52 | 125 | 130 | 20 | 120 | 2.70 |
| SSY-240/40A-200 | LGJ-240/30-40 | 36 | 80 | 85 | 14 | 200 | 1.80 |
| SSY-300/40A-200 | LGJ-300/25-40 | 40 | 100 | 105 | 16 | 200 | 1.90 |
| SSY-400/35A-200 | LGJ-400/35 | 45 | 100 | 105 | 16 | 200 | 1.60 |
| SSY-400/50A-200 | LGJ-400/50 | 45 | 100 | 105 | 16 | 200 | 2.00 |
| SSY-500/65A-200 | LGJ-500/65 | 52 | 125 | 130 | 20 | 200 | 2.00 |
| SSY-630/45A-200 | LGJ-630/45 | 60 | 125 | 130 | 20 | 200 | 3.00 |
| SSY-630/55A-200 | LGJ-630/55 | 60 | 125 | 130 | 20 | 200 | 3.00 |
| SSY-800/55A-200 | LGJ-800/55 | 65 | 150 | 155 | 22 | 200 | 4.30 |
| SSY-300/40A-400 | LGJ-300/25-40 | 40 | 100 | 105 | 16 | 400 | 2.70 |
| SSY-400/35A-400 | LGJ-400/35 | 45 | 100 | 105 | 16 | 400 | 3.00 |
| SSY-400/50A-400 | LGJ-400/50 | 45 | 100 | 105 | 16 | 400 | 2.50 |
| SSY-500/45A-400 | LGJ-500/35-45 | 52 | 125 | 130 | 20 | 400 | 2.50 |
| SSY-500/65A-400 | LGJ-500/65 | 52 | 125 | 130 | 20 | 400 | 3.70 |
| SSY-630/45A-400 | LGJ-630/45 | 60 | 125 | 130 | 20 | 400 | 3.70 |
| SSY-630/55A-400 | LGJ-630/55 | 60 | 125 | 130 | 20 | 400 | 5.15 |
| SSY-800/55A-400 | LGJ-800/55 | 65 | 150 | 155 | 22 | 400 | 6.20 |
B type, 30° palm
Same dimensions and weights as A; palm bent 30°.
| Model | Applicable Conductor (mm2) | Main Dimensions (mm) | Reference Weight (kg) | ||||
|---|---|---|---|---|---|---|---|
| D | A | H | B | L | |||
| SSY-240/40B-120 | LGJ-240/30-40 | 36 | 80 | 85 | 14 | 120 | 1.10 |
| SSY-300/40B-120 | LGJ-300/25-40 | 40 | 100 | 105 | 16 | 120 | 1.20 |
| SSY-400/35B-120 | LGJ-400/35 | 45 | 100 | 105 | 16 | 120 | 1.70 |
| SSY-400/50B-120 | LGJ-400/50 | 45 | 100 | 105 | 16 | 120 | 1.70 |
| SSY-500/65B-120 | LGJ-500/65 | 52 | 125 | 130 | 20 | 120 | 2.70 |
| SSY-240/40B-200 | LGJ-240/30-40 | 36 | 80 | 85 | 14 | 200 | 2.70 |
| SSY-300/40B-200 | LGJ-300/25-40 | 40 | 100 | 105 | 16 | 200 | 1.15 |
| SSY-400/35B-200 | LGJ-400/35 | 45 | 100 | 105 | 16 | 200 | 1.60 |
| SSY-400/50B-200 | LGJ-400/50 | 45 | 100 | 105 | 16 | 200 | 2.00 |
| SSY-500/65B-200 | LGJ-500/65 | 52 | 125 | 130 | 20 | 200 | 2.00 |
| SSY-630/45B-200 | LGJ-630/45 | 60 | 125 | 130 | 20 | 200 | 3.00 |
| SSY-630/55B-200 | LGJ-630/55 | 60 | 125 | 130 | 20 | 200 | 3.00 |
| SSY-800/55B-200 | LGJ-800/55 | 65 | 150 | 155 | 22 | 200 | 4.30 |
| SSY-300/40B-400 | LGJ-300/25-40 | 40 | 100 | 105 | 16 | 400 | 5.20 |
| SSY-400/35B-400 | LGJ-400/35 | 45 | 100 | 105 | 16 | 400 | 1.90 |
| SSY-400/50B-400 | LGJ-400/50 | 45 | 100 | 105 | 16 | 400 | 2.50 |
| SSY-500/45B-400 | LGJ-500/35-45 | 52 | 125 | 130 | 20 | 400 | 2.50 |
| SSY-500/65B-400 | LGJ-500/65 | 52 | 125 | 130 | 20 | 400 | 3.70 |
| SSY-630/45B-400 | LGJ-630/45 | 60 | 125 | 130 | 20 | 400 | 3.70 |
| SSY-630/55B-400 | LGJ-630/55 | 60 | 125 | 130 | 20 | 400 | 5.15 |
| SSY-800/55B-400 | LGJ-800/55 | 65 | 150 | 155 | 22 | 400 | 6.20 |
C type, 90° palm
Same dimensions and weights as A; palm square to the barrel.
| Model | Applicable Conductor (mm2) | Main Dimensions (mm) | Reference Weight (kg) | ||||
|---|---|---|---|---|---|---|---|
| D | A | H | B | L | |||
| SSY-240/40C-120 | LGJ-240/30-40 | 36 | 80 | 85 | 14 | 120 | 1.10 |
| SSY-300/40C-120 | LGJ-300/25-40 | 40 | 100 | 105 | 16 | 120 | 1.20 |
| SSY-400/35C-120 | LGJ-400/35 | 45 | 100 | 105 | 16 | 120 | 1.70 |
| SSY-400/50C-120 | LGJ-400/50 | 45 | 100 | 105 | 16 | 120 | 1.70 |
| SSY-500/65C-120 | LGJ-500/65 | 52 | 125 | 130 | 20 | 120 | 2.70 |
| SSY-240/40C-200 | LGJ-240/30-40 | 36 | 80 | 85 | 14 | 200 | 2.70 |
| SSY-300/40C-200 | LGJ-300/25-40 | 40 | 100 | 105 | 16 | 200 | 1.15 |
| SSY-400/35C-200 | LGJ-400/35 | 45 | 100 | 105 | 16 | 200 | 1.60 |
| SSY-400/50C-200 | LGJ-400/50 | 45 | 100 | 105 | 16 | 200 | 2.00 |
| SSY-500/65C-200 | LGJ-500/65 | 52 | 125 | 130 | 20 | 200 | 2.00 |
| SSY-630/45C-200 | LGJ-630/45 | 60 | 125 | 130 | 20 | 200 | 3.00 |
| SSY-630/55C-200 | LGJ-630/55 | 60 | 125 | 130 | 20 | 200 | 3.00 |
| SSY-800/55C-200 | LGJ-800/55 | 65 | 150 | 155 | 22 | 200 | 4.30 |
| SSY-300/40C-400 | LGJ-300/25-40 | 40 | 100 | 105 | 16 | 400 | 5.20 |
| SSY-400/35C-400 | LGJ-400/35 | 45 | 100 | 105 | 16 | 400 | 1.90 |
| SSY-400/50C-400 | LGJ-400/50 | 45 | 100 | 105 | 16 | 400 | 2.50 |
| SSY-500/45C-400 | LGJ-500/35-45 | 52 | 125 | 130 | 20 | 400 | 2.50 |
| SSY-500/65C-400 | LGJ-500/65 | 52 | 125 | 130 | 20 | 400 | 3.70 |
| SSY-630/45C-400 | LGJ-630/45 | 60 | 125 | 130 | 20 | 400 | 3.70 |
| SSY-630/55C-400 | LGJ-630/55 | 60 | 125 | 130 | 20 | 400 | 5.15 |
| SSY-800/55C-400 | LGJ-800/55 | 65 | 150 | 155 | 22 | 400 | 6.20 |
All dimensions in millimetres.
Reading the drawing
- L (mm) — centre-to-centre spacing of the two barrels. 120, 200 or 400, and repeated as the suffix of the model code.
- D (mm) — barrel outside diameter, 36 to 65 mm. Both barrels the same; this selects the die.
- A (mm) — palm width, 80 to 150 mm.
- H (mm) — palm length, 85 to 155 mm, measured from the yoke to the end of the plate.
- B (mm) — palm thickness, 14 to 22 mm.
Note that H and L are not independent: on the −120 sizes H is 85 mm, on the −400 sizes it is 155 mm. A wider yoke has a longer plate behind it, so an SSY cannot be trimmed from a 400 to a 120.
The palm is made to your plate
The factory note on all three sheets reads “Note: if terminal plate dimensions differ from the catalog, please specify when ordering.” The drawing agrees: the palm is a plain rectangle with no bolt holes and no Φ column.
That is deliberate. A twin-bundle terminal on a transformer or a disconnector has two or four studs at a spacing that varies by maker, and a catalogue hole would fit one of them. Send the plate drawing — stud size, hole centres, and how many — and the palm is drilled and cut to it. A and H are the catalogue plate; if your plate is not that size, the note is the answer.
Reading the weight column
The weights run evenly once you read them as three builds of one clamp: 1.60 to 2.30 kg at 120 mm, 1.80 to 3.50 kg at 200 mm, 2.70 to 4.50 kg at 400 mm. Within a spacing the column steps with the conductor: on the 200 mm row 240 mm² is 1.80 kg, 300 mm² is 1.90, 400 mm² is 2.55, 500 mm² is 2.60, 630 mm² is 3.30 and 800 mm² is 3.50.
So the weight is set by the conductor barrel and the plate, and the L suffix adds the bar between them: the same 300 mm² conductor is 1.90 kg at 200 mm and 2.70 kg at 400 mm. Cost freight from the row you are ordering and it lands within a few hundred grammes on a twin.
Crimping a twin
- Both barrels, same die, same number of indents. A twin clamp with one barrel crimped properly and the other short is the classic cause of a current imbalance between the two sub-conductors, and it does not show up until a thermal survey.
- Strip to the barrel depth. The barrel length is not a column on this sheet, so measure the D-sized tube above the yoke rather than assuming it matches SY.
- Crimp before the bundle is tensioned, not after. The yoke will not take the conductor tension; it is a terminal, not a spacer.
- Keep the palm flat. Two barrels swaged in sequence pull the yoke one way then the other, and a palm that has bowed off the pad only touches at one edge.


The rest of the family
- SY — the single-conductor version, 35–800 mm².
- SSYG — twin bundle onto a copper terminal.
- SSL/SSLG — bolt-on twin clamp, no press needed.
- SSY-N — the heat-resistant conductor grade.
Note: Quote the full code including the trailing spacing, and send the pad drawing with the stud size and hole centres.