DTGR Short-Body Copper Terminal
Models: DTGR-25 – DTGR-240 (9 sizes)

DTGR is the short-body version of the copper terminal in this family. Same conductor range, same palm drilling, same copper — the whole point of it is that it takes 10 to 25 mm less space along the axis of the conductor.
That is not a cosmetic difference. On a retrofit, or inside a link box, a disconnector housing or a cable trough that was built for something else, the length is often the only thing that does not fit; the palm and the bore are rarely the problem.
Part of the electrified railway equipment clamp family.
Technical parameters
| Model | Φ | D | d | L |
|---|---|---|---|---|
| DTGR-25 | 10.5 | 12 | 8.5 | 66 |
| DTGR-35 | 10.5 | 14 | 10 | 72 |
| DTGR-50 | 12.5 | 16 | 12 | 80 |
| DTGR-70 | 12.5 | 18 | 13 | 87 |
| DTGR-95 | 14.5 | 20 | 15 | 96 |
| DTGR-120 | 14.5 | 22 | 16 | 103 |
| DTGR-150 | 16.5 | 25 | 18 | 115 |
| DTGR-185 | 16.5 | 27 | 20 | 120 |
| DTGR-240 | 21 | 31 | 24 | 135 |
All dimensions in millimetres.
Where the length goes

Set against the DTR at the same conductor size:
| Size | DTR L (mm) | DTGR L (mm) | Saved (mm) |
|---|---|---|---|
| 25 mm² | 79 | 66 | 13 |
| 35 mm² | 87 | 72 | 15 |
| 50 mm² | 95 | 80 | 15 |
| 70 mm² | 105 | 87 | 18 |
| 95 mm² | 112 | 96 | 16 |
| 120 mm² | 118 | 103 | 15 |
| 150 mm² | 125 | 115 | 10 |
| 185 mm² | 136 | 120 | 16 |
| 240 mm² | 160 | 135 | 25 |
The bore d and the barrel outside diameter D are essentially unchanged, so the saving is not made by shrinking the conductor hole. It comes out of the barrel and the neck between the barrel and the palm — which is also the crimp zone.
Two things follow, and both are worth settling before you order:
- Strip length and crimp position change. The conductor still has to reach the bottom of the barrel, but there is less barrel to crimp into. Take the strip length from the drawing rather than from the DTR sheet.
- The 25 mm saving at 240 mm² is the one to check. That is a bigger proportion of the barrel than the 13 mm at 25 mm², and it is where a short body starts to cost crimp length.
Reading the table

- Φ (mm) — palm hole. Identical to the DTR at every size, so the two are interchangeable on the pad: five drillings — 10.5, 12.5, 14.5, 16.5 and 21 mm — covering the nine sizes.
- D (mm) — barrel outside diameter, 12 to 31 mm; selects the die.
- d (mm) — bore. 10 to 25 mm.
- L (mm) — overall length, 66 to 135 mm.
The DTGR sheet publishes only these four. It does not give L2 (palm length), W (palm width) or S (palm thickness), although S is dimensioned on the drawing. If palm length or thickness is a design input for you — for example because the palm sits against a machined pad face — send the pad drawing and we will confirm those figures against it rather than let you work from the DTR numbers.
Where DTGR is the easier fit on the bore
At two sizes the bore is one step more generous than the DTR:
| Size | DTR d (mm) | DTGR d (mm) | DTR D (mm) | DTGR D (mm) |
|---|---|---|---|---|
| 35 mm² | 9.6 | 10 | 14 | 14 |
| 240 mm² | 23 | 24 | 30 | 31 |
If you are crimping fine-strand flexible cable at the top of a size — a 240 mm² class 5 bundle, for instance — the extra millimetre is the difference between the bundle entering freely and having to be dressed into the barrel. Everything else being equal, take the DTGR for flexible cable.
The palm hole
Same rule as everywhere else in this family: the hole can be drilled to your stud, and the limit is the metal either side of it, (W − Φ)/2. The DTGR palm is the DTR palm, so the practical ceiling is the same — roughly M12 on the 25 mm² and M42 on the 240 mm². Ask for a different stud and the palm is drilled, not reamed out.
Crimping
Hexagonal die on the barrel outside diameter, one die position per diameter. Because the barrel is shorter than the DTR’s, do not carry a crimp schedule across from the DTR page — recalculate the positions for this body.
Work from the palm end toward the barrel mouth. Crimping the other way traps air at the palm end, and a void there is exactly where a grounding terminal fails years later.
Standards
Dimensioned against TB/T 2073-2020, tested to TB/T 2074-2020, mechanical requirements to GB/T 2314 and GB/T 2317.1, copper T2 to GB/T 5231. Where the terminal forms part of the OCS electrical connection, TB/T 2075.11 (electrical connection devices) governs it.
The rest of the family
- DTR — the standard-length version this one is derived from.
- DTR-S — two-hole palm at standard length.
- STR — wider, thicker palm with a plain face.
Note: Catalogue dimensions; confirm L2, W and S against your pad drawing before fixing them in a design.