SYG Copper-Aluminium Transition Clamp — Electrified Railway Only
Models: SYG-120A/B/C, SYG-150A/B/C — railway series only

The code is shared, the part is not. There is another SYG on this site — the overhead-line clamp, aluminium barrel and copper palm, chosen against an LGJ conductor and listed as SYG-50A up to SYG-800/100A. It uses the same codes: SYG-120A on that page is a different fitting from SYG-120A here. This page is the railway series, and it is the reverse direction — copper barrel, aluminium palm. On an enquiry, write railway SYG as well as the code, and give the conductor. The overhead-line part is on the SYG compression copper-aluminium equipment clamp page.
A copper-aluminium transition part runs in one of two directions, and it is worth fixing the words before you look at the drawing:
- Standard direction — aluminium barrel, copper palm. An aluminium conductor lands on copper equipment. This is what a normal SYG clamp is, and it is the same direction as the DTL terminal.
- Reverse direction — copper barrel, aluminium palm. A copper conductor lands on an aluminium pad. The catalogues call this the reverse type, or the inverted type, and some makers give it the model DLT — DTL with the two letters the other way round.
Both tables on this page are the reverse direction. That is the application: in OCS and rigid-catenary work a stranded copper cable feeds an aluminium alloy busbar, and the two metals must not sit in contact. Both constructions therefore carry a copper barrel; what changes between them is where the bimetal boundary sits.
Every other clamp on the neighbouring railway pages is copper all the way through — DTR, STR, SST — and expects a copper or tinned pad. SYG is the one that is part aluminium.
Part of the electrified railway equipment clamp family.
Two ways to build the same joint
The sheet carries two constructions under the same model codes, and the difference is where the copper stops:
- Inverted, welded (SYG, first table) — the palm is solid aluminium, welded to a copper barrel. There is one bimetal interface, at the neck, and it is made by welding rather than by bolting.
- Copper-based, aluminium-clad (SYG, second table) — the palm is a composite. The drawing labels the neck side copper and the face that meets the pad aluminium, so copper carries current out of the barrel into the palm and the aluminium sits as a layer on the contact face. The bimetal boundary is inside the palm instead of at the neck.
Read either one against the cable: the conductor sits in copper, the equipment pad sits on aluminium. That is the whole point of a reverse-direction clamp. What you are choosing between is a welded neck and a clad face.
If the joint is being specified for a location you cannot inspect — a tunnel, a foundation stub, anything with water on it — the clad version is the one to argue for. If it is a dry terminal box and cost matters, the welded inverted type does the same electrical job.
Technical parameters
Inverted transition:
| Model | d | D | L | L1 | L2 | W | S |
|---|---|---|---|---|---|---|---|
| SYG-120A | 16.7 | 24 | 135 | 50 | 50 | 48 | 8 |
| SYG-120B | 16.7 | 24 | 135 | 50 | 63 | 48 | 8 |
| SYG-120C | 16.7 | 24 | 158 | 50 | 63 | 48 | 8 |
| SYG-150A | 19 | 27 | 135 | 50 | 50 | 48 | 8 |
| SYG-150B | 19 | 27 | 135 | 50 | 63 | 48 | 8 |
| SYG-150C | 19 | 27 | 158 | 50 | 63 | 48 | 8 |
Copper-based, aluminium-clad:
| Model | d | D | L | L1 | L2 | W | S |
|---|---|---|---|---|---|---|---|
| SYG-120A | 16.7 | 24 | 130 | 50 | 50 | 48 | 8 |
| SYG-120B | 16.7 | 24 | 130 | 50 | 63 | 48 | 8 |
| SYG-120C | 16.7 | 24 | 158 | 50 | 63 | 48 | 8 |
| SYG-150A | 19 | 27 | 135 | 50 | 50 | 48 | 8 |
| SYG-150B | 19 | 27 | 135 | 50 | 63 | 48 | 8 |
| SYG-150C | 19 | 27 | 158 | 50 | 63 | 48 | 8 |
All dimensions in millimetres. The two tables are identical except in L at the 120 sizes — 135 mm against 130. Specify which construction you want; the model code alone does not distinguish them.
Reading the drawing
- d (mm) — bore: 16.7 for 120 mm², 19 for 150. Generous for the conductor size, which is deliberate: it takes fine-strand flexible cable without dressing the bundle in.
- D (mm) — barrel outside diameter, 24 and 27 mm. Selects the die.
- L1 (mm) — barrel length, 50 mm on every model. The strip length and crimp schedule do not change across the range.
- L2 (mm) — palm length, 50 or 63 mm. This is the real variable between A, B and C.
- W (mm) — palm width, 48 mm on every model.
- S (mm) — palm thickness, 8 mm on every model.
- Φ 13 — the palm hole, dimensioned on the drawing.
- 19 mm — from the palm end to the hole centre.
One palm, two conductor sizes
W and S do not move across the six models: 48 mm wide, 8 mm thick, one drilling. Only the barrel changes between 120 and 150 mm². That is worth something on a project — one pad pattern, one set of bolts, one torque setting for both conductor sizes, and the spares you keep are barrels rather than complete clamps.
It also means the palm has material to spare. The hole is Ø13 (M12) at 19 mm from the end, and with 48 mm of width there is 17.5 mm of metal either side of it. Going to Ø18 for an M16 stud still leaves 15 mm each side, and to Ø22 leaves 13 mm. In this family SYG has by far the most room to open the palm up — which is the useful thing about it when the equipment pad turns out to be drilled for a bigger stud than the drawing said.
Along the palm the constraint is the 19 mm offset: a Ø22 hole at 19 mm centres leaves 8 mm of metal to the palm end. That is still sound on an 8 mm thick palm, but it is the figure to check, not the width.
A, B and C
The three letters are about reach, not about current:
| Model | L2 (mm) | L (mm) | Effect |
|---|---|---|---|
| A | 50 | 135 | compact palm; the bolted joint sits closest to the conductor |
| B | 63 | 135 | 13 mm more palm at the same overall length |
| C | 63 | 158 | the long reach, 23 mm more overall |
Because the hole is at 19 mm from the palm end, a longer palm moves the bolted joint further from the conductor by the same amount. On a terminal where the pad sits behind an obstruction, that reach is the whole reason for buying B or C; on a plain terminal, A is the shortest thing that fits.
Crimping and the transition
- Strip to L1 (50 mm), less 1 to 2 mm.
- Crimp from the palm end toward the barrel mouth, one die position per barrel diameter — a 24 mm barrel takes two.
- Do not heat the neck. On the inverted type the weld between the aluminium palm and the copper barrel is the joint the whole fitting is bought for. A torch to straighten a palm, or a die run onto the neck, is how that joint is ruined. If the palm needs adjusting, it needs a new clamp.
Where the bimetal joint earns its money
A copper-to-aluminium joint bolted dry is fine until water arrives. Then, at the interface, the aluminium becomes the anode, an oxide film forms, resistance climbs, the joint runs hot, and the heat accelerates the whole thing. A welded or clad transition exists to remove that interface from the weather — the joint metal is bonded, not merely touching.
That is also why the standards test it under load cycling rather than just at one temperature: the damage happens on the way up and down, not at the top.
Standards
Dimensioned against TB/T 2073-2020, tested to TB/T 2074-2020; general requirements GB/T 2314, mechanical tests GB/T 2317.1, load-cycling stability of the joint GB/T 2317.3. Where the clamp forms part of the OCS electrical connection, TB/T 2075.11 (electrical connection devices) governs it.

The rest of the family
- DTR — all-copper terminal, the default where the pad is copper or tinned.
- STR — all-copper, wider palm, drilled to pattern.
- SST — plate type, two conductors to one pad.
- SYG compression clamp — the overhead-line SYG, standard direction, aluminium barrel on an LGJ conductor. Same family of codes, different part.
- DTL — the standard direction: aluminium barrel, copper palm, aluminium conductor onto copper equipment.
Note: Tell us which construction you want — welded inverted or copper-based clad — and the stud size for the palm; the tables differ by 5 mm in L at 120 mm² and by nothing else.