PF Power Fittings Technical Reference

DL Aluminium Terminal, DLM / DL-S

DLM aluminium terminal

Models: DLM-16 to DLM-800 (oil-sealed, 15 sizes), DL-16S to DL-630S (two-hole, 14 sizes), and an alloy-conductor set from 16 to 300 (11 sizes)

DL is the aluminium compression lug, and before anything else on this page there is one thing to get right: two of the three sets use the same model codes and are not interchangeable.

The copper counterpart is a separate page: DT copper terminal.

Two sets share the same code

The oil-sealed DLM and the set marked for aluminium alloy conductor both run DLM-16 through DLM-300. Same code, different metal thickness, different bore, different palm hole:

Model Oil-sealed: Ø / d / L / S Alloy set: Ø / d / L / S
DLM-16 8.4 / 5.5 / 70 / 3.0 8.5 / 6.0 / 75 / 3.5
DLM-25 8.4 / 7.0 / 75 / 3.5 8.5 / 7.0 / 75 / 3.5
DLM-70 12.5 / 12.0 / 102 / 4.5 10.5 / 11.5 / 110 / 5.2
DLM-120 14.5 / 15.0 / 120 / 5.5 12.5 / 15.0 / 125 / 6.8
DLM-240 16.5 / 20.0 / 140 / 7.5 12.5 / 21.0 / 142 / 8.3
DLM-300 21.0 / 23.0 / 165 / 8.5 16.5 / 23.0 / 160 / 9.0

DLM-25 is the only row where the two are identical. Every other size differs, and the wall thickness moves in opposite directions: the alloy set is thinner at the wall (S 8.3 against 7.5 at 240) but thicker at the barrel mouth on the small sizes.

Aluminium alloy — AAAC, and the 6201-type alloys — behaves differently from plain EC-grade aluminium under a crimp. It is harder, it springs back more, and it needs a different bore to fill. So when you quote a DLM, give the conductor type as well as the mm². Given only “DLM-120” we will ask which conductor before releasing the order.

Why the wall is thicker than copper

The bore d is almost the same as the copper lug of the same size — 16, 25, 35, 70, 120, 240 and 300 all differ by 0 or 0.5 mm, because the bore follows the conductor and the conductor is the same. What changes is the outside:

Size (mm²) DTM outside D DLM outside D Difference
16 10 10 0
35 12 14 +2
70 16 18 +2
120 20 23 +3
240 27 30 +3
400 34 38 +4
630 45 54 +9
800 50 60 +10

That is conductivity, not sloppiness. Aluminium carries about 61 % of what copper does for the same cross-section, so an aluminium barrel needs a thicker wall to reach the same current — and it matters most at the top of the range, where one size costs 10 mm of outside diameter. Check terminal-box clearance before you substitute a DL for a DT, because the aluminium part is fatter even though the conductor is the same.

The ranges do not match either. DT starts at 10 mm² and reaches 1000; DL starts at 16 and stops at 800. If you need 10 mm² there is no aluminium lug, and above 800 there is no aluminium lug at all.

What the code tells you

The old catalogue prints DL, the standard prints DLM. The 2020 sample book writes DL-120; GB/T 14315 writes DLM-120, where the M means sealed. Both names are in circulation, and the shorter one is the one your buyer is most likely to send you.

On the paper Standard designation What it actually is Table below
DL-120 (2020 sample book) DLM-120 sealed, solid bar 1
DL-120S no standard code — S is trade shorthand sealed, two-hole palm 2
DL-120 from an alloy-conductor enquiry DLM-120 same code, different bore 3

DLM is the single-hole sealed lug, machined from solid aluminium bar with the barrel closed so oil cannot wick along the strands. Same barrel logic as the copper DTM, and the same reason: transformer leads and oil-filled terminations.

S means two holes, and it drops the M. The two-hole palm is DL-S, so DL-120S, never DLM-120S. The palm table adds L2 palm length and L3 hole spacing.

Square head at the top. DLM-630 and DLM-800 carry no Ø figure — the palm is a square block and the hole is drilled to your stud. From DLM-630 up there is no catalogue hole to choose from.

The two-hole palm takes a smaller hole. DL-300S is drilled 16.5 where DLM-300 is 21.0, for the same reason as on copper: two holes need metal between them, and it comes out of the palm width.

The bore is the dimension you cannot fix later

Everything else on a lug can be changed at the die level: palm length, palm angle, hole position, plating. The bore cannot. It has to match the actual conductor.

Nominal mm² is not enough. Flexible Class 5 and 6 cable is fatter than Class 2 at the same figure, and an aluminium conductor compacts under the die differently from copper. Measure the conductor, or tell us the cable type and class.

Aluminium handling — this is where DL joints fail

The lug is not the hard part. The installation is.

  • Brush the conductor and the bore immediately before crimping, and apply contact paste. Aluminium oxide re-forms within minutes in humid air and it is an insulator. This single step separates a joint that lasts from one that does not.
  • Crimp to full die closure, not to a “feel”. Aluminium needs more deformation than copper to break the oxide and fill the barrel.
  • Re-torque after the first thermal cycle. Aluminium creeps under bolt preload and copper does not do so to the same degree. A joint that was correct at installation can be loose a year later, and the first hot summer finds it.
  • Seal the mouth outdoors, in cable pits and in manholes.

Never put a copper lug on aluminium

Copper against aluminium with moisture between them is a galvanic cell. The aluminium corrodes, the joint resistance climbs, and the failure is invisible until the terminal runs hot.

Two ways out, both welded rather than pressed:

And the reverse — an aluminium lug on a copper conductor — is just as wrong.

Standards

Made to GB/T 14315-2008 — compression terminal lugs and ferrules for power cable conductors up to 35 kV, aluminium 16–630 mm². Test methods GB/T 9327-2008, international counterpart IEC 61238-1.

The 800 sizes sit outside that table. GB/T 14315-2008 covers aluminium to 630 mm², but DLM-800 is made and shipped. It is produced to drawing and tested to the same methods — pull-out, temperature rise, thermal cycling, DC resistance across the joint — but it is not a row in the standard, so do not write “to GB/T 14315” against an 800 order without saying so.

Installation

  1. Strip to the barrel depth — the palm end, not past it.
  2. Brush and paste. Mandatory. Both the conductor strands and the bore.
  3. Insert fully and mark the strip length first — the single-hole DLM has no peep hole.
  4. Crimp from the palm end outward, one hexagonal crimp per 15–20 mm, each overlapping the previous by a third.
  5. Full die closure — a regular hexagon, die faces meeting.
  6. Seal the mouth outdoors and underground.
  7. Re-torque the palm bolts after the first load cycle.

Where these joints fail

  • The wrong set. Alloy conductor with the oil-sealed DLM, or the reverse. Same code, wrong bore.
  • No oxide removal. The crimp looks perfect and measures badly.
  • Bore matched to nominal mm² instead of the conductor diameter.
  • Not re-torqued. Aluminium creep loosens the palm over the first year.
  • A DL substituted for a DT without checking clearance. The aluminium part is 2 to 10 mm fatter.

FAQ

Is DLM the same as DT, just in aluminium? No. Same conductor, same crimping method, different dimensions. The bore is nearly identical, but the outside diameter is 2 mm larger at 35 mm² and 10 mm larger at 800, and the range stops at 800 where copper reaches 1000. See the table above before substituting.

Which set do I need — the sealed DLM or the alloy one? Tell us the conductor: plain EC-grade aluminium, or aluminium alloy (AAAC / 6201 type). The two sets share model codes and are not interchangeable. For plain stranded aluminium it is the oil-sealed set; for alloy it is the other one.

DLM or DL-S? One hole or two. DLM-120 for a single stud; DL-120S for a pad with two bolts so the palm cannot rotate. L3 is the hole spacing.

Can I get DLM-1000? No. The aluminium range stops at DLM-800. Above that the conductor takes a different terminal design altogether, so send the drawing.

What about a waterproof version? DTL-F is the bimetal one, with a sealing sleeve at the mouth that closes onto the insulation after the crimp. For an all-aluminium joint in a pit or a manhole, ask — the sealing sleeve is the part that matters, not the lug.

Technical Parameters

1. DLM — aluminium terminal, single hole, oil-sealed

DLM aluminium terminal drawingDLM aluminium terminal dimensions

ModelMain Dimensions (mm)
ØDdLWS
DLM-168.4105.570163.0
DLM-258.4127.075183.5
DLM-3510.5148.585203.5
DLM-5010.5169.590234.0
DLM-7012.51812.0102264.5
DLM-9512.52113.0112285.0
DLM-12014.52315.0120305.5
DLM-15014.52516.0126346.0
DLM-18516.52718.0133376.5
DLM-24016.53020.0140407.5
DLM-30021.03423.0165458.5
DLM-40021.03826.0170529.5
DLM-50021.04229.01906010.0
DLM-630Square Head5434.02257810.5
DLM-800Square Head6038.027010011.0

Aluminium barrel walls run thicker than copper for the same conductor: compare DLM-120 (D = 23) with DTM-120 (D = 20). From DLM-630 up the palm is a square block and the hole is drilled to your stud.

2. DL-S — aluminium terminal, two-hole palm

DLM two-hole aluminium terminal

DLM two-hole terminal drawingDLM two-hole terminal dimensions

ModelMain Dimensions (mm)
ØDdLL2L3WS
DL-16S8.4105.5904520183.0
DL-25S8.5127.093.54420183.2
DL-35S10.5148.510448.520203.6
DL-50S10.5169.51125020234.0
DL-70S12.51812.01255925264.5
DL-95S12.52113.01366025284.8
DL-120S14.52315.01456930305.5
DL-150S14.52516.01507030346.0
DL-185S14.52718.01627635376.5
DL-240S14.53020.01707835407.0
DL-300S16.53423.01908740458.5
DL-400S21.03826.01958740508.5
DL-500S21.04230.01959545609.5
DL-630S21.04534.520095456010.5

The same 16.5 against 21.0 split appears at DL-300S against DLM-300, and here it runs up to DL-630S, which stays at 21.0 where the single-hole DLM-630 has no catalogue hole at all.

3. DLM — aluminium terminal, for aluminium alloy conductor

DLM aluminium alloy conductor terminal

DLM alloy terminal drawing

ModelMain Dimensions (mm)
ØDdLWS
DLM-168.5106.075163.5
DLM-258.5127.075183.5
DLM-3510.5148.590234.3
DLM-5010.5169.792234.8
DLM-7010.51811.5110285.2
DLM-9510.52113.5112285.7
DLM-12012.52315.0125346.8
DLM-15012.52516.5127347.0
DLM-18512.52718.5140407.8
DLM-24012.53021.0142408.3
DLM-30016.53423.0160459.0

Same model numbers as table 1 but a different palm hole and wall — this set is for aluminium alloy conductor. Quote with the conductor type as well as the mm².

Note: Dimensions may vary slightly with manufacturing tolerance. Where the Ø column reads Square Head the palm is a square block and the hole is drilled to your stud; on every other size the Ø shown is the catalogue hole. The bore d is set by the conductor and is not a custom dimension.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: