PF Power Fittings Technical Reference

CAU Copper-Aluminum Terminal (Export Type)

Models: CAU-16 – CAU-630 (14 sizes)

CAU is the second export pattern in the bimetal family, alongside the DTL-2. It is dimensioned differently in one important respect: the catalogue gives it a palm width W, which the DTL-2 does not. That single column is what makes CAU the series to quote when the palm has to cover a pad rather than just reach a stud.

Part of the DTL copper-aluminium terminal family.

CAU against DTL-2

Both are export patterns on the same conductor range, and both are shorter and heavier than the domestic DTL. The differences, at four sizes taken straight from the two tables:

Size CAU L (mm) DTL-2 L (mm) CAU palm W (mm) CAU hole Ø (mm) DTL-2 hole Ø (mm)
16 mm² 75 90 20 10.5 8.5
120 mm² 115 118 30 12.8 12.8
300 mm² 153 130 36 16.5 12.8
500 mm² 200 200 Figure B Figure B Square Head

Read across and the pattern is clear:

  • CAU is shorter at the small sizes — 75 mm against 90 at 16 mm² — because the palm is wider rather than longer.
  • CAU carries a larger catalogue hole at the sizes where DTL-2 is stuck on Ø 12.8. At 300 mm², CAU is drilled 16.5 while DTL-2 is 12.8.
  • At 500 mm² and above, neither series publishes numbers: CAU refers to Figure B for the palm (both Ø and W), DTL-2 uses a Square Head palm drilled to your stud.

So the selection rule is short: need palm width? CAU. Need a shorter body? CAU at the small sizes, DTL-2 at the middle. Need neither and the domestic lug fits the box? Take the DTL — it is the cheapest of the three.

Reading the table

  • Ø (mm) — palm hole: 10.5, 12.8 or 16.5 depending on size, and Figure B at 500/630. Drilled to your stud as on every DTL.
  • D (mm) — outside diameter over the transition; selects the die. 16 to 47 mm across the range.
  • d (mm) — bore, set by the conductor diameter, not a custom dimension.
  • L (mm) — overall length.
  • L1 (mm) — the barrel section, i.e. the crimp zone. 32 mm at 16 mm² up to 100 mm at 500/630.
  • W (mm) — palm width, 20 to 36 mm. The only series in this family where W is catalogued, and the reason to pick it.

The palm, and how far the hole goes

The edge rule is the same as everywhere in this family: at least half the hole diameter of metal between hole and palm edge. With W published, you can work it out before ordering:

  • CAU-16: (20 − 10.5) / 2 = 4.75 mm each side. Snug. A bigger stud here means going up a size.
  • CAU-120: (30 − 12.8) / 2 = 8.6 mm. Comfortable for the catalogued hole.
  • CAU-300: (36 − 16.5) / 2 = 9.75 mm. Room to work, but not unlimited.

That arithmetic is the whole reason to quote a series with a W column: on the series without it, the same question has to be answered by us from the drawing.

What can be changed: hole diameter, hole count, hole spacing, palm length, the angle of the palm to the barrel. What cannot: the bore d.

Two levels of change: a different hole in the same palm is a drilling change — short lead time, no meaningful minimum. A different W or a two-hole pattern is a die change with a minimum quantity.

For 500 and 630: the palm is Figure B, so send the pad drawing rather than a hole size. The palm at that size is a plate and can be cut to a pattern.

Standards and testing

GB/T 14315-2008 for the terminal, GB/T 9327-2008 / IEC 61238-1 for the methods: resistance ratio against an equal length of conductor, temperature rise, resistance after thermal cycling, mechanical pull-out.

The cycling test is the one that matters on a bimetal joint: the transition interface opens under repeated expansion and the resistance steps up there, while a cold measurement still looks fine.

Installation

  1. Strip to the barrel section L1 — insulation finishing at the mouth.
  2. Brush the conductor and bore; contact paste on the aluminium side.
  3. Insert fully.
  4. Crimp with the die matched to D — a domestic DTL die will not close on a CAU. Work from the transition end toward the mouth, one crimp per 15–20 mm, overlapping by a third.
  5. Check hexagonal closure with the die faces meeting.
  6. Seal the mouth outdoors and in buried joints.

Where these joints fail

  • A domestic DTL die on a CAU. D is larger; the crimp comes out oval.
  • Palm chosen by length alone. The stud ends up near the palm edge, the strip of metal is thin, and the joint loosens under preload. Check W before you check L.
  • Bore matched to the nominal mm² rather than the conductor diameter. Flexible cable is fatter and the crimp collapses the outer strands.
  • No seal outdoors. Water wicks into the barrel and the conductor corrodes from inside.

FAQ

CAU or DTL-2? CAU where the palm has to be wide or the pad is big; DTL-2 where the body has to be long enough to reach a stud set back from the cable entry. Both are export patterns and both are shorter than the domestic DTL.

Is there a two-hole CAU? Not in the catalogue. A two-hole palm on CAU is a cut pattern quoted against your drawing; the catalogued two-hole series is DTL-S.

What is Figure B? The drawing sheet for the 500 and 630 mm² palms. At those sizes the palm is a plate and its hole and width are taken from the drawing rather than from a table cell.

Can the hole be drilled to my stud? Yes. Give the stud size — the catalogued sizes are M10, M12 and M16 clearances, so anything else is a drilling change.

Technical Parameters

CAU copper-aluminium terminal CAU terminal drawing CAU terminal dimensions

Model Main Dimensions (mm)
Ø D d L L1 W
CAU-1610.5165.5753220
CAU-2510.5166.5753220
CAU-3512.8168.0863825
CAU-5012.8209.0863825
CAU-7012.82011.0863825
CAU-9512.82012.5863825
CAU-12012.82513.71155830
CAU-15012.82515.51155830
CAU-18512.83217.01155830
CAU-24012.83219.51155830
CAU-30016.54023.51538836
CAU-40016.54026.01538836
CAU-500Figure B4729.1200100Figure B
CAU-630Figure B4732.5200100Figure B

Note: Figure B means the palm hole and palm width are taken from the drawing sheet — at 500 and 630 mm² the palm is a plate and is cut to your pattern. L1 is the barrel (crimp) section, not the palm length. The bore d is not a custom dimension. Dimensions may vary slightly with manufacturing tolerance.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: