SYT Compression Copper Equipment Clamp, Type A and B
Sizes: SYT-35 to SYT-1000, 14 sizes · Plate: Type A 0°, Type B 30°

SYT is a one-piece copper lug: a compression barrel at one end, a flat palm at the other, no bolts over the conductor. It is made in copper throughout — this is the copper member of the compression family, not a bimetallic transition.
Fourteen sizes cover 35 to 1000 mm² nominal, in two plate options, A and B.
Type A and Type B are the same clamp at a different angle
The sheet carries both types on one table because D, A and L1 do not change between them. Only the plate position differs:
| Type | Plate | What the drawing shows |
|---|---|---|
| A | 0° | plate continues straight out of the barrel, in line with the barrel axis |
| B | 30° | plate is bent 30° away from the barrel axis, and the sheet marks the angle |
So the choice is a routing decision, not a strength decision. A straight palm lands on a pad that faces the conductor end-on; the 30° palm clears a terminal that sits behind or beside the run. Order the type that matches the pad, and remember that L2 is measured along the plate — on Type B it is a length along the slant, not a vertical drop.
Technical parameters
| Model | Main dimensions (mm) | ||||
|---|---|---|---|---|---|
| D | A | L (ref.) | L1 | L2 | |
| SYT-35 | 14 | 30 | 125 | 60 | 50 |
| SYT-50 | 16 | 30 | 125 | 60 | 50 |
| SYT-70 | 18 | 40 | 145 | 70 | 60 |
| SYT-95 | 20 | 40 | 155 | 70 | 65 |
| SYT-120 | 22 | 40 | 165 | 75 | 70 |
| SYT-150 | 25 | 50 | 175 | 75 | 80 |
| SYT-185 | 27 | 50 | 185 | 80 | 80 |
| SYT-240 | 30 | 50 | 185 | 80 | 80 |
| SYT-300 | 32 | 60 | 200 | 90 | 85 |
| SYT-400 | 36 | 60 | 205 | 90 | 85 |
| SYT-500 | 40 | 80 | 210 | 90 | 90 |
| SYT-630 | 45 | 100 | 240 | 100 | 110 |
| SYT-800 | 50 | 100 | 245 | 110 | 110 |
| SYT-1000 | 55 | 100 | 255 | 110 | 110 |
All dimensions in millimetres. The sheet prints no weight and no plate thickness for SYT — see the note at the end of this page.
Reading the drawing
- D (mm) — outside diameter of the compression barrel, 14 to 55. This is the barrel, not the conductor: at SYT-35 a 35 mm² copper conductor is about 7.6 mm, and the barrel has to be thick enough to take the die.
- A (mm) — width of the palm, 30 to 100.
- L1 (mm) — length of the compression barrel, 60 to 110. This is the figure that matters when you check whether the conductor will go fully home.
- L2 (mm) — length of the palm, 50 to 110.
- L (mm) — overall length, marked as a reference only. It is always longer than L1 + L2, because the difference is the forged neck between barrel and palm: 15 mm at the small sizes, rising to 35 mm at SYT-1000.
Six palm widths across fourteen sizes
A is not a free variable — it steps, and unevenly:
| Palm width A | Sizes |
|---|---|
| 30 mm | 35, 50 |
| 40 mm | 70, 95, 120 |
| 50 mm | 150, 185, 240 |
| 60 mm | 300, 400 |
| 80 mm | 500 only |
| 100 mm | 630, 800, 1000 |
So 80 mm is a single-size step, at SYT-500 alone. If you are standardising bolt lengths across a substation, that is the odd one out.
Two rows also deserve a second look before you draw them. SYT-185 and SYT-240 are dimensionally identical — same A (50), same L (185), same L1 (80), same L2 (80) — and differ only in D, 27 against 30. Same forging, larger bore. And L2 is longer than L1 at SYT-150 and SYT-630, the only two places in the table where the palm outruns the barrel.
How it compares with the aluminium clamp
The aluminium SY sheet uses the same letters for the same features — D barrel, A palm, L1 barrel length — so the two read side by side. Over the thirteen sizes they share:
- The copper barrel is slimmer. D is 2 mm smaller at SYT-35 and widens to 15 mm smaller by SYT-800. Copper carries the same current in less metal.
- The copper barrel is shorter at the top end. L1 matches at 35, 50 and 70, then falls behind: 10 mm at SYT-95, 20 mm at SYT-240, 30 mm at SYT-400, 60 mm at SYT-800.
- The palm widths mostly agree, but not everywhere — 10 mm narrower at SYT-120, 3 mm at SYT-300 and SYT-400, 25 mm at SYT-800. Do not assume a like-for-like swap onto the same pad.
- SYT-1000 has no SY counterpart. 1000 mm² is copper only.
Fitting it
- It is copper, so it is for copper — a copper conductor, or a copper-to-copper joint. For ACSR onto a copper pad the part is SYG, which is bimetallic. An all-copper palm bolted to an aluminium terminal puts the joint straight into galvanic corrosion.
- Match the die to the barrel, not to the conductor size. The barrel wall differs from the aluminium clamp at the same nominal size, so an SY die is not automatically the right die here.
- Ask for the palm thickness before you drill anything. The sheet does not print it, and it is what sets your stud length.
- L1 is the insertion check. Measure the stripped conductor against L1 before crimping; a conductor that stops short of the barrel shoulder has no mechanical grip.
- No weight is published, so do not quote freight off this table.
The rest of the family
- SY — aluminium, ACSR, plates at 0°, 30° and 90°.
- SYG — copper-aluminium transition, aluminium barrel on a copper plate.
- STY and STYG — the two-piece adjustable clamp for expanded hollow conductor.
- SLSG — bolted twin clamp with a copper plate, for when there is no press on site.
Note: Quote the size and the type — SYT-240 Type B — and say what the conductor is. A copper palm on an aluminium terminal is the one mistake this family punishes.